Johnson Controls TEC2004-4, TEC2004-4+PIR Installation Instructions Manual

Page 1
TEC2004-4 and TEC2004-4+PIR Multi-Stage Economizer Wireless Thermostat Controller
Installation Instructions
TEC2004-4 and TEC2004-4+PIR
Part No. 24-9890-1168, Rev. B
Issued July 13, 2010
Supersedes May 17, 2010
Applications
The TEC Series Wireless Thermostat Controller System provides wireless networked control of Heating, Ventilating, and Air Conditioning (HVAC) equipment on a Building Automation System (BAS) that enables remote monitoring and programming. This TEC Series System integrates into a supervisory controller that uses BACnet® Internet Protocol (IP) or BACnet Master-Slave/Token-Passing (MS/TP) communications.
TEC20 Coordinators allow the supervisory controlle r to communicate with multiple TEC Wireless Thermostat Controllers. TEC200x-4 Series Wireless Thermostat Controllers provide networked control of a variety of staged equipment. TEC2004-4 and TEC2004-4+PIR Multi-Stage Economizer Wireless Thermostat Controllers control economizer operation for single­and multi-stage unitary rooftop equipment.
The TEC2004-4+PIR Thermostat Controller provides advanced active occupancy logic that automatically switches occupancy from Occupied to Unoccupied as required by the presence of local activity. See the
Occupancy Sensor Operation – TEC2004-4+PIR Thermostat Controller section for more information.
The wireless mesh network uses ZigBee™ technology to enable remote monitoring and programming and to enhance reliability by providing redundant transmission paths through other TEC Wireless Thermostat Controllers, creating a resilient, self-healing mesh network.
IMPORTANT: The TEC2004-4 and TEC2004-4+PIR Wireless Thermostat Controllers are intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the thermostat controller could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the thermostat controller.
North American Emissions Compliance
United States
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense.
RF Transmitters: Compliance Statement (Part 15.19)
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received, including interference that may cause undesired operation.
Warning (Part 15 .21)
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
TEC2004-4 and TEC2004-4+PIR Multi-Stage Economizer Wireless Thermostat
1
Controller Installation Instructions
Page 2
Canada
Figure 1: Removing the Thermostat Controller
Cover (TEC2004-4+PIR Model Shown)
FIG:cvr_ rmvl
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
RF Transmitter s: Industry Canada Statement
The term IC before the certification/registration number only signifies that the Industry Canada technical specifications were met.
Le terme « IC » précédant le numéro d'accré ditation / inscription signifie simplement que le produit est conforme aux spécifications techniques d'Industrie Canada.
Installation
Location Considerations
Locate a thermostat controller:
on a partitioning wall, approximately 1.5 m (5 ft) above the floor in a location of average temperature
For detailed information on locating devices for optimum signal strength, refer to the Wireless Metasys System Location Guide (LIT-12011294).
Installing the Thermostat Controller
Follow these steps to install the thermostat controller:
1. Use a Phillips-head screwdriver to remove the security screw if it is installed on the bottom of the thermostat controller cover.
Note: Normally, the security screw is packaged separately in a plastic bag with the thermostat controller. Skip this step if the screw is not installed on the bottom of the cover.
2. Pull the bottom edge of the cover and open the thermostat controller as illustrated in Figure 1.
Note: PIR Models have a wiring connection between the cover and the Printed Circuit Board (PCB). This connection allows for proper wiring of the occupancy sensor . Car efully remove the wiring connection from the PCB by pulling up on the connector block. Do not attempt to remove the connector block by pulling on the wires.
away from direct sunlight, radiant heat, outside walls, outside doors, air discharge grills, or stairwells, or from behind doors
away from steam or water pipes, warm air stacks, unconditioned areas (not heated or cooled), or sources of electrical interference
For integrated Passive Infrared (PIR) models, make sure the thermostat controller is located centrally, where occupant movement is frequent.
Note: Allow for vertical air circulation to the thermostat controller.
Wireless Signal Transmission Range
Line-of-sight transmission ranges between a TEC20 Coordinator and a TEC Wireless Thermostat Controller (or between TEC Wireless Thermostat Controllers) can be less than the recommended distances shown in Table 1. The effective transmission range for indoor applications varies because of Radio Frequency (RF) signal absorption and re flectio n due to metal obstructions, walls (or floors), and furniture found
in typical building interiors.
Table 1: Recommended Transmission Ranges
Type Distance
Through Walls 10 m (32.8 ft) Open Space 30 m (98.4 ft)
TEC2004-4 and TEC2004-4+PIR Multi-Stage Economizer Wireless Thermostat Controller
2
Installation Instructions
Page 3
3. Carefully pull the locking tabs on the right side of
Figure 2: Opening the PCB
Tabs
F
I
G
Figure 3: Securing the Mounting Base to the Wall
F
I
G
:
m
n
t
n
g
_
b
s
Figure 4: Removing the Screw Terminal Blocks
the mounting base and unlock the PCB. Open the PCB to the left as illustrated in Figure 2.
PCB Locking
d
r b
_
t
c
r
c
_ d
t
n
r
p
:
4. Pull approximately 152 mm (6 in.) of wire from the wall and insert the wire through the hole in the mounting base.
5. Align the mounting base on the wall and use the base as a template to mark the two mounting hole locations.
6. Position the mounting base so that the arrow on the base points upward to indicate the top of the thermostat controller.
Note: If you need to install the thermostat on an electrical junction box, use 2-1/2 x 4 in. (63 x 101 mm) square boxes with mud ring covers, and avoid smaller 1-1/2 x 4 in. (38 x 101 mm) square or 3 x 2 in. (76 x 51 mm) boxes. This procedure ensures you have enough space for cabling and end-of-line devices, if needed.
Note: For surface-mount applications, use durable mounting hardware, such as Molly bolt anchors, that cannot be easily pulled out of the mounting surface.
Note: Be careful not to overtighten the mounting screws.
8. Swing the PCB back to the right and carefully snap it into the locking tabs on the mounting base.
9. Remove the screw terminal blocks that are attached to a disposable adhesive. Figure 4 illustrates the locations of the screw terminal blocks on the thermostat controller.
s k
c
l
b
_
l
n m
r
t
: G
I F
7. Secure the mounting base to the wall surface using two mounting screws as illustrated in Figure 3.
TEC2004-4 and TEC2004-4+PIR Multi-Stage Economizer Wireless Thermostat Controller
3
Installation Instructions
Page 4
Wiring
!
!
24 VAC
Thermostat Power
Y2 Y1
RC C
If using the same power source install a jump er ac ros s RC and RH .
Heat 1
Heat 2
RH W1 W2
Cool 1
Energizes on a Call for First-Stage Cooling
24 VAC from Equipment Transformer 24 VAC (Common) from Equipment Transformer 24 VAC for Heating Stages Energizes on a Call for First-Stage Heati ng Energizes on a Call for Second-Stage Heati ng Auxiliary O utp ut Configurable Di gital Input 1 Configurable Di gital Input 2 Remote Room Sensor Sensor Common Auxiliary/O utdoor Air Sensor Remote Monitoring Supply Temperature Sensor 0 to 10 VDC Economizer Actuator Output
Function
Y1 Y2
G
RC
C RH W1 W2
Aux
DI1 DI2 RS
Scom
OS MS EC
Terminal
RS
• Ligh t ing
• On/Off Actuation
• Exhaust Fan
Outdoor
EC
0 to 10
VDC
24 VAC
Common
Supply Sensor
Cool 2
FIG:wrng_2004-4
Y2
G
C
RS
Three-Pole Right Top Connector
Eight-Pole Bottom Connector
OS
EC
G
Fan
Room
Figure 5: Wiring the TEC2004-4 or TEC2004-4+PIR Thermostat Controller
CAUTION: Risk of Electric Shock.
Disconnect power supply before making electrical connections to avoid electric shock.
CAUTION: Risk of Property Damage.
Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment.
To wire the thermostat controller:
1. Strip the ends of each wire 6 mm (1/4 in.) and connect them to the appropriate screw terminals as indicated in Figure 5.
Note: If multiple wires are inserted into the screw terminals, be sure to properly twist the wires together prior to inserting them into the screw terminals.
2. Carefully push any excess wire back into the wall. Note: Seal the hole in the wall with fireproof
material to prevent drafts from affecting the ambient temperature readings.
IMPORTANT: Make all wiring connections in accordance with local, national, and regional regulations. Do not exceed the electrical ratings of the thermostat controller.
When replacing an existing thermostat controller, remove and label the wires to identify the terminal functions. When replacing a thermostat controller of the same model, simply remove the old screw terminal blocks and reinsert them onto the PCB of the replacement thermostat controller.
Energizes on a Call for Second-Stage Cooling Energizes Fan in Accordance with the Selected Fan Mode
for the thermostat and heating loads,
3. Reinsert the screw terminal blocks onto the PCB.
4. Reattach the cover to the mounting base (top side first).
5. Use a Phillips-head screwdriver to reinstall the security screw on the bottom of the cover.
See Figure 5 for information on wiring the thermostat controllers.
Five-Pole Left Top Connector
Aux
Aux
Aux Contact (High Side Common)
DI2
DI1
Y1
Aux
Scom
Remote
Sensor
RC
DI1 DI2
OS
Auxiliary/
Air Sensor
RH W1 W2
Scom
Remote
Monitoring
Temperature
MS
TEC2004-4 and TEC2004-4+PIR Multi-Stage Economizer Wireless Thermostat Controller
4
Installation Instructions
Page 5
Figure 6: Front Cover of Thermostat Controller (TEC2004-4+PIR Model Shown)
FIG:TEC2004-4_frnt
70.0ºF
Room Temp
Backl i t, plain t ex t
Liquid Crystal Display (LCD)
is easy to rea d in any condition.
Five keys on the thermostat control l er make operation easy and intuitive.
indicate system activi t y.
Status LED beneath c over
indicates network status.
PIR motion detector
saves ener gy using
standby setpoints.
Light-Emitting Diodes (LEDs)
Setup and Adjustments
Thermostat Controller User Interface Keys
The user interface consists of keys on the front cover (Figure 6). The function of each key is as follows:
•Use the YES key to:
- confirm menu selections and to advance to the next menu item
- stop the Status Display Menu from scrolling and to manually scroll to the next parameter on the menu
Note: When the thermost at controller is left unattended for 45 seconds, the display resumes scrolling.
•Use the NO key to decline a parameter change and advance to the next menu item.
•Use the MENU key to:
- access the Main User Menu or to exit the menu
(See the Main User Menu
- access the Installer Configuration Menu or to
exit the menu (See the Configuring the Thermostat Controller section.)
section.)
Light-Emitting Diodes (LEDs)
Three LEDs are included to indicate the fan status, call for heat, or call for cooling:
The fan LED is on when the fan is on.
The heat LED is on when heating is on.
The cool LED is on when cooling is on. The Status LED, located beneath the cover, flashes at
5-second intervals to provide indication of the network status of the thermostat controller. See Table 2.
Table 2: Status LED
Flashes per 5-Second Interval
1 Power On 2 Power On, Communicating 3 Power On, Communicating, Found
4 Power On, Communicating, Found
Condition Indicated
Wireless Network
Wireless Network, Communicating with TEC20 Coordinator
configuration parameters and activate a setpoint adjustment.
TEC2004-4 and TEC2004-4+PIR Multi-Stage Economizer Wireless Thermostat Controller
•Use the UP/DOWN arrow keys change the
Backlit Liquid Crystal Display (LCD)
The thermostat controller includes a 2-line, 8- character backlit display. Low-level backlighting is present during normal operation and brightens when any user interface key is pressed. The backlight returns to low level when the thermostat controller is left unatte nded for 45 seconds.
5
Installation Instructions
Page 6
Integrated PIR Sensor – TEC2004-4+PIR Thermostat Controller
The integrated PIR sensor allows for automatic switching between fully adjustable Occupied and Unoccupied temperature setpoints without user interaction. This feature generates inc rem en tal energ y savings during scheduled occupied period s while the space is unoccupied.
Programming Overview
Three menus are used to view, program, and configur e the TEC2004-4 and TEC2004-4+PIR Thermostat Controllers: the Status Display Menu, the Main User Menu, and the Installer Configuration Menu.
Status Display Menu
The Status Display Menu displays during normal operation. This menu scrolls through several parameters:
Room Temperature
System Mode
Schedule Status (Occupied/Unoccupied/Override)
Outdoor Temperature – An outdoor air tempera ture sensor must be connected.
Applicable Alarms – The backlight lights up as an alarm condition is displayed.
Note: Press the YES key to temporarily stop this menu from scrolling.
Note: An option is available within the Installer Configuration Menu to lock out the scrolling display and show only the Room Temperature parameter.
Main User Menu
Use the Main User Menu to access and change the basic operating parameters of the thermost at controller . Access the menu by pressing the MENU key during normal thermostat controller operation.
Installer Configuration Menu
Use the Installer Configuration Menu to set up the thermostat controller for application-specific operation. To access the menu, press and hold the MENU key for approximately 8 seconds.
Occupancy Sensor Operation – TEC2004-4+PIR Thermostat Controller
A TEC2004-4+PIR Thermostat Controller (or a TEC2004-4 Thermostat Controller equipped with a PIR accessory cover) provides advanced occupancy logic.
Note: The PIR strategy is an occupied strategy. If the thermostat controller is programmed to be Unoccupied , the PIR function does not have an effect on the occupancy strategy.
The thermostat controller automatically switches the occupancy level between Occupied and Unoccupied as required, when local movement is sensed. In the Occupied mode, if no movement is detected beyond the Unocc TM parameter setting, the mode changes to Unoccupied. Once movement is detected, the mode changes back to Occupied.
Occupancy sensing is enabled only if a PIR cover is installed. The PIR cover is auto detected when installed.
PIR Diagnostic LEDs
The diagnostic LEDs inside the PIR lens brighten when movement is detected within the first 30 minutes after powerup. The LEDs do not light up or brighten after the initial 30-minute period.
Setpoints
The installer must be certain that the difference between the Occupied and Unoccupied setpoints can be recovered within a timely fashion to ensure occupancy comfort. In addition, the difference between the two setpoints must be large enough to warrant maximum energy savings.
These setpoints and Unoccupied time are adjust able to allow for customization, as dictated by the individual space requirements. See Figure 7 for an example of increasing room temperature setpoints.
TEC2004-4 and TEC2004-4+PIR Multi-Stage Economizer Wireless Thermostat Controller
6
Installation Instructions
Page 7
Figure 7: Increasing Room Temperature Setpoints
Occ Heat
= 72°F
Occ Cool
= 75°F
Unocc Heat
= 65°F
Room Temperature
FIG:rm_tmp
Configuring the Thermostat Controller
The thermostat controller ships from the factory with default settings for all configurable parameters. The default settings are shown in Table 3. To reconfigure the parameters via the thermostat controller, follow the steps in this section.
1. To access the Installer Configuration Menu, press and hold the MENU key for approximately 8 seconds.
Note: If the Password parameter is configured, Password 0 appears on the thermostat controller display indicating that the configured password is required to proceed. Use the UP/DOWN arrow keys to indicate the configured password, then press the MENU key to proceed through the Installer Configuration Menu parameters.
2. Once the Installer Configuration Menu begins, release and press the NO key to scroll through the parameters listed in Table 3.
3. When the desired parameter is displayed, use the YES key to choose the desired selection option.
4. Press the YES key and then the NO key to continue scrolling through the parameters.
When the thermostat controller is in the Installer Configuration Menu and left unattended for approximately 8 seconds, the thermostat controller reverts to the Status Display Menu.
Configuring the Wireless Mesh Network Settings
Use the following process to configure the wireless mesh network settings.
1. Select a PAN ID and Channel. Use these same values for every TEC Wireless Thermostat Controller (and the associated coordinator) on the same wireless mesh network.
2. Select a Com Address for each TEC Wireless Thermostat Controller (1 to 254). This address must be unique to each thermostat controller on the same wireless network (that is, unique to the PAN ID and Channel combination).
After configuring the wireless mesh network settings, refer to the TEC20xx-4 and TEC20xx-4+PIR Series
Wireless Thermostat Controller System Technical Bulletin (LIT-12011596) for directions on integrating the
TEC20xx-4 and TEC20xx-4+PIR Series Wireless Thermostat Controllers and TEC20 Coordinator with a supervisory controller.
Configuring Inputs DI1 and DI2
When DI1 and DI2 are configured for an alarm condition, an alarm condition is displayed locally when the input is closed. An alarm message is included on the scrolling Status Display Menu and when the message is displayed, the backlight momentarily lights up.
Both inputs can be configured to the Selection Options included in Table 3.
TEC2004-4 and TEC2004-4+PIR Multi-Stage Economizer Wireless Thermostat Controller
7
Installation Instructions
Page 8
Table 3: Installer Configuration Menu (Part 1 of 5)
Parameter
Description and Default Selection Options Appearing on Display
Pswrd Sets the protective access
password to prevent unauthorized
access to the Installer Configuration
Menu.
Default: 0
Note: The default setting does not
lock out access to the Installer
Configuration Menu. Com addr Wireless address at the thermostat
controller; Default: 254
PAN ID Sets the Personal Area Network
Identification (PAN ID) of the
wireless network. All devices on a
network must have the same
PA N ID setting to communicate with
each other. Default: 0 Channel Sets the mesh network channel the
device uses for communication.
Only devices using the same mesh
network channel can communicate
with each other. Default: 10
GET FROM Parameter not available at this time. N/A DI1 Configuration of Digital Input 1.
Default: None
Range: 0 to 1,000
Range: 000 to 254 Addresses of each item on the wireless bus must be uniquely
numbered, increasing from 1. Note: Setting this parameter to 0 disables the function.
Range: 0 to 500 Note: Setting this parameter to 0 disables the function.
Range: 11 to 26
Note: Setting this parameter to 10 disables the function.
(None): No function is associated with an input. (RemNSB): Remote Night Setback (NSB) via a time clock input, an
occupancy sensor, or from a voltage-free contact. Contact open = Occupied; contact closed = Unoccupied.
(RemOVR): Temporary occupancy request via a remote input. This override function is controlled by a manual remote occupancy override. When enabled, this condition disables the override capability of the thermostat controller.
(Filter): A Filter alarm is displayed. This alarm can be connected to a differential pressure switch that monitors a filter.
(Service): A Service alarm is displayed on the thermostat controller when the input is energized. Tie this input into the air conditioning unit control card, which provides an alarm if a malfunction occurs.
(Fan lock): A backlit flashing Fan lock alarm is displayed on the thermostat controller when the input is not energized. This alarm is used in conjunction with a local airflow sensor connected to the input. The thermostat controller heating or cooling action is locked out if no airflow is detected 10 seconds after the fan (Terminal G) is energized. Contact open = no airflow; contact closed = airflow present.
TEC2004-4 and TEC2004-4+PIR Multi-Stage Economizer Wireless Thermostat Controller
8
Installation Instructions
Page 9
Table 3: Installer Configuration Menu (Part 2 of 5)
Parameter
Description and Default Selection Options Appearing on Display
DI2 Configuration of Digital Input 2.
Default: None
MenuScro Gives the option of having the
Lockout Selectable Lockout Levels for
Pwr del
Frost pr Provides a minimum heating
Heat max
1
2
display continuously scroll the
parameters.
Default: on
limiting end user keypad interaction.
Default: 0
Sets the delay time period at
thermostat controller powerup, or at
each time power is removed and
reapplied, before any operation
(fan, heating, or cooling) is
authorized. Also can be used to
sequence the startup of multiple
units in one location.
Default: 10.0 sec
setpoint of 5.5°C/42.0°F to prevent
freezing in the zone controlled by
the thermostat controller.
Default: off
Sets the Occupied and Unoccupied
maximum Heating setpoint values.
Default: 32.0°C/90.0°F
(None): No function is associated with an input. (RemNSB): Remote Night Setback (NSB) via a time clock input, an
occupancy sensor, or from a voltage-free contact. Contact open = Occupied; contact closed = Unoccupied.
(RemOVR): Temporary occupancy request via a remote input. This override function is controlled by a manual remote occupancy override. When enabled, this condition disables the override capability of the thermostat controller.
(Filter): A Filter alarm is displayed. This alarm can be connected to a differential pressure switch that monitors a filter.
(Service): A Service alarm is displayed on the thermostat controller when the input is energized. Tie this input into the air conditioning unit control card, which provides an alarm if a malfunction occurs.
(Fan lock): A backlit flashing Fan lock alarm is displayed on the thermostat controller when the input is not energized. This alarm is used in conjunction with a local airflow sensor connected to the input. The thermostat controller heating or cooling action is locked out if no airflow is detected 10 seconds after the fan (Ter minal G) is energized. Contact open = no airflow; contact closed = airflow present.
(off): The scroll is inactive. (on): The scroll is active.
Function Level
Resume/Override Scheduling
Permanent T emperature Setpoints
T emporary T emperature Setpoints
System Mode Setting Access No Access No Access Fan Mode Setting Access No Access No Access Range: 10.0 to 120.0 sec
(on): Enabled (off): Disabled
Range: 4.5°C/40.0°F to 32.0°C/90.0°F
(0) (1) (2)
Access Access No Access
Access No Access No Access
Access Access No Access
TEC2004-4 and TEC2004-4+PIR Multi-Stage Economizer Wireless Thermostat Controller
9
Installation Instructions
Page 10
Table 3: Installer Configuration Menu (Part 3 of 5)
Parameter
Description and Default Selection Options Appearing on Display
Cool min
Pband Proportional Band used by the PI
Anticycl Anti-Short Cycle timer sets the
Heat cph Sets the maximum number of
Cool cph Sets the maximum number of
Deadband Sets the minimum deadband
Fan cont Determines how the fan is activated
Fan del Fan delay extends fan operation
2
Sets the Occupied and Unoccupied
minimum Cooling setpoint values.
Default: 12.0°C/54.0°F
temperature control loop of the
thermostat controller.
Pband is not converted with C or F
scale and is always shown with a
range of 2 to 8.
Default: 2 (2.0F°/1.1C°)
minimum on/off times for heating
and cooling stages.
Default: 2.0 min
Heating cycles per hour.
Default: 4.0
Cooling cycles per hour.
Default: 4.0
between the heating and cooling
setpoints.
Default: 1.0C°/2.0F°
in response to a call for heating or
cooling.
Default: on
after a heating or cooling cycle has
ended.
Default: off
Range: 12.0°C/54.0°F to 37.5°C/100.0°F
Value F Scale Pband/C Scale Pband 2 2.0F°/1.1C° 3 3.0F°/1.7C° 4 4.0F°/2.2C° 5 5.0F°/2.8C° 6 6.0F°/3.3C° 7 7.0F°/3.9C° 8 8.0F°/4.4C° Note: The use of a larger proportional band is not to use the
thermostat controller as a discharge air controller device. The use of a larger proportional band can be used to solve issues for flawed HVAC design with basic sizing and thermostat controller location errors that cannot be worked around.
Range: 0.0 to 5.0 min adjustable in 1-minute increments Set the anti-short cycle timer to 0.0 min for equipment that already
has its own anti-short cycle timer.
Range: 3.0 to 8.0 cycles per hour
Range: 3.0 or 4.0 cycles per hour
Range: 1.0C°/2.0F° to 2.0C°/4.0F° adjustable in 0.5C°/1.0F° increments
(off): Enables the thermostat controller to activate the fan in response to a call for cooling only.
(on): Enables the thermostat controller to activate the fan in response to a call for heating or cooling.
When there is a call for auxiliary heating, the fan is activated by the equipment fan and limit control.
(on): Extends fan operation by 60 seconds after a heating or cooling cycle has ended.
(off): No extension of fan operation after a heating or cooling cycle has ended.
The fan delay is only active when the fan is in the Auto mode.
TEC2004-4 and TEC2004-4+PIR Multi-Stage Economizer Wireless Thermostat Controller
10
Installation Instructions
Page 11
Table 3: Installer Configuration Menu (Part 4 of 5)
Parameter
Description and Default Selection Options Appearing on Display
TOccTime Sets the duration of the Temporary
Occupancy Time (when the
thermostat controller is in the
Unoccupied mode) when a
Schedule Override Function is
enabled using either the Main User
Menu or DI1 or DI2 configured as a
temporary override remote contact
(RemOVR).
Sets the effective duration of the
Temporary heating or cooling
setpoints set using the
UP/DOWN arrow keys.
Default: 3.0 hrs Cal RS Sets the desired room air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default: 0.0C°/0.0C°F Cal OS Sets the desired outdoor air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default: 0.0C°/0.0F° H stage Reverts the operation of a two-stage
thermostat controller to a
single-stage thermostat controller
when the second heating stage is
not needed.
Default: 2.0 C stage Reverts the operation of a two-stage
thermostat controller to a
single-stage thermostat controller
when the second cooling stage is
not needed.
Default: 2.0 H lock Disables heating stage(s) operation
when the outside air temperature is
greater than the configured value. If
the fan mode is set to Auto or
Smart, the fan output is also
disabled. Requires that an outside
air temperature sensor be installed
and connected.
Default: 120°F/49°C C lock Disables cooling stage(s) operation
when the outside air temperature is
less than the configured value. If the
fan mode is set to Auto or Smart,
the fan output is also disabled.
Requires that an outside air
temperature sensor be installed and
connected.
Default: -40°F/-40°C
Range: 0.0 to 12.0 hrs adjustable in 1-hour increments
Range: -2.5C°/-5.0F° to 2.5C°/5.0F° adjustable in 0.5C°/1.0F° increments
Range: -2.5C°/-5.0F° to 2.5C°/5.0F° adjustable in 0.5C°/1.0F° increments
(1.0): One Stage (2.0): Two Stages
(1.0): One Stage (2.0): Two Stages
Range: -15°F/-26°C to 120°F/49°C adjustable in 5F°/5C° increments
Range: -40°F/-40°C to 95°F/35°C adjustable in 5F°/5C° increments
TEC2004-4 and TEC2004-4+PIR Multi-Stage Economizer Wireless Thermostat Controller
11
Installation Instructions
Page 12
Table 3: Installer Configuration Menu (Part 5 of 5)
Parameter
Description and Default Selection Options Appearing on Display
Aux cont Energizes peripheral devices
(lighting equipment, exhaust fans,
and economizers).
Default: n.o.
Note: The contact toggles with the
internal Occupied/Unoccupied
schedule (or the NSB contact on
one of the digital inputs, if used).
Chngstpt
Min pos Sets the minimum position for the
C mech Determines whether to allow
Mix stpt
MS temp Displays the mixed air temperature.
2
2
Sets the economizer changeover
strategy, based on the outdoor air
temperature. Requires that an
outdoor air temperature sensor be
installed and connected.
When the OA temperature is below
the changeover setpoint, free
cooling is used (economizer
operation). When the OA
temperature is above the setpoint,
mechanical cooling is used
(compressor operation).
Default: 13.0°C/55.0°F
OA dampers on the economizer.
These dampers are energized to
minimum position when the fan
(Terminal G) is energized and the
thermostat controller is in the
Occupied mode. When the
schedule is in the Unoccupied
mode, the minimum position is 0%.
Default: 0.0%
mechanical cooling (compressor
operation) if free cooling
(economizer operation) cannot
maintain the cooling setpoint.
Default: off
Establishes the mixed air
temperature when operating in the
economizer mode.
Default: 55.0°F/13.0°C
Requires that an MS be installed
and connected.
Default: N/A
(n.c.): Contact open = Occupied; contact closed = Unoccupied (n.o.): Contact closed = Occupied; contact open = Unoccupied
Range: -10.0°C/14.0°F to 21.0°C/70.0°F
Range: 0.0 to 100.0% equals 0 to 10 VDC output range
(0.0%) 0% 0 to 20% (5.0%) 5% 24% (10.0%) 10% 28% (15.0%) 15% 32% (20.0%) 20% 36% (25.0%) 25% 40% (30.0%) 30% 44% (on): Typically applies when the MS is installed before the
mechanical cooling refrigeration coils in the mixing plenum. In this scenario, mechanical cooling is allowed when free cooling cannot maintain the cooling setpoint.
(off): Typically applies when the remote Mixed air Sensor (MS) is installed after the mechanical cooling refrigeration coils. In this scenario, mechanical cooling will never operate at the same time as free cooling.
Range: 50.0°F/10.0°C to 90.0°/32.0°C
The mixed air temperature can be used to help service and troubleshoot the equipment and the economizer operation. The mixed air temperature is only accessible via the Installer Configuration Menu.
% OA Setting for 0 to 10 VDC
Actuator
Setting for 2 to 10 VDC
Actuator
1. When adjusting the numeric value, press the UP or DOWN arrow key to change the value by single increments; press and hold the UP or DOWN arrow key to change the numeric value in increments of ten.
2. When adjusting the temperature, press the UP or DOWN arrow key to change the value in 0.5F°/0.5C° increments; press and hold the UP or DOWN arrow key to change the value in 5.0F°/5.0C° increments.
TEC2004-4 and TEC2004-4+PIR Multi-Stage Economizer Wireless Thermostat Controller
12
Installation Instructions
Page 13
Operation
75.0°F
set? Y/N
set? Y/N
75.0°F
set? Y/N
68.0°F
set? Y/N
Programming the Thermostat Controller
After configuring the thermostat controller by means of the Installer Configuration Menu, prog ram it s ope ratin g parameters by means of the Main User Menu. Access this menu by pressing the MENU key during normal operation. The Main User Menu contains the basic operating features of the thermostat controller.
The Main User Menu also uses Auto Help, which is displayed automatically in the menu when there is a pause in programming activity. To exit Auto Help, continue with the programming selection. When the thermostat controller is in the Main User Menu and is left unattended for 45 seconds, the menu revert s to the Status Display Menu.
Enabling Override Schedule
Note: The Override Schedule prompt only appears when the thermostat controller is in the Unoccupied Mode.
This menu selection gives the user the option of overriding the unoccupied setpoints with the occupied setpoints for the amount of time specified under the
TOccTime paramete r. Se e Table 3. Note: If one of the digital inputs is configured to
operate as a remote override contact, this menu is disabled.
T o o verride the unoccupied state while in the Main User Menu:
1. Press the NO key to all prompts until the Override Schedule prompt appears. If the thermostat controller is in the unoccupied state, this is the first prompt.
2. Press the YES key to enable the temporary override. The thermostat controller returns to the Status Display Menu.
When scrolling through the Status Display Menu, Override now appears for the schedule status parameter.
Resuming the Programmed Schedule
This menu only appears when the thermost at controller is in the override mode.
To resume the schedule while in the Main User Menu:
1. Press the NO key to all prompts until the Resume Schedule prompt appears. If the thermostat controller is in the override state, this is the first prompt.
2. Press the YES key to resume the programmed schedule.
The thermostat controller returns to the Status Display Menu.
Entering Permanent Temperature Setpoints
The first prompt appearing in the Main User Menu of the thermostat controller when in the occupied state is to set the permanent temperature setpoint. Permanent setpoints are stored in the programmed schedule.
To enter the permanent heating and cooling setpoints for the Occupied and Unoccupied Modes, follow the steps in Table 4. When changing the temperatures, press the keys once to change the temperature in
0.5C°/0.5F° increments; press and hold down the keys to change the temperature in 5.0F°/5.0C° increments.
Table 4: Entering Permanent Temperature
Setpoints (Part 1 of 2)
Thermostat Controller Display
RoomTemp
Temperat
Cooling
Cooling
Heating
Heating
Unocc CL
Description
Press the MENU key while in the Status Display Menu to enter the Main User Menu.
Press the NO key to all prompts until the temperature setpoint prompt appears on the display (it may be the first prompt). Press the YES key to enter the temperature setting menu.
Press the YES key to change the occupied cooling setpoint. Press the NO key to advance to the occupied heating setpoint menu.
Press the UP/DOWN arrow keys to set the temperature. Press the YES key to store the value and advance to the next menu.
Press the YES key to change the occupied heating setpoint. Press the NO key to advance to the unoccupied cooling setpoint menu.
Press the UP/DOWN arrow keys to set the temperature. Press the YES key to store the value and advance to the next menu.
Press the YES key to change the unoccupied cooling setpoint. Press the NO key to advance to the unoccupied heating setpoint.
TEC2004-4 and TEC2004-4+PIR Multi-Stage Economizer Wireless Thermostat Controller
13
Installation Instructions
Page 14
Table 4: Entering Permanent Temperature
80.0°F
set? Y/N
62.0°F
C
set? Y/N
Y/N
Setpoints (Part 2 of 2)
Thermostat
Description Controller Display
Press the UP/DOWN arrow keys to
Unocc CL
set the temperature. Press the
key to store the value and advance to
the next menu.
YES
The setpoint reverts to the Permanent Temperature Setpoint.
Selecting the System Mode
The thermostat controller has four system modes:
Automatic Mode (auto): Automatic changeover between heating and cooling. This is the default setting.
Cooling Mode (cool): Cooling operation only
YES key to change the
NO key to advance to the
UP/DOWN arrow keys to
YES
YES key to set the display
NO key to
YES key to return to the
NO
Unocc HT
Unocc HT
°F/°
Exit?
Press the unoccupied heating setpoint. Press the temperature display units.
Press the set the temperature. Press the key to store the value and advance to the next menu.
Press the units to °F or °C. Press the advance to the temperature setpoint type menu.
Press the Status Display Menu or press the key to reenter the temperature setting menu.
Entering Temporary Temperature Setpoints
To temporarily change the setpoint, press the UP/DOWN arrow keys to change the temporary setpoint for the current mode of operation.
Note: Whether the thermostat controller is heating or cooling, the respective setpoint is temporarily adjusted. To toggle between the temporary heating and cooling setpoints, press the NO key while changing the temporary setpoints.
Ending Temporary Temperature Setpoints
The temporary setpoints remain in effect for the duration set in the TOccTime parameter or until manually released.
To release the temporary setpoint sooner, while in the Main User Menu:
1. Press the YES key to the first prompt that appears.
2. If the thermostat controller does not immediately return to the S tatus Display Menu, press the MENU key again and press the YES key to exit the Main User Menu.
Heating Mode (heat): Heating operation only
Off Mode (off): The thermostat controller is off; however, when frost protection (Frost pr parameter) is enabled, the thermostat controller still calls for heat (if required).
To set the system mode while in the Main User Menu:
1. Press the NO key to all prompts until the system mode prompt appears on the display. Press the YES key to select the desired system mode.
2. Press the UP/DOWN arrow keys to locate the desired system mode. Press the YES key to select the desired system mode.
3. Press the YES key to return to the Status Display Menu or press the NO key to return to the system mode selection menu.
Selecting the Fan Mode
The thermostat controller has three fan mode settings:
On Fan Mode (on): Energizes the fan all the time for both occupied and unoccupied states, even if the system mode is set to off.
Automatic Fan Mode (auto): Energizes the fan only on a call for heating or cooling, for both occupied and unoccupied states.
Smart Fan Mode (smart): Energizes the fan all the time for occupied states, and only on a call for heating or cooling in unoccupied states. This is the default setting.
To select the fan mode while in the Main User Menu:
1. Press the NO key to all prompts until the fan mode prompt appears on the display. Press the YES key to set the fan mode.
2. Press the UP/DOWN arrow keys to locate the desired fan mode. Press the YES key to select the desired fan mode.
3. Press the YES key to return to the Status Display Menu or press the NO key to return to the fan mode selection menu.
TEC2004-4 and TEC2004-4+PIR Multi-Stage Economizer Wireless Thermostat Controller
14
Installation Instructions
Page 15
Troubleshooting
See Table 5 for display messaging. Refer to the
TEC20xx-4 and TEC20xx-4+PIR Series Wireless Thermostat Controller System Technical Bulletin (LIT-12011596) for troubleshooting details.
Accessories
Repair Information
If a TEC2004-4 or TEC2004-4+PIR Wireless Thermostat Controller fails to operate within its specifications, replace the unit. For a replacement thermostat controller, contact the nearest Johnson Controls representative.
All the accessories in Table 6 include mounting hardware; contact the nearest Johnson C on tr ols ® representative to order any of these parts.
Note: Review the technical specifications of the accessories prior to their use in an application.
Table 5: Alarm Messages
Display Function
Frost Indicates that the heating is energized by the low limit frost protection room temperature setpoint 5.6°C (42°F). Fan Lock Indicates that the heating and cooling action are locked out due to a defective fan operation. Service Indicates that there is a service alarm in accordance with a programmable Digital Input. Filter Indicates that the filter(s) is dirty in accordance with a programmable Digital Input.
Table 6: Accessories (Order Separately)
Code Number Description
SEN-600-1 Remote Indoor Air Temperature Sensor SEN-600-4 Remote Indoor Air Temperature Sensor with Occupancy Override and LED
TEC-3-PIR TE-6361M-1 TE-6363P-1
TE-636S-1 Strap-Mount Temperature Sensor TEC20-A-1 Replacement Antenna for TEC20 Coordinator
TEC20-RA-1 NPB-PWR
TEC20-8X-1 120 VAC to 15 VDC Power Supply for TEC20 Coordinator TEC20-9B-1 Replacement Battery Pack for TEC20 Coordinator TEC20-3C-2 BACnet IP Wireless Coordinator; Requires 15 VDC Power Supply TEC20-6C-2 BACnet MS/TP Wireless Coordinator; Requires 15 VDC Power Supply
1
4
Cover with Occupancy Sensor
2
Duct Mount Air Temperature Sensor
2
Outside Air Temperature Sensor
3
Remote Antenna for TEC20 Coordinator DIN Rail Mount 24 VAC/DC Power Module for TEC20 Coordinator
1. The TEC-3-PIR Accessory Cover can be used to replace the existing cover on a non-PIR TEC2004-4 Thermostat Controller to provide occupancy sensing capability.
2. Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the
TE-6300 Series Temperature Sensors Product Bulletin (LIT-216320) for more details.
3. This antenna is used when the TEC Coordinator is installed inside a metal cabinet, or when a remote antenna is required by physical installation.
4. DIN Rail: Type NS35/7.5 (35 x 7.5 mm) and DIN rail end clips. Length of DIN rail depends on the number of DIN rail mounted options.
TEC2004-4 and TEC2004-4+PIR Multi-Stage Economizer Wireless Thermostat Controller
15
Installation Instructions
Page 16
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2010 Johnson Controls, Inc.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Tech nical Specifications
TEC2004-4 and TEC2004-4+PIR Multi-Stage Economizer Wireless Thermostat Controllers
Power Requirements 19 to 30 VAC, 50/60 Hz, 2 VA (Terminals RC and C) at 24 VAC Nominal, Class 2 or
Safety Extra-Low Voltage (SELV)
Economizer Output Rating 0 to 10 VDC into 2k ohm Resistance (Minimum) Relay/Triac Contact Rating 19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush, Class 2 or SELV Digital Inputs Voltage-Free Contacts across Terminal C to Terminals DI1 and DI2 Analog Inputs Resistive Inputs (RS and UI3) for 10k ohm Johnson Controls Type II Negative
Temperature Coefficient (NTC) Thermistor Sensors
Wire Size 18 AWG Maximum, 22 AWG Recommended Transmission Range Through Walls: 10 m (32.8 ft)
RF Band Direct-Sequence Spread-Spectrum Transmission; 2.4 GHz unlicensed band Transmission Power 10 mW Maximum Temperature Range Backlit Display: -40.0°C/ -40.0°F to 50.0°C/122.0°F
Temperature Sensor Type Local 10k ohm Negative Temperature Coefficient (NTC) Thermistor Resolution ±0.1C°/±0.2F° Control Accuracy ±0.5C°/±0.9F° at 21.0°C/70.0°F Typical Calibrated Auxiliary/Outdoor Air
Temperature Indication Range Minimum Deadband 1C°/2F° between Heating and Cooling Ambient Conditions Operating: 0 to 50°C (32 to 122°F); 95% RH Maximum, Noncondensing
Compliance United States:
Shipping Weight TEC2004-4 Models: 0.75 lb (0.34 kg)
Line-of-Sight (Open Space): 30 m (98.4 ft)
Heating Control: 4.5°C/40.0°F to 32.0°C/90.0°F in 0.5° Increments Cooling Control: 12.0°C/54.0°F to 100.0°F/38.0°C in 0.5° Increments
-40.0°C/-40.0°F to 50.0°C/122.0°F
Storage:-30 to 50°C (-22 to 122°F); 95% RH Maximum, Noncondensing
UL Listed, File E27734, CCN XAPX, Under UL 873, Temperature Indicating and Regulating Equipment
FCC Compliant to Part 15.247 Regulations for Low Power Unlicensed Transmitters
Canada:
UL Listed, File E27734, CCN XAPX7, Under CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment
Industry Canada, ICES-003
TEC2004-4+PIR Models: 0.77 lb (0.35 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
TEC2004-4 and TEC2004-4+PIR Multi-Stage Economizer Wireless Thermostat Controller
16
Installation Instructions
Published in U.S.A. www.johnsoncontrols.com
Loading...