Johnson Controls TEC200x-4 Series, TEC200x-4+PIR Series Catalog Page

Code No. LIT-1900625
TEC200x-4 Wireless Thermostat Controller and
TEC20 Coordinator with Direct-Mount Antenna
and Remote Mount Antenna
Issued July 16, 2010
TEC200x-4 and TEC200x-4+PIR Series
Wireless Thermostat Controller System for Staged Equipment
The TEC200x-4 and TEC200x-4+PIR Series Wireless Thermostat Controller System provides wireless networked control of Heating, Ventilating, and Air Conditioning (HVAC) equipment on a Building Automation System (BAS) that enables remote monitoring and programming.
The TEC200x-4+PIR Series Wireless Thermostat Controllers have occupancy sensing capability built into the device. These devices provide energy savings in high-energy usage light commercial buildings such as schools and hotels. The devices maximize these energy savings by using additional setpoint strategies during occupied times.
This system integrates into a supervisory controller that uses BACnet® Internet Protocol (IP) or BACnet Master-Slave/Token-Passing (MS/TP) communications.
TEC20 Coordinators allow the supervisory controller to communicate with multiple TEC Wireless Thermostat Controllers. The TEC200x-4 and TEC200x-4+PIR Series Wireless Thermostat Controllers provide networked control of a variety of staged equipment:
• TEC2001-4(+PIR) Single-Stage Wireless Thermostat Controllers control fan coil units, unit heaters, and single-stage packaged heating/cooling equipment
• TEC2002-4(+PIR) Heat Pump Wireless Thermostat Controllers control heat pumps with up to three heating and two cooling stages
• TEC2003-4(+PIR) Multi-Stage Wireless Thermostat Controllers control multi-stage packaged heating/cooling equipment
• TEC2004-3(+PIR) Multi-Stage Economizer Wireless Thermostat Controllers control economizer operation for single- and multi-stage unitary rooftop equipment
The wireless mesh network uses ZigBee™ technology to enable remote monitoring and programming and to enhance reliability by providing redundant transmission paths through other TEC200x-4 and TEC200x-4+PIR Wireless Thermostat Controllers, creating a resilient, self-healing mesh network.
Refer to the TEC200x-4 and TEC200x-4+PIR Series Wireless
Thermostat Controller System for Staged Equipment Product Bulletin (LIT-12011590) for important product application information.
Features
• wireless communication — allows BAS communications capability in applications where field bus wiring within the building is prohibitive
• integral wireless signal strength testing built into wireless thermostat controllers and coordinators — provides quick, easy, visual indication of the wireless Radio Frequency (RF) signal strength between a sensor and associated receiver; helps locate optimum device positions during installation; and aids troubleshooting your applications
• onboard occupancy sensor (Passive Infrared [PIR] Models) — provides energy savings without additional installation time and cost
• password protection option — protects against unwanted thermostat controller tampering
• backlit Liquid Crystal Display (LCD) — offers real-time control status of the environment in easy-to-read, English text messages with constant backlight that brightens during user interaction
• two configurable digital inputs on all models — provide additional inputs for advanced functions such as remote night setback, service or filter alarms, or occupancy override
• over 20 configurable parameters — enable the TEC200x-4 and TEC200x-4+PIR Series Wireless Networked Thermostat Controllers to adapt to any application, allowing installer parameter access without opening the cover
• Economizer output (TEC2004-4 and TEC2004-4+PIR models) — provides control of economizer operation for single- and multi-stage unitary rooftop equipment
• optional discharge air sensor — monitors unit efficiency
Applications
The TEC200x-4 and TEC200x-4+PIR Series Wireless Thermostat Controller System is ideal for any location where it is cost-prohibitive, difficult, or aesthetically unappealing to hard wire between BACnet devices, including supervisory controllers (such as NCE25 or NAE35/ 45/55 engines) and thermostat controllers. Examples of these locations include the following:
• commercial structures with brick or solid concrete walls and/or ceilings that impede hard-wired TEC200x-4 and TEC200x-4+PIR Series Thermostat Controller applications
• office buildings, retail stores, and other commercial real estate where tenant turnover is frequent
• museums, historical buildings, atriums, and other sites where building aesthetics and historical preservation are important
• buildings with marble, granite, glass, mirrored, wood veneer, or other decorative surfaces that present challenges to hard-wired applications
• buildings with asbestos or other hazardous materials that must not be penetrated or disturbed
• buildings with occupants sensitive to disruptions to business
Locations or applications that prohibit cellular telephones or Wireless Fidelity (WiFi) systems are unsuitable for the TEC200x-4 and TEC200x-4+PIR Series Wireless Thermostat Controller System:
• operating rooms or radiation therapy rooms
• validated environments
• UL 864 applications
Repair Information
If the TEC200x-4 and TEC200x-4+PIR Series Wireless Thermostat Controller System for Staged Equipment fails to operate within its specifications, replace the unit. For a replacement, contact the nearest Johnson Controls® representative.
The performance specifications are nomina l and conf orm to accep table industr y standar ds. For ap plications a t condition s beyond th ese specification s, consult the local Johnson Controls o ffice. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2012 Johnson Controls, Inc.
1 of 3
www.johnsoncontrols.com
TEC200x-4 and TEC200x-4+PIR Series Wireless Thermostat Controller System for Staged Equipment (Continued)
Selection Charts
TEC200x-4 and TEC200x-4+PIR Series Wireless Thermostat Controller Models
Code Number Description Applications
TEC2001-4 Single-Stage Fan Coil Units, Unit Heaters, and Single-Stage Packaged Heating/Cooling Equipment TEC2001-4+PIR Single-Stage with Onboard Occupancy
TEC2002-4 Heat Pump One or Two Heat Pump Stages with Optional Auxiliary Heat Stage TEC2002-4+PIR Heat Pump with Onboard Occupancy
TEC2003-4 Multi-Stage Multi-Stage Packaged Heating/Cooling Equipment TEC2003-4+PIR Multi-Stage with Onboard Occupancy
TEC2004-4 Multi-Stage Economizer Economizer Operation for Single- and Multi-Stage Unitary Rooftop Equipment TEC2004-4+PIR Multi-Stage Economizer with Onboard
TEC20 Coordinators
Code Number Description
TEC20-3C-2 BACnet IP Wireless Coordinator; Requires 15 VDC Power Supply TEC20-6C-2 BACnet MS/TP Wireless Coordinator; Requires 15 VDC Power Supply
TEC Wireless Accessories (Order Separately)
Code Number Description
SEN-600-1 Remote Indoor Air Temperature Sensor SEN-600-4 Remote Indoor Air Temperature Sensor with Occupancy Override and LED
TEC-3-PIR TE-6361M-1
TE-636S-1 Strap-Mount Temperature Sensor TE-6363P-1
TEC20-A-1 Replacement Antenna for TEC20 Coordinator TEC20-RA-1 NPB-PWR
TEC20-8X-1 120 VAC to 15 VDC Power Supply for TEC20 Coordinator TEC20-9B-1 Replacement Battery Pack for TEC20 Coordinator
1. The TEC-3-PIR Accessory Cover can be used to replace the existing cover on a non-PIR TEC200x-4 Thermostat Controller to provide occupancy sensing
2. Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the TE-6300Series Temperature Sensors Product
3. This antenna is used when the TEC Coordinator is installed inside a metal cabinet, or when a remote antenna is required by physical installation.
4. DIN Rail: Type NS35/7.5 (35 x 7.5 mm) and DIN rail end clips. Length of DIN rail depends on the number of DIN rail mounted options.
1
2
2
3
4
capability. Bulletin (LIT-216320) for more details.
Sensor
Sensor
Sensor
Occupancy Sensor
Cover with Occupancy Sensor Duct Mount Air Temperature Sensor
Outside Air Temperature Sensor
Remote Antenna for TEC20 Coordinator DIN Rail Mount 24 VAC/DC Power Module for TEC20 Coordinator
Technical Specifications
TEC20 Wireless Coordinator (Part 1 of 2)
Product Code Numbers TEC20-3C-2: BACnet IP Version
Power Requirements 15 VDC, 6 W Maximum Platform IBM® PowerPC® 405EP 250 MHz Processor
Operating System Niagra Communications Ethernet: Two 10/100 Mbps Ports (RJ-45 Connection)
Transmission Range Through Walls: 10 m (30 ft)
RF Band Direct-Sequence, Spread-Spectrum Transmission; 2.4 Ghz Unlicensed Band Transmission Power 10 mW Maximum Wire Size 18 AWG Maximum, 22 AWG Re commended
The performance specifications are nomina l and conf orm to accep table industr y standar ds. For ap plications a t condition s beyond th ese specification s, consult the local Johnson Controls o ffice. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2012 Johnson Controls, Inc.
TEC20-6C-2: BACnet MS/TP Version
64 MB SDRAM and 64 MB Serial Flash Battery Backup - Shutdown Begins within 10 Seconds Real-Time Clock - 3 Month Backup Maximum with Battery
AX
RS-232: 9-Pin D-Shell Connection RS-485: 3-Pin Non-Isolated Port
Line-of-Sight (Open Space): 30 m (100 ft)