Johnson Controls TE-637DP-1 Catalog Page

Product/Technical Bulletin TE-637DP-1 Issue Date 0316
24-9378- 3, Rev. C
TE-637DP-1 Surface-mount
Duct Temperature Sensor
The TE-637DP-1 provides temperature sensing in a compact surface-mounted unit for use inside economizer rooftop systems. The unit housing is a durable plastic enclosure that installs easily to the duct surface. A protective membrane prevents sensor contamination due to dust, dirt, and insects.
The TE-637DP-1 has a thermistor temperature sensor with a negative temperature coefficient, and a reference resistance of 2.2k ohms at 77°F (25°C).
Figure 1: TE-637DP-1 Surface-mount Duct
Temperature Sensor
Features and Benefits
Protective Membrane Prevents sensor contamination Quick-mount, 2-screw
Installation
Compact Enclosure for
Mounting Inside Ducts
© 2016 Johnson Controls, Inc. 1 Part No. 24-9378-3, Rev. C www.johnsoncontrols.com Code No. LIT-216325
Reduces installation time
Designed for rooftop unit applications and retrofits; enables surface-mount installation
roduct Overview
P
The TE-637DP-1 outputs temperature signals for use in rooftop economizer applications. The TE-637DP-1 is suitable for use with a Johnson Controls Direct Mount Economizer (DME) Controller.
The TE-637DP-1 is a durable, yet cost-effective solution for sensing temperature. It is housed in an easy-to-install plastic enclosure, which speeds commissioning time and reduces cost.
IMPORTANT: The TE-637DP-1 is intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the TE-637DP-1 could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the TE-637DP-1.
IMPORTANT: Le TE-637DP-1 est destiné à transmettre des données entrantes à un équipement dans des conditions normales de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du TE-637DP-1 risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du TE-637DP-1.
heory of Operation
T
The TE-637DP-1 has a thermistor temperature sensor with a negative temperature coefficient, and a reference resistance of 2.2k ohms at 77°F (25°C). (See Figure 3.)
80,000 70,000 60,000
Resistance
(ohms)
50,000 40,000 30,000 20,000 10,000
0
-40
-20
-40
-290-1820-740460168027
Temperatu r e, °F (°C)
1003812049140
Figure 3: Temperature vs. Resistance
Relationship for the TE-637DP-1
60
imensions
D
3.0 76
3.0 76
2.5
63.5
2.5
63.5
3/16
5
Diameter
1.23 31
Figure 2: TE-637DP-1 Dimensions, in. (mm)
2 TE-637DP-1 Surface-mount Duct Temperature Sensor Product/Technical Bulletin
Table 1: Temperature vs. Resistance
Temperature Resistance
F C
-40 -40 75466
-30 -34 52571
-20 -29 37116
-10 -23 26539 0 -18 19208
10 -12 14062 20 -7 10408 30 -1 7784 40 4 5880 50 10 4484 60 16 3450 70 21 2678 80 27 2095
90 32 1652 100 38 1313 110 43 1051 120 49 847 130 54 687 140 60 561
nstallation
I
(ohms)
ocation Considerations
L
The sensor must be mounted inside a duct or
economizer rooftop system.
Orientation: The sensor must be mounted on a
flat surface in a vertical, upright position. (See Figure 4.)
Placement: Mount the unit at least eight feet
downstream from sources of heat or humidity and away from areas with no air flow.
IMPORTANT: Do not install this TE-637DP-1 in condensing, wet, or damp environmeners. Moisture may cause damage to the TE-637DP-1.
ounting
M
To mount the TE-637DP-1:
1. Using the sensor as a template, mark the location of the two self-tapping screws.
2. Use a drill with an 1/8 in. bit to drill two holes in the duct.
3. Attach the sensor to the duct using a 1/4 in. nut driver and the two included No. 6 sheet metal screws. (See Figure 4.)
Tools Needed
drill with 1/8 in. drill bit  1/4 in. nut driver
Note: The sensor must be mounted in an upright
position.
TE-637DP-1 Surface-mount Duct Temperature Sensor Product/Technical Bulletin 3
Self-tapping
Screws (2)
Duct
Figure 4: TE-637DP-1 Mounting
iring
W
!
WARNING: Electrical Shock Hazard.
Disconnect the power supply before making electrical connections. Contact with components carrying hazardous voltage can cause electric shock and may result in severe personal injury or death.
AVERTISSEMENT: Risque de décharge électrique.
Débrancher l'alimentation avant de réaliser tout branchement électrique. Tout contact avec des composants conducteurs de tensions dangereuses risque d'entraîner une décharge électrique et de provoquer des blessures graves, voire mortelles.
heckout
C
After installation and wiring are complete, apply power and make an operational check as shown in the appropriate controller documentation.
epair and Replacement
R
Field repairs must not be made. To obtain a replacement, contact the nearest Johnson Controls representative.
rdering Information
O
To order a duct-mount temperature sensor, contact your local Johnson Controls representative and specify product code number TE-637DP-1.
Table 2: Accessories
Product Code Number
ACC-BRKT-100
Description
Mounting Bracket for mounting the sensor perpendicular to the duct;
3.25 H x 3.62 W x 0.75 in. D (83 x 92 x 19 mm)
IMPORTANT: Make all wiring connections in
accordance with the National Electrical Code and local regulations.
To wire the TE-637DP-1:
1. Route the wires from the controller to the TE-637DP-1. Use of No. 18 AWG wire is recommended.
2. Connect the wires to the appropriate terminals of the wiring block. (See Figure 5 and refer to the appropriate controller documentation.)
Controller
TEMP
COM
Figure 5: Typical TE-637DP-1 Wiring
4 TE-637DP-1 Surface-mount Duct Temperature Sensor Product/Technical Bulletin
TE-637DP-1
TEMP TEMP
ACC-CBL-100
Wiring Harness, 53 in. (1.3 m)
pecifications
S
Product TE-637DP-1 Surface-mount Duct Temperature Sensor
Reference Resistance 2.2k ohms at 77°F (25°C)
Resistance Change Nonlinear, negative temperature coefficient
Accuracy 0.9°F (0.5°C) in the range of 32 to 158°F (0 to 70°C)
Ambient Operating
Conditions
Survival Operating
Conditions
Ambient Storage
Conditions
Terminal Connections 1/4 in. (6.35 mm) male spade Acceptable Wire Gauge 16 to 24 AWG wire (18 AWG wire recommended) Dimensions (H x W x L) 3.00 x 3.00 x 1.23 in. (76 x 76 x 31 mm)
Shipping Weight 0.50 lb (0.23 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
32 to 131°F (0 to 55°C) 0-100% RH, 85°F (29.4°C) maximum dew point
-22 to 140°F (-30 to 60°C) 0 to 100% RH, 85
-40 to 140°F (-40 to 60°C) 0-100% RH, 85
°F (29.4°C) maximum dew point
°F (29.4°C) maximum dew point
European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact:
JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY
JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA
JOHNSON CONTROLS C/O CONTROLS PRODUCT MANAGEMENT NO. 22 BLOCK D NEW DISTRICT WUXI JIANGSU PROVINCE 214142 CHINA
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc.
TE-637DP-1 Surface-mount Duct Temperature Sensor Product/Technical Bulletin 5