TEC2001-4 and TEC2001-4+PIR Single-Stage Wireless
Thermostat Controllers
Installation Instructions
TEC2001-4 and TEC2001-4+PIR
Part No. 24-9890-1125, Rev. B
Issued July 13, 2010
Supersedes May 17, 2010
Applications
The TEC Series Wireless Thermostat Controller
System provides wireless networked control of
Heating, Ventilating, and Air Conditioning (HVAC)
equipment on a Building Automation System (BAS)
that enables remote monitoring and programming. This
TEC Series System integrates into a supervisory
controller that uses BACnet® Internet Protocol (IP) or
BACnet Master-Slave/Token-Passing (MS/TP)
communications.
TEC20 Coordinators allow the supervisory controlle r to
communicate with multiple TEC Wireless Thermostat
Controllers. The TEC200x-4 Series Wireless
Thermostat Controllers provide networked control of a
variety of staged equipment. The TEC2001-4
Single-Stage Wireless Thermostat Controllers control
fan coil units, unit heaters, and single-stage packaged
heating/cooling equipment.
The TEC2001-4+PIR Thermostat Controller provides
advanced active occupancy logic that automatically
switches occupancy from Occupied to Unoccupied as
required by the presence of local activity. See the
Occupancy Sensor Operation – TEC2001-4+PIR
Thermostat Controller section for more information.
The wireless mesh network uses ZigBee™ technology
to enable remote monitoring and programming and to
enhance reliability by providing redundant transmission
paths through other TEC Wireless Thermostat
Controllers, creating a resilient, self-healing mesh
network.
IMPORTANT: The TEC2001-4 and
TEC2001-4+PIRWireless Thermostat Controllers
are intended to provide an input to equipment under
normal operating conditions. Where failure or
malfunction of the thermostat controller could lead to
personal injury or property damage to the controlled
equipment or other property, additional precautions
must be designed into the control system.
Incorporate and maintain other devices, such as
supervisory or alarm systems or safety or limit
controls, intended to warn of or protect against
failure or malfunction of the thermostat controller.
North American Emissions Compliance
United States
This equipment has been tested and found to
comply with the limits for a Class A digital device
pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection
against harmful interference when this equipment is
operated in a commercial environment. This
equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in
accordance with the instruction manual, may cause
harmful interference to radio communications.
Operation of this equipment in a residential area is
likely to cause harmful interference, in which case
the user will be required to correct the interference
at his/her own expense.
This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions:
1. This device may not cause harmful interference,
and
2. This device must accept any interference
received, including interference that may cause
undesired operation.
Warning (Part 15 .21)
Changes or modifications not expressly approved by
the party responsible for compliance could void the
user’s authority to operate the equipment.
TEC2001-4 and TEC2001-4+PIR Single-Stage Wireless Thermostat Controllers
1
Installation Instructions
Canada
Figure 1: Removing the Thermostat Controller
Cover (TEC2001-4+PIR Model Shown)
FIG:cvr_ rmvl
This Class (A) digital apparatus meets all the
requirements of the Canadian Interference-Causing
Equipment Regulations.
Table 1: Recommended Transmission Ranges
TypeDistance
Through Walls 10 m (30 ft)
Open Space 30 m (100 ft)
Cet appareil numérique de la Classe (A) respecte
toutes les exigences du Règlement sur le matériel
brouilleur du Canada.
RF Transmitter s: Industry Canada Statement
The term IC before the certification/registration
number only signifies that the Industry Canada
technical specifications were met.
Le terme « IC » précédant le numéro d'accré ditation /
inscription signifie simplement que le produit est
conforme aux spécifications techniques d'Industrie
Canada.
Installation
Location Considerations
Locate a thermostat controller:
•on a partitioning wall, approximately 1.5 m (5 ft)
above the floor in a location of average
temperature
•away from direct sunlight, radiant heat, outside
walls, outside doors, air discharge grills, or
stairwells, or from behind doors
•away from steam or water pipes, warm air stacks,
unconditioned areas (not heated or cooled), or
sources of electrical interference
For detailed information on locating devices for
optimum signal strength, refer to the Wireless Metasys System Location Guide (LIT-12011294).
Installing the Thermostat Controller
Follow these steps to install the thermostat controller:
1. Use a Phillips-head screwdriver to remove the
security screw if it is installed on the bottom of the
thermostat controller cover.
Note: Normally, the security screw is packaged
separately in a plastic bag with the thermostat
controller. Skip this step if the screw is not installed
on the bottom of the cover.
2. Pull the bottom edge of the thermostat controller
cover and open the thermostat controller as
illustrated in Figure 1.
Note: PIR models have a wiring connection
between the cover and the Printed Circuit Board
(PCB). This connection allows for proper wiring of
the occupancy sensor . Car efully remove the wiring
connection from the PCB by pulling up on the
connector block. Do not attempt to remove the connector block by pulling on the wires.
For integrated Passive Infrared (PIR) models, make
sure the thermostat controller is located centrally,
where occupant movement is frequent.
Note: Allow for vertical air circulation to the
TEC2001-4 and TEC2001-4+PIR Thermostat
Controllers.
Wireless Signal Transmission Range
Line-of-sight transmission ranges between a
TEC20 Coordinator and a TEC Wireless Thermostat
Controller (or between TEC Wireless Thermostat
Controllers) can be less than the recommended
distances shown in Table 1. The effective transmission
range for indoor applications varies because of Radio
Frequency (RF) signal absorption and re flectio n due to
metal obstructions, walls (or floors), and furniture found
in typical building interiors.
TEC2001-4 and TEC2001-4+PIR Single-Stage Wireless Thermostat Controllers Installation Instructions2
3. Carefully pull the locking tabs on the right side of
Figure 2: Opening the PCB
F
I
G
:
p
r
n
t
_
c
i
r
c
_
Tabs
Figure 3: Securing the
Mounting Base to the Wall
F
I
G
:
m
Figure 4: Removing the Screw Terminal Blocks
the mounting base and unlock the PCB. Open the
PCB to the left as illustrated in Figure 2.
PCB
Locking
d
r
b
Note: Be careful not to overtighten the mounting
screws.
s
b
_
g
n
t
n
4. Pull approximately 152 mm (6 in.) of wire from the
wall and insert the wire through the hole in the
mounting base.
5. Align the mounting base on the wall and use the
base as a template to mark the two mounting hole
locations.
6. Position the thermostat controller mounting base
so that the arrow on the base points upward to
indicate the top of the thermostat controller.
Note: If you need to install the thermostat on an
electrical junction box, use 2-1/2 x 4 in.
(63 x 101 mm) square boxes with mud ring covers,
and avoid smaller 1-1/2 x 4 in. (38 x 101 mm)
square or 3 x 2 in. (76 x 51 mm) boxes. This
procedure ensures you have enough space for
cabling and end-of-line devices, if needed.
Note: For surface-mount application s, use
durable mounting hardware such as Molly bolt
anchors that cannot be easily pulled out of the
mounting surface.
7. Secure the mounting base to the wall surface using
two mounting screws as illustrated in Figure 3.
8. Swing the PCB back to the right and carefully snap
it into the locking tabs on the mounting base.
9. Remove the screw terminal blocks that are
attached to a disposable adhesive. Figure 4
illustrates the locations of the screw terminal
blocks on the thermostat controller.
s
k
c
l
b
_
l
n
m
r
t
:
G
I
F
TEC2001-4 and TEC2001-4+PIR Single-Stage Wireless Thermostat Controllers Installation Instructions3
Wiring
!
!
Cool 1
24 VAC
Thermostat Power
Heat 1
Y1RC
C
RHW1
for the thermostat and heating loads,
install a jumper across RC and RH.
Supply
Sensor
Aux
Aux
Outdoor
Function
Terminal
24 VAC from Equipment Trans fo rmer
24 VAC (Comm on from Equipment Tr ansformer
24 VAC for Heating Stage
Auxiliary Out put
Configurable Digital Input 1
Configurable Digital Input 2
Remote Room Sensor
Sensor Co m m on
Auxiliary/Outdoor Air Sensor
Remote M onitoring Suppl y Temper at ur e Sensor
)
W1
Y1
G
RC
C
RH
Aux
DI1
DI2
RS
Scom
OS
MS
Y1 G
C
RS
Two-Pole
Right Top
Connector
Aux
Fan
G
• Lighting
• On/Of f Actua tio n
• Exhaust Fan
Remote
Room
Sensor
Figure 5: Wiring the TEC2001-4 or TEC2001-4+PIR Thermostat Controller
CAUTION: Risk of Electric Shock.
Disconnect the power supply before
making electrical connections to avoid
electric shock.
CAUTION: Risk of Property Damage.
Do not apply power to the system before
checking all wiring connections. Short
circuited or improperly connected wires
may result in permanent damage to the
equipment.
To wire the thermostat controller:
1. Strip the ends of each wire 6 mm (1/4 in.) and
connect them to the appropriate screw terminals as
indicated in Figure 5.
Note: If multiple wires are inserted into the screw
terminals, be sure to properly twist the wires
together prior to inserting them into the screw
terminals.
2. Carefully push any excess wire back into the wall.
Note: Seal the hole in the wall with fireproof
material to prevent drafts from affecting the
ambient temperature readings.
IMPORTANT: Make all wiring connections in
accordance with local, national, and regional
regulations. Do not exceed the electrical ratings of
thethermostat controller.
When replacing an existing thermostat controller,
remove and label the wires to identify the terminal
functions. When replacing a thermostat controller of the
same model, simply remove the old screw terminal
blocks and reinsert them onto the PCB of the
replacement thermostat controller.
Energizes on Call for Heating
Energizes on Call for Cooling
Energize s Fan in Accordance with the Selected Fan Mode
3. Reinsert the screw terminal blocks onto the PCB.
4. Reattach the cover to the mounting base (top side
first).
5. Use a Phillips-head screwdriver to reinstall the
security screw on the bottom of the thermostat
controller cover.
See Figure 5 for information on wiring the thermostat
controller.
Four-Pole
Left Top Con nec tor
Seven-Pole Bottom Connector
DI1
DI2
Aux Cont act (High Side Common )
RS
Scom
RC
DI1 DI2
OS
MS
RH W1
Scom
OS
MS
If using the same power source
TEC2001-4 and TEC2001-4+PIR Single-Stage Wireless Thermostat Controllers Installation Instructions4
Auxiliary/
Air Sensor
Remote
Monitoring
Temperature
FIG:wrng_2001
Setup and Adjustments
Figure 6: Front Cover of Thermostat Controller (TEC2001-4+PIR Model Shown)
70.0ºF
Backlit, plain text
Liquid Crystal Display (LCD)
is easy to read in any condition.
Five keys on the thermostat contr ol ler
make ope ra t ion easy and i nt ui tive.
indicate system activi t y.
FIG:2001-4frnt_vw
PIR mot io n detector
saves ener gy using
standby setpoints.
Status L ED beneath co ver
indicat es network sta tu s.
Thermostat Controller User Interface Keys
The user interface consists of keys on the front cover
(Figure 6). The function of each key is as follows:
•Use the YES key to:
-confirm menu selections and to advance to the
next menu item
-stop the Status Display Menu from scrolling
and to manually scroll to the next parameter on
the menu
Note: When the thermosta t controller is left
unattended for 45 seconds, the display resumes
scrolling.
•Use the NO key to decline a parameter change and
to advance to the next menu item.
•Use the MENU key to:
-access the Main User Menu or to exit the menu
(See the Main User Menu
section.)
-access the Installer Configuration Menu or to
exit the menu (See the Configuring the Thermostat Controller section.)
•Use the UP/DOWN arrow keys to change the
configuration parameters and activate a setpoint
adjustment.
Light-Emitting Diodes (LEDs)
Three LEDs are included to indicate the fan status, call
for heat, or call for cooling:
•The fan LED is on when the fan is on.
•The heat LED is on when heating is on.
•The cool LED is on when cooling is on.
The Status LED, located beneath the cover, flashes at
5-second intervals to provide indication of the network
Room Temp
Light-Emitting Diodes (LEDs)
Table 2: Status LED
Flashes per
Condition Indicated
5-Second
Interval
1Power On
2Power On, Communicating
3Power On, Communicating, Found
Wireless Network
4Power On, Communicating, Found
Wireless Network, Communicating with
TEC20 Coordinator
TEC2001-4 and TEC2001-4+PIR Single-Stage Wireless Thermostat Controllers Installation Instructions5
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.