Johnson Controls TE-7800 Series, TE-7820-0, TE-7830-0, TE-7820-1, TE-7830-1 Installation Instructions Manual

Page 1
TE-7800 Series Receivers for One-to-One Wireless Room
24-10139-8, Rev.
G
Temperature Sensing Systems
Installation Instructions
TE-7820-0, TE-7830-0, TE-7820-1, TE-7830-1
Refer to the QuickLIT website for the most up-to-date version of this document.

Application

The TE-7800 Series Receivers for One-to-One wireless room temperature sensing systems receive wireless Radio Frequency (RF) temperature data from WRS Series Wireless Room Temperature Sensors, and provide single zone temperature control data to specified digital controllers in building Heating, Ventilating, and Air Conditioning (HVAC) systems.
In a typical application, one WRS Series Sensor reports to one TE-7800 Series Receiver; however, up to four WRS Series Sensors can associate to a single TE-7800 Series Receiver. In multi-sensor applications, the receiver either averages the sensors’ temperature input or selects the highest or lowest sensed temperature for control of the target zone.
The TE-7820-x Series Receivers communicate over a zone bus interface with Johnson Controls® VMA14 Series Controllers. The receiver supplies the sensed zone temperature, temperature setpoint, field strength measurements, and low battery conditions.
The TE-7830-x Series Receivers communicate over an analog interface with Johnson Controls AS-AHU, AS-UNT, AS-VAV, DX-9100, and FXxx Series Field Controllers. The TE-7830-x Series Receivers communicate 0 to 5 VDC analog signals for zone temperature and setpoint, binary inputs for low battery indication, and occupancy status to the supported fie ld controllers.
Note: TE-78x0-1 Series Receivers (CE Mark compliant models) have a reduced transmission power (10 dBm) and transmission range to comply with the requirements of select countries.
Refer to the TE-7800 Series One-to-One Wireless
Room Temperature Sensing System Technical Bulletin (LIT-12011097) for information on commissioning TE-
7800 Series Receivers and configuring One-to-One wireless temperature sensing systems.
Part No. 24-10139-8, Rev. G
Issued February 2016
The TE-7800 Series Receivers use direct-sequence, spread-spectrum RF technology and operate on the
2.4 GHz Industrial, Scientific, Medical (ISM) band. The receiver meets the IEEE 802.15.4 standard for low power, low duty cycle RF transmitting systems.
A TE-7800 Series Receiver operates as a transceiver to create a bidirectional association with a WRS Series Sensor that allows the temperature sensing system to confirm and synchronize data transmissions between the sensor and the receiver.
IMPORTANT: The TE-7800 Series Receiver is intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the receiver could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the receiver.
IMPORTANT: Le TE-7800 Series Receiver est destiné à transmettre des données entrantes à un équipement dans des conditions normales de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du receiver risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du receiver.
IMPORTANT: The TE-7800 Series Receivers are not designed or intended for use in mission-critical or life/safety applications.
TE-7800 Series Receivers for One-to-One Wireless Room Temperature
Sensing Systems Installation Instructions
1
Page 2

North American Emissions Compliance

Figure 1: TE-7800 Series Receiver
Dimensions, in./mm
2-1/16
52
4-13/16
122
5-3/4
146
FIG:dmnsns
Omnidirectional
Indoor Antenna
5-1/2
140

United States

This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense.

Canada

This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.

Dimensions

Installation

IMPORTANT: Before installing the TE-7800 Series
Receivers in plenum applications, verify acceptance of exposed plastic materials in plenum areas with the local building authority. Building codes for plenum requirements vary by location. Some local building authorities accept compliance to UL 1995, Heating and Cooling Equipment, while others use different acceptance criteria.
Follow these guidelines:
Transport the TE-7800 Series Receivers in the original container to minimize vibration and shock damage to the receiver.
Verify that all the parts shipped with the receiver.
Do not drop the receiver or subject it to physical shock.

Parts Included

one TE-7800 Series Receiver
one omnidirectional indoor antenna
one control interface and power cable
four No. 6 pan-head, sheet-metal screws

Mounting

Location Considerations

Receivers Using the Omnidirectional Indoor Antenna

Follow these guidelines when locating a TE­7800 Series Receiver using the omnidirectional antenna.
Locate the receiver so that it is easily accessible (typically just above the ceiling tiles) and within close proximity to the field controller when using the 6 ft (1.8 m) power and zone bus interface cable included with the receiver.
Note: Additional communication cables of various lengths are available to connect the (TE-7820-x Series) zone bus only (no power cable). See Table 1 for details.
The TE-7820-x Series Receivers may be
located up to 300 ft (91 m) from the VMA14 Series Controller.
•The TE-7830-x Series Receivers may be
located up to 100 ft (30 m) from the supported field controller.
one installation instructions sheet TE-7800 Series Receivers for One-to-One Wireless Room Temperature Sensing Systems Installation Instructions
2
Page 3
Locate the receiver near the center of the
Figure 2: Mounting the TE-7800 Series Receivers
1. Remov e the recei ver housing by pressi n g t he locking ta b s i n at the slots on the mounting base to
release the receiver from its base.
2. Use th e m ounting base
as a screw hole template.
3. Insert the four No. 6 screws into the moun t ing holes on the mounti ng base, and tighten them evenly to the surface.
4. Reinstall the receiver housing by aligning t he locking t abs with the slot s on the mo unting base, and pressing the housing until it locks onto the base.
FIG:mntng
Slots
Locking
Tabs (4)
associated sensor layout in multi-sensor applications.
Locate the receiver on the same floor or building level as the associated sensors. (Transmissions may pass through floors. Test the transmission strength before installing associated sensors and receivers on different floors or building levels.)
Locate the receiver in line-of-sight with the sensors whenever possible.
Mount the receiver in any orientation. For best signal transmission, the antenna should be oriented vertically, and at least 2 in. (50 mm) of the tip of the antenna should be exposed below or beyond any pipes, duct work, or other metal obstructions in direct line-of-sight to the sensors.
Avoid metal obstructions (including equipment rooms and elevator shafts) and concrete/brick walls between the receiver and sensors.
Mount the receiver in metal enclosures, only if you take special measures for the omnidirectional antenna to protrude from the metal enclosure.
You can also use the WRS-SST Series Wireless Sensing System Tool to determine the RF signal strength between the sensor and receiver locations. Refer to the WRS-SST Series Wireless Sensing
System Tools Technical Bulletin (Part No. 24-10139-16) for more informatio n on testing
RF signal strength in your One-to-One application.

Mounting the Base

The TE-7800 Series Receivers can be surface mounted using the four No. 6 self-tapping, pan-head screws.
To mount the receiver base with screws:
1. Remove the receiver from the mounting base (Figure 2).
2. Use the mounting base as a screw hole template; place the mounting base against the mounting surface and mark the location for the four screw holes (Figure 2).
3. Drill a pilot hole at the four marked locations.
4. Secure the mounting base to the surface with the (four) No. 6 screws supplied (Figure 2).
Do not mount the receiver in recessed areas or shelving units.

Wireless RF Signal Transmission Considerations

The maximum transmission range for indoor line-of-sight transmissions between a WRS-TTx-0000­0 Series Sensor and a TE-78x0-0 Series Receiver is 500 ft (152 m). Taking into consideration RF signal absorption and reflection due to metal objects, walls, and furniture found in typical building interiors, the practical average indoor (line-of-sight) transmission range between a sensor and receiver is 200 ft (61 m).
The maximum transmission range for indoor line-of-sight transmissions between a WRS-TTx-0000­1 Series Sensor and a TE-78x0-1 Series Receiver is 375 ft (114 m). Taking into consideration RF signal absorption and reflection due to metal objects, walls, and furniture found in typical building interiors, the practical average indoor (line-of-sight) transmission range between a sensor and receiver is 165 ft (50 m).
The RF signal strength between an installed sensor and receiver can be tested by pressing and releasing the occupancy button on the WRS Series Sensor. Refer to the TE-7800 Series One-to-One Wireless
Room Temperature Sensing System T e ch nical Bulletin (LIT-1201 1097) for more information on determining
the signal strength between a WRS Series Sensor and a TE-7800 Series Receiver.
IMPORTANT: Do not overtighten the mounting screws. Overtightening the mounting screws may damage the mounting base or mounting surface.
5. Reinstall receiver housing to the mounted base (Figure 2).
TE-7800 Series Receivers for One-to-One Wireless Room Temperature Sensing Systems Installation Instructions
3
Page 4

Wiring

Wiring Considerations and Guidelines

Risk of Property Damage.
Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment.
Risque de dégâts matériels.
Ne pas mettre le système sous tension avant d'avoir vérifié tous les raccords de câblage. Des fils formant un court-circuit ou connectés de façon incorrecte risquent d'endommager irrémédiablement l'équipement.
IMPORTANT: Use copper conductors only. Make all wiring in accordance with local, national, and regional regulations. The TE-7800 Series Receivers are low-voltage (less than 30 VAC) devices. Do not exceed the receiver’s electrical ratings.
Follow these guidelines when wiring a receiver:
Route the power supply wires and Ethernet cables at least 2 in. (50 mm) away from the vent slots on the sides of the receiver housing.
Provide slack in the wires and cables. Keep cables routed neatly around the receiver to promote good ventilation, Light-Emitting Diode (LED) visibility, and ease of service.
Wire a TE-7820-x Series Receiver up to 300 ft (91 m) from the VMA14 Series Controller, as shown in Figure 3.
Wire a TE-7830-x Series Receiver up to 100 ft (30 m) from the supported controller, as shown in Figure 4.

Accessories

IMPORTANT: Prevent any static electric discharge
to the TE-7800 Series Receivers. S tatic electric discharge can damage the receiver and void any warranties.
Table 1: Ordering Information (Part 1 of 2)
Product Code Number Product Description
WRS-TTP0000-0
WRS-TTP0000-1 Wireless Room Temperature Sensor, Warmer/Cooler Setpoint Adjustment,
-TTR0000-0
WRS
WRS-TTR0000-1 Wireless Room Temperature Sensor, No Setpoint Adjustment, 10 dBm Transmission
WRS
-TTS0000-0
WRS-TTS0000-1 Wireless Room Temperature Sensor, Setpoint Adjustment Scale: 55 to 80°F and
WRS-SST-100 Wireless Sensing System Tool, 15 dBm Transmission Power WRS-SST-101 Wireless Sensing System Tool, 10 dBm Transmission Power (CE Mark)
-2420
TP
Wireless Room Temperature Sensor, Warmer/Cooler Setpoint Adjustment, 15 dBm Transmission Power
10 dBm Transmission Power (CE Mark) Wireless Room Temperature Sensor, No Setpoint Adjustment, 15 dBm Transmission
Power
Power (CE Mark) Wireless Room Temperature Sensor, Setpoint Adjustment Scale: 55 to 80°F and
12 to 28°C, 15 dBm Transmission Power
12 to 28°C, 10 dBm Transmission Power (CE Mark)
Wall Plug Mount Transformer, 120 VAC to 24 VAC, 20 VA, Class 2
TE-7800 Series Receivers for One-to-One Wireless Room Temperature Sensing Systems Installation Instructions
4
Page 5
Table 1: Ordering Information (Part 2 of 2)
Figure 3: Wiring a TE-7820-x Series Receiver to a VMA14 Series Controller
AVG
HIGH
LOW
ZONE BUS
24 VAC
24 VAC COM
ZONE BUS
to VMA1400
(Tstat)
RF ADDRESS
MULT
XMTRS
TE-7820-0
RECEIVER
24 VAC COM
Power and Zone Bus Interface with
Johnson Controls VMA14 Series Digital Controller,
6 ft (1.8 m) Interface Cable included with TE-7820-x Series RF Receiver
To Supply
Transformer
T
s
t
a
t
2
4
V
A
C
:
2
24 VAC
2
4
V
A
C
:
1
TE-782 0- x Series RF Receiver
with Zone Bus Interface
Johnson Cont r o ls
VMA14 Series
Digital Controller
RF SIGNAL
OFF ON
OFF ON
256
128643216842
1
FIG:te782 0_wrng
Product Code Number Product Description
Y65T31-0
1
CBL-STAT25 25 ft (7.6 m) Zone Bus Interface Cable to Connect TE-7820-x Series Receivers to
CBL-STAT50 50 ft (15.2 m) Zone Bus Interface Cable to Connect TE-7820-x Series Receivers to
CBL-STAT75 75 ft (22.9 m) Zone Bus Interface Cable to Connect TE-7820-x Series Receivers to
CBL-STAT100 100 ft (30.5 m) Zone Bus Interface Cable to Connect TE-7820-x Series Receivers to
Transformer, 102 /208/240 VAC to 24 VAC, 40 VA, Class 2, Foot Mount, 8 in. (20 cm) Primary Leads and Secondary Screw Terminals
VMA14 Series Controllers; Does Not Include Power Cable
VMA14 Series Controllers; Does Not Include Power Cable
VMA14 Series Controllers; Does Not Include Power Cable
VMA14 Series Controllers; Does Not Include Power Cable
1. Additional Y60 Series Transformers are available from Johnson Controls.

Technical Specifications

TE-7800 Series (Part 1 of 3)

Product Codes TE-7820-x Series Receivers for One-to-One Zone Bus Interface Applications
TE-7830-x Series Receivers for One-to-One 0 to 5 VDC Analog Interface Applications
Field Controller Interface TE-7820-x Series Receivers: Power and Zone Bus Interface between TE-7820-
x Series Receiver and VMA14 Series Controller
Power Requirements
TE-7830-x Series Receivers: Power and 0 to 5 VDC Analog Interface between TE-
7830-x Series Receiver and AS-AHU, AS-UNT, AS-VAV, DX-9100, and FXxx Series Controller
24 VAC (+10%/
TE-7800 Series Receivers for One-to-One Wireless Room Temperature Sensing Systems Installation Instructions
-15%), 50/60 Hz, 4.5 VA (Minimum) Class 2 Power Supply
5
Page 6
TE-7800 Series (Part 2 of 3)
Figure 4: Wiring a TE-7830-x Series Receiver to an Analog Interface Field Controlle r
*
Relay Common (green wire) should be connected to either Binary In COM or
Binary In SR C , dependi ng on the field control le r.
24 VAC
Johnson C ontrols
AS-AHU, AS-UNT, AS-VA V, DX-9100, or
FXxx Series Controller
RF ADD R ESS
TE-7830-0
RECEIVER
ANALOG INTERFACE
OUT COMMON
SET POINT OUT
ZONE TEM PERATURE OU T
RELAY COMMO N
LOW BATT ERY REL AY
OCCUPANC Y RELAY
24 VAC COMMON
OFF ON
Tstat LOW B ATTERY
REMOVE FOR AS-AH U, DX-9100
24 VAC COM
24 VA C CO M
OCC BI
BI COM
*
TEMP AI-1
**
SET PT AI
AI COM
24 VAC
RED
BLK
BLU
YEL
GRN
WHT
ORN
BRN
RED
BLK
BLU
YEL
GRN
WHT
ORN
BRN
Note: Remove Jumper J1 for Johnson Controls A S-AHU, DX-910 0, and FXxx Series Controller ap plications that require disablin g t he manual override status via th e zone temperature . Do not rem ove Jumper J1 for Johnson Controls AS - UNT or AS-VAV Controller ap plications .
Jumper J1
RF SIGNAL
TE-783 0- x Series RF Receiver
with Analog Interface
LOW BAT BI
To Supply
Transformer
Power and Analog Interface with
Johnson Controls AS-AHU, AS-UNT, AS-VA V,
DX-9100, or FXxx Series Controller,
6 ft (1.8 m) Interface Cable Included with
TE-783 0- x Series RF Receiver
24 VAC
OFF ON
AVG
HIGH
LOW
OFF ON
256
128643216842
1
**
Zone Temperature Out (white wire) should be connected to analog input AI-1
of the field co nt r oller (zone temperat ur e).
FIG:te78 30_wrng
Addressing TE-7820-x Series Receivers: DIP Switches, Field Adjustable for up to 510 Unique
Ambient Operating Temperature Limits
Ambient Operating Humidity Limits
Ambient Storage Temperature Limits
Ambient Storage Humidity Limits
RF Band Direct-Sequence, Spread-S pectrum, 2.4 GHz ISM Bands Transmission Power TE-78x0-0 Series Receivers: 15 dBm Maximum
Transmission Range
Transmissions Every 60 Seconds (±20 Seconds)
Addresses; for Addresses 0 and 511, the TE-7820-x Series Receiver Matches the N2 Address of the Associated VMA14 Series Controller for Its Actual Address
TE-7830-x Series Receivers: DIP Switches, Field Adjustable for up to 510 Unique Addresses; Addresses 0 and 511 are Invalid
32 to 122°F (0 to 50°C)
5 to 95% RH, Noncondensing
-40 to 160°F (-40 to 71°C)
5 to 90% RH, Noncondensing
TE-78x0-1 Series Receivers: 10 dBm Maximum TE-78x0-0 Series Receivers: 500 ft (152 m) Maximum Indoor Line
200 ft (61 m) Practical Average Indoor TE-78x0-1 Series Receivers: 375 ft (114 m) Maximum Indoor Line-of-Sight;
165 ft (50 m) Practical Average Indoor
-of-Sight;
TE-7800 Series Receivers for One-to-One Wireless Room Temperature Sensing Systems Installation Instructions
6
Page 7
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
TE-7800 Series (Part 3 of 3)
Receiver Outputs TE-7820-x Series Receivers: One Zone Bus Output for Temperature, Setpoint,
Field Strength Measurements, and Low Battery Indication TE-7830-x Series Receivers: Two Analog Outputs for Zone Temperature and Setpoint:
0 to 5 VDC, 2 mA Maximum; Two Binary Outputs for Occupancy and Low Battery: Dry Contacts Rated for 24 VAC, 50 mA Maximum
Temperature System Accuracy 1F° (0.6C°) Over the Range of 55 to 85°F (13 to 29°C);
1.5F° (0.9C°) Over a Range of 32 to 55°F (0 to 13°C) and 85 to 1 1 0°F (29 to 43°C)
Sensor Type Internal 10k ohm Negative Temperature Coefficient (NTC) Thermistor Wiring T erminations and
Network Interfaces
Materials Mounting Compliance (TE-78x0-0 Series
Receivers)
Compliance (TE-78x0-1 Series Receivers)
TE-7820-x Series Receivers: One Two
Supply Power and One Zone Bus Port TE-7830-x Series Receivers: One Two
Supply Power, One Three-Position Terminal Block for Occupancy and Low Battery Binary Output Relays, and One Three-Position Termin al Block for Zone Temperature and Setpoint Temperature Outputs
Gray Plastic Housing with UL94 Screw Mount; Four No. 6 Pan United States: Intended for NEC Class 2 Connection
UL Listed, File E107041, CCN PAZX
-5VB Flammability Rating
UL 94 FCC Compliant to CFR 47, Part 15, Subpart B, Class A Transmission Complies with FCC Part 15.247 Regulations for Low Power Unlicensed
Transmitters Receiver Radio Module FCC Identification: CB2
Canada: Intended for CEC Class 2 Connection UL Listed, File E107041, CCN PAZX7
-5VB Flammability Rating
UL 94 Industry Canada IC: 279A-RFMOD24A
Australia and New Zealand: RCM Mark, Australia/NZ Emissions Compliant Europe: CE Mark – Johnson Controls, Inc., declares that this product is in
compliance with the essential requirements and other relevant provisions of the R&TTE Directive.
South Africa: Accepts Directives for Europe
-5VB Flammability Rating
-Head, Sheet-Metal Screws Included
-Position Terminal Block for 24 VAC Class 2
-Position Terminal Block for 24 VAC Class 2
-RFMOD2400A
Shipping Weight 1.0 lb (0.45 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact:
JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY
JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA
JOHNSON CONTROLS C/O CONTROLS PRODUCT MANAGEMENT NO. 22 BLOCK D NEW DISTRICT WUXI JIANGSU PROVINCE 214142 CHINA
TE-7800 Series Receivers for One-to-One Wireless Room Temperature Sensing Systems Installation Instructions
Published in U.S.A. www.johnsoncontrols.com
7