Johnson Controls TEC2001-4, TEC2001-4+PIR Installation Instructions Manual

TEC2001-4 and TEC2001-4+PIR Single-Stage Wireless Thermostat Controllers
Installation Instructions
TEC2001-4 and TEC2001-4+PIR
Part No. 24-9890-1125, Rev. B
Issued July 13, 2010
Supersedes May 17, 2010
Applications
The TEC Series Wireless Thermostat Controller System provides wireless networked control of Heating, Ventilating, and Air Conditioning (HVAC) equipment on a Building Automation System (BAS) that enables remote monitoring and programming. This TEC Series System integrates into a supervisory controller that uses BACnet® Internet Protocol (IP) or BACnet Master-Slave/Token-Passing (MS/TP) communications.
TEC20 Coordinators allow the supervisory controlle r to communicate with multiple TEC Wireless Thermostat Controllers. The TEC200x-4 Series Wireless Thermostat Controllers provide networked control of a variety of staged equipment. The TEC2001-4 Single-Stage Wireless Thermostat Controllers control fan coil units, unit heaters, and single-stage packaged heating/cooling equipment.
The TEC2001-4+PIR Thermostat Controller provides advanced active occupancy logic that automatically switches occupancy from Occupied to Unoccupied as required by the presence of local activity. See the
Occupancy Sensor Operation – TEC2001-4+PIR Thermostat Controller section for more information.
The wireless mesh network uses ZigBee™ technology to enable remote monitoring and programming and to enhance reliability by providing redundant transmission paths through other TEC Wireless Thermostat Controllers, creating a resilient, self-healing mesh
network.
IMPORTANT: The TEC2001-4 and TEC2001-4+PIR Wireless Thermostat Controllers are intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the thermostat controller could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the thermostat controller.
North American Emissions Compliance
United States
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense.
RF Transmitters: Compliance Statement (Part 15.19)
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received, including interference that may cause undesired operation.
Warning (Part 15 .21)
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
TEC2001-4 and TEC2001-4+PIR Single-Stage Wireless Thermostat Controllers
1
Installation Instructions
Canada
Figure 1: Removing the Thermostat Controller
Cover (TEC2001-4+PIR Model Shown)
FIG:cvr_ rmvl
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Table 1: Recommended Transmission Ranges
Type Distance
Through Walls 10 m (30 ft) Open Space 30 m (100 ft)
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
RF Transmitter s: Industry Canada Statement
The term IC before the certification/registration number only signifies that the Industry Canada technical specifications were met.
Le terme « IC » précédant le numéro d'accré ditation / inscription signifie simplement que le produit est conforme aux spécifications techniques d'Industrie Canada.
Installation
Location Considerations
Locate a thermostat controller:
on a partitioning wall, approximately 1.5 m (5 ft) above the floor in a location of average temperature
away from direct sunlight, radiant heat, outside walls, outside doors, air discharge grills, or stairwells, or from behind doors
away from steam or water pipes, warm air stacks, unconditioned areas (not heated or cooled), or sources of electrical interference
For detailed information on locating devices for optimum signal strength, refer to the Wireless Metasys System Location Guide (LIT-12011294).
Installing the Thermostat Controller
Follow these steps to install the thermostat controller:
1. Use a Phillips-head screwdriver to remove the security screw if it is installed on the bottom of the thermostat controller cover.
Note: Normally, the security screw is packaged separately in a plastic bag with the thermostat controller. Skip this step if the screw is not installed on the bottom of the cover.
2. Pull the bottom edge of the thermostat controller cover and open the thermostat controller as illustrated in Figure 1.
Note: PIR models have a wiring connection between the cover and the Printed Circuit Board (PCB). This connection allows for proper wiring of the occupancy sensor . Car efully remove the wiring connection from the PCB by pulling up on the connector block. Do not attempt to remove the connector block by pulling on the wires.
For integrated Passive Infrared (PIR) models, make sure the thermostat controller is located centrally, where occupant movement is frequent.
Note: Allow for vertical air circulation to the TEC2001-4 and TEC2001-4+PIR Thermostat Controllers.
Wireless Signal Transmission Range
Line-of-sight transmission ranges between a TEC20 Coordinator and a TEC Wireless Thermostat Controller (or between TEC Wireless Thermostat Controllers) can be less than the recommended distances shown in Table 1. The effective transmission range for indoor applications varies because of Radio Frequency (RF) signal absorption and re flectio n due to metal obstructions, walls (or floors), and furniture found in typical building interiors.
TEC2001-4 and TEC2001-4+PIR Single-Stage Wireless Thermostat Controllers Installation Instructions2
3. Carefully pull the locking tabs on the right side of
Figure 2: Opening the PCB
F
I
G
:
p
r
n
t
_
c
i
r
c
_
Tabs
Figure 3: Securing the
Mounting Base to the Wall
F
I
G
:
m
Figure 4: Removing the Screw Terminal Blocks
the mounting base and unlock the PCB. Open the PCB to the left as illustrated in Figure 2.
PCB Locking
d
r
b
Note: Be careful not to overtighten the mounting screws.
s
b
_ g
n
t
n
4. Pull approximately 152 mm (6 in.) of wire from the wall and insert the wire through the hole in the mounting base.
5. Align the mounting base on the wall and use the base as a template to mark the two mounting hole locations.
6. Position the thermostat controller mounting base so that the arrow on the base points upward to indicate the top of the thermostat controller.
Note: If you need to install the thermostat on an electrical junction box, use 2-1/2 x 4 in. (63 x 101 mm) square boxes with mud ring covers, and avoid smaller 1-1/2 x 4 in. (38 x 101 mm) square or 3 x 2 in. (76 x 51 mm) boxes. This procedure ensures you have enough space for cabling and end-of-line devices, if needed.
Note: For surface-mount application s, use durable mounting hardware such as Molly bolt anchors that cannot be easily pulled out of the mounting surface.
7. Secure the mounting base to the wall surface using two mounting screws as illustrated in Figure 3.
8. Swing the PCB back to the right and carefully snap it into the locking tabs on the mounting base.
9. Remove the screw terminal blocks that are attached to a disposable adhesive. Figure 4 illustrates the locations of the screw terminal blocks on the thermostat controller.
s k
c
l
b
_
l
n m
r
t
: G
I F
TEC2001-4 and TEC2001-4+PIR Single-Stage Wireless Thermostat Controllers Installation Instructions 3
Wiring
!
!
Cool 1
24 VAC
Thermostat Power
Heat 1
Y1 RC
C
RH W1
for the thermostat and heating loads, install a jumper across RC and RH.
Supply Sensor
Aux
Aux
Outdoor
Function
Terminal
24 VAC from Equipment Trans fo rmer 24 VAC (Comm on from Equipment Tr ansformer 24 VAC for Heating Stage Auxiliary Out put Configurable Digital Input 1 Configurable Digital Input 2 Remote Room Sensor Sensor Co m m on Auxiliary/Outdoor Air Sensor Remote M onitoring Suppl y Temper at ur e Sensor
)
W1
Y1
G
RC
C
RH
Aux
DI1 DI2 RS
Scom
OS MS
Y1 G
C
RS
Two-Pole Right Top Connector
Aux
Fan
G
• Lighting
• On/Of f Actua tio n
• Exhaust Fan
Remote
Room
Sensor
Figure 5: Wiring the TEC2001-4 or TEC2001-4+PIR Thermostat Controller
CAUTION: Risk of Electric Shock.
Disconnect the power supply before making electrical connections to avoid electric shock.
CAUTION: Risk of Property Damage.
Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment.
To wire the thermostat controller:
1. Strip the ends of each wire 6 mm (1/4 in.) and connect them to the appropriate screw terminals as indicated in Figure 5.
Note: If multiple wires are inserted into the screw terminals, be sure to properly twist the wires together prior to inserting them into the screw terminals.
2. Carefully push any excess wire back into the wall. Note: Seal the hole in the wall with fireproof
material to prevent drafts from affecting the ambient temperature readings.
IMPORTANT: Make all wiring connections in accordance with local, national, and regional regulations. Do not exceed the electrical ratings of the thermostat controller.
When replacing an existing thermostat controller, remove and label the wires to identify the terminal functions. When replacing a thermostat controller of the same model, simply remove the old screw terminal blocks and reinsert them onto the PCB of the replacement thermostat controller.
Energizes on Call for Heating Energizes on Call for Cooling Energize s Fan in Accordance with the Selected Fan Mode
3. Reinsert the screw terminal blocks onto the PCB.
4. Reattach the cover to the mounting base (top side first).
5. Use a Phillips-head screwdriver to reinstall the security screw on the bottom of the thermostat controller cover.
See Figure 5 for information on wiring the thermostat controller.
Four-Pole Left Top Con nec tor
Seven-Pole Bottom Connector
DI1
DI2
Aux Cont act (High Side Common )
RS
Scom
RC
DI1 DI2
OS
MS
RH W1
Scom
OS
MS
If using the same power source
TEC2001-4 and TEC2001-4+PIR Single-Stage Wireless Thermostat Controllers Installation Instructions4
Auxiliary/
Air Sensor
Remote
Monitoring
Temperature
FIG:wrng_2001
Setup and Adjustments
Figure 6: Front Cover of Thermostat Controller (TEC2001-4+PIR Model Shown)
70.0ºF
Backlit, plain text
Liquid Crystal Display (LCD)
is easy to read in any condition.
Five keys on the thermostat contr ol ler make ope ra t ion easy and i nt ui tive.
indicate system activi t y.
FIG:2001-4frnt_vw
PIR mot io n detector
saves ener gy using
standby setpoints.
Status L ED beneath co ver
indicat es network sta tu s.
Thermostat Controller User Interface Keys
The user interface consists of keys on the front cover (Figure 6). The function of each key is as follows:
•Use the YES key to:
- confirm menu selections and to advance to the next menu item
- stop the Status Display Menu from scrolling and to manually scroll to the next parameter on the menu
Note: When the thermosta t controller is left unattended for 45 seconds, the display resumes scrolling.
•Use the NO key to decline a parameter change and to advance to the next menu item.
•Use the MENU key to:
- access the Main User Menu or to exit the menu
(See the Main User Menu
section.)
- access the Installer Configuration Menu or to
exit the menu (See the Configuring the Thermostat Controller section.)
•Use the UP/DOWN arrow keys to change the configuration parameters and activate a setpoint
adjustment.
Light-Emitting Diodes (LEDs)
Three LEDs are included to indicate the fan status, call for heat, or call for cooling:
The fan LED is on when the fan is on.
The heat LED is on when heating is on.
The cool LED is on when cooling is on. The Status LED, located beneath the cover, flashes at
5-second intervals to provide indication of the network
Room Temp
Light-Emitting Diodes (LEDs)
Table 2: Status LED
Flashes per
Condition Indicated 5-Second Interval
1 Power On 2 Power On, Communicating 3 Power On, Communicating, Found
Wireless Network 4 Power On, Communicating, Found
Wireless Network, Communicating with
TEC20 Coordinator
TEC2001-4 and TEC2001-4+PIR Single-Stage Wireless Thermostat Controllers Installation Instructions 5
Loading...
+ 11 hidden pages