Wireless Thermostat Controller System for Staged Equipment
Description
The TEC200x-4 and TEC200x-4+PIR Series Wireless Thermostat
Controller System provides wireless networked control of Heating,
Ventilating, and Air Conditioning (HVAC) equipment on a Building
Automation System (BAS) that enables remote monitoring and
programming.
The TEC200x-4+PIR Series Wireless Thermostat Controllers have
occupancy sensing capability built into the device. These devices
provide energy savings in high-energy usage light commercial
buildings such as schools and hotels. The devices maximize these
energy savings by using additional setpoint strategies during occupied
times.
This system integrates into a supervisory controller that uses BACnet®
Internet Protocol (IP) or BACnet Master-Slave/Token-Passing (MS/TP)
communications.
TEC20 Coordinators allow the supervisory controller to communicate
with multiple TEC Wireless Thermostat Controllers. The TEC200x-4
and TEC200x-4+PIR Series Wireless Thermostat Controllers provide
networked control of a variety of staged equipment:
• TEC2001-4(+PIR) Single-Stage Wireless Thermostat Controllers
control fan coil units, unit heaters, and single-stage packaged
heating/cooling equipment
• TEC2002-4(+PIR) Heat Pump Wireless Thermostat Controllers
control heat pumps with up to three heating and two cooling stages
• TEC2004-3(+PIR) Multi-Stage Economizer Wireless Thermostat
Controllers control economizer operation for single- and multi-stage
unitary rooftop equipment
The wireless mesh network uses ZigBee™ technology to enable
remote monitoring and programming and to enhance reliability by
providing redundant transmission paths through other TEC200x-4 and
TEC200x-4+PIR Wireless Thermostat Controllers, creating a resilient,
self-healing mesh network.
Refer to the TEC200x-4 and TEC200x-4+PIR Series Wireless
Thermostat Controller System for Staged Equipment Product Bulletin
(LIT-12011590) for important product application information.
Features
• wireless communication — allows BAS communications capability
in applications where field bus wiring within the building is
prohibitive
• integral wireless signal strength testing built into wireless thermostat
controllers and coordinators — provides quick, easy, visual
indication of the wireless Radio Frequency (RF) signal strength
between a sensor and associated receiver; helps locate optimum
device positions during installation; and aids troubleshooting your
applications
• onboard occupancy sensor (Passive Infrared [PIR] Models) —
provides energy savings without additional installation time and cost
• backlit Liquid Crystal Display (LCD) — offers real-time control status
of the environment in easy-to-read, English text messages with
constant backlight that brightens during user interaction
• two configurable digital inputs on all models — provide additional
inputs for advanced functions such as remote night setback, service
or filter alarms, or occupancy override
• over 20 configurable parameters — enable the TEC200x-4 and
TEC200x-4+PIR Series Wireless Networked Thermostat
Controllers to adapt to any application, allowing installer parameter
access without opening the cover
• Economizer output (TEC2004-4 and TEC2004-4+PIR models) —
provides control of economizer operation for single- and multi-stage
unitary rooftop equipment
• optional discharge air sensor — monitors unit efficiency
Applications
The TEC200x-4 and TEC200x-4+PIR Series Wireless Thermostat
Controller System is ideal for any location where it is cost-prohibitive,
difficult, or aesthetically unappealing to hard wire between BACnet
devices, including supervisory controllers (such as NCE25 or NAE35/
45/55 engines) and thermostat controllers. Examples of these
locations include the following:
• commercial structures with brick or solid concrete walls and/or
ceilings that impede hard-wired TEC200x-4 and TEC200x-4+PIR
Series Thermostat Controller applications
• office buildings, retail stores, and other commercial real estate
where tenant turnover is frequent
• museums, historical buildings, atriums, and other sites where
building aesthetics and historical preservation are important
• buildings with marble, granite, glass, mirrored, wood veneer, or
other decorative surfaces that present challenges to hard-wired
applications
• buildings with asbestos or other hazardous materials that must not
be penetrated or disturbed
• buildings with occupants sensitive to disruptions to business
Locations or applications that prohibit cellular telephones or Wireless
Fidelity (WiFi) systems are unsuitable for the TEC200x-4 and
TEC200x-4+PIR Series Wireless Thermostat Controller System:
• operating rooms or radiation therapy rooms
• validated environments
• UL 864 applications
Repair Information
If the TEC200x-4 and TEC200x-4+PIR Series Wireless Thermostat
Controller System for Staged Equipment fails to operate within its
specifications, replace the unit. For a replacement, contact the nearest
Johnson Controls® representative.
TEC200x-4 and TEC200x-4+PIR Series Wireless Thermostat Controller System for
Staged Equipment (Continued)
Selection Charts
TEC200x-4 and TEC200x-4+PIR Series Wireless Thermostat Controller Models
Code NumberDescriptionApplications
TEC2001-4Single-StageFan Coil Units, Unit Heaters, and Single-Stage Packaged Heating/Cooling Equipment
TEC2001-4+PIRSingle-Stage with Onboard Occupancy
TEC2002-4Heat PumpOne or Two Heat Pump Stages with Optional Auxiliary Heat Stage
TEC2002-4+PIRHeat Pump with Onboard Occupancy
TEC2003-4Multi-StageMulti-Stage Packaged Heating/Cooling Equipment
TEC2003-4+PIRMulti-Stage with Onboard Occupancy
TEC2004-4Multi-Stage Economizer Economizer Operation for Single- and Multi-Stage Unitary Rooftop Equipment
TEC2004-4+PIRMulti-Stage Economizer with Onboard
TEC20 Coordinators
Code NumberDescription
TEC20-3C-2BACnet IP Wireless Coordinator; Requires 15 VDC Power Supply
TEC20-6C-2BACnet MS/TP Wireless Coordinator; Requires 15 VDC Power Supply
TEC Wireless Accessories (Order Separately)
Code NumberDescription
SEN-600-1Remote Indoor Air Temperature Sensor
SEN-600-4Remote Indoor Air Temperature Sensor with Occupancy Override and LED
TEC-3-PIR
TE-6361M-1
TE-636S-1Strap-Mount Temperature Sensor
TE-6363P-1
TEC20-A-1Replacement Antenna for TEC20 Coordinator
TEC20-RA-1
NPB-PWR
TEC20-8X-1120 VAC to 15 VDC Power Supply for TEC20 Coordinator
TEC20-9B-1Replacement Battery Pack for TEC20 Coordinator
1. The TEC-3-PIR Accessory Cover can be used to replace the existing cover on a non-PIR TEC200x-4 Thermostat Controller to provide occupancy sensing
2. Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the TE-6300Series Temperature Sensors Product
3. This antenna is used when the TEC Coordinator is installed inside a metal cabinet, or when a remote antenna is required by physical installation.
4. DIN Rail: Type NS35/7.5 (35 x 7.5 mm) and DIN rail end clips. Length of DIN rail depends on the number of DIN rail mounted options.
1
2
2
3
4
capability.
Bulletin (LIT-216320) for more details.
Sensor
Sensor
Sensor
Occupancy Sensor
Cover with Occupancy Sensor
Duct Mount Air Temperature Sensor
Outside Air Temperature Sensor
Remote Antenna for TEC20 Coordinator
DIN Rail Mount 24 VAC/DC Power Module for TEC20 Coordinator
Technical Specifications
TEC20 Wireless Coordinator (Part 1 of 2)
Product Code NumbersTEC20-3C-2: BACnet IP Version
Power Requirements15 VDC, 6 W Maximum
PlatformIBM® PowerPC® 405EP 250 MHz Processor
Operating SystemNiagra
CommunicationsEthernet: Two 10/100 Mbps Ports (RJ-45 Connection)
Transmission RangeThrough Walls: 10 m (30 ft)
RF BandDirect-Sequence, Spread-Spectrum Transmission; 2.4 Ghz Unlicensed Band
Transmission Power10 mW Maximum
Wire Size18 AWG Maximum, 22 AWG Re commended
64 MB SDRAM and 64 MB Serial Flash
Battery Backup - Shutdown Begins within 10 Seconds
Real-Time Clock - 3 Month Backup Maximum with Battery
AX
RS-232: 9-Pin D-Shell Connection
RS-485: 3-Pin Non-Isolated Port
Line-of-Sight (Open Space): 30 m (100 ft)
www.johnsoncontrols.com
2 of 3
TEC200x-4 and TEC200x-4+PIR Series Wireless Thermostat Controller System for
Staged Equipment (Continued)
TEC20 Wireless Coordinator (Part 2 of 2)
Ambient ConditionsOperating: 0 to 50°C (32 to 122°F); 95% RH Maximum, Noncondensing
ComplianceUnited States:
Shipping Weight1.1 lb (0.499 kg)
Power Requirements19 to 30 VAC, 50/60 Hz, 2 VA (Terminals RC and C) at 24 VAC Nominal, Class 2 or SafetyExtra-Low Voltage
Economizer Output Rating TEC2004-4 and TEC2004-4+PIR Models: 0 to 10 VDC into 2k ohm Resistance (Minimum)
Relay/Triac Contact Rating19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush, Class 2 or SELV
Digital InputsVoltage-Free Contacts across Terminal C to Terminals DI1 and DI2
Transmission RangeThrough Walls: 10 m (30 ft)
RF BandDirect-Sequence, Spread-Spectrum Transmission; 2.4 Ghz Unlicensed Band
Transmission Power10 mW Maximum
Wire Size18 AWG Maximum, 22 AWG Recommended
Temperature Sensor TypeLocal 10k ohm Negative Temperature Coefficient (NTC) Thermistor
Resolution±0.1C°/±0.2F°
AccuracyTemperature: ±0.5C°/±0.9F° at 21.0°C/70.0°F Typical Calibrated
Temperature RangeBacklit Display: -40.0°C/ -40.0°F to 50.0°C/122.0°F
Auxiliary/Outdoor Air Temperature
Indication Range
Minimum Deadband1C°/2F° between Heating and Cooling
Ambient ConditionsOperating: 0 to 50°C (32 to 122°F); 95% RH Maximum, Noncondensing
ComplianceUnited States:
Shipping WeightTEC200x-4 Models: 0.34 kg (0.75 lb)
Storage: -20 to 60°C (-4 to 140°F); 95% RH Maximum, Noncondensing
UL Listed, File E27734, CCN XAPX, Under UL 873, Temperature Indicating and Regulating Equipment
FCC Compliant to CFR 47, Part 15, Subpart B and Part 15 Class A
Canada:
C-UL Listed, File E207782, CCN XAPX7, Under CAN/CSA C22.2 No. 24, Temperature Indicating an d Regulating
Equipment, and C22.2 No. 205-M1983 Signal Equipment
Industry Canada, ICES-003
TEC200x-4 and TEC200x-4+PIRWireless Thermostat Controllers
(SELV)
Line-of-Sight (Open Space): 30 m (100 ft)
Heating Control: 40.0°F/4.5°C to 32.0°C/ 90.0°F in 0.5° Increments
Cooling Control: 54.0°F/12.0°C to 38.0°C/100.0°F in 0.5° Increments
-40.0°C/-40.0°F to 50.0°C/122.0°F
Storage: -30 to 50°C (-22 to 122°F); 95% RH Maximum, Noncondensing
UL Listed, File E27734, CCN XAPX, Under UL 873, Temperature Indicating and Regulating Equipment
FCC Compliant to Part 15.247 Regulations for Low Power Unlicensed Transmitters
Canada:
UL Listed, File E27734, CCN XAPX7, Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating