Figure 1: Flush Mount Sensor with Logo
Dimensions, in. (mm)
4 -1/2 (114.3)
2 -3/4 (69.85)
F
i
g
:
D
i
m
TE-6300F Series Flush Mount Sensors
24- 4034-255, Rev. C
Installation Instructions
TE-63xxF-0, TE-63xxF-1
Refer to the QuickLIT website for the most up-to-date version of this document.
Part No. 24-4034-255, Rev. C
Issued March 2016
Applications
The TE-6300F Series Flush Mount Te mperature Sensor is a device that measures air temperatur e, via a temperature sensing element, thermally bonded to a metal electrical box cover. The sensor is designed for direct connection to a supervisory controller.
IMPORTANT: The TE-6300F Series Flush Mount Temperature Sensor is intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the sensor could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the sensor.
IMPORTANT : Le TE-6300F Series Flush Mount Temperature Sensor est destiné à transmettre des données entrantes à un équipement dans des conditions normales de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du sensor risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de con tr ôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du sensor.
IMPORTANT: Do not install the TE-6300F Series
Flush Mount Temperatur e Sensor probe in ambient temperatures beyond the specified 32 to 104°F (0 to 40°C) temperature range. Installing the temperature sensor probe in ambient temperatures beyond this range may damage the unit and void the warranty.
Dimensions
TE-6300F Series Flush Mount Sensors Installation Instructions 1
Mounting
Figure 2: Installing a Sensor Plate to the
Conduit Box
!
Location Considerations
Consider the following mounting location guidelines:
Avoid areas subject to excessive vibration, electrical noise, direct sunlight, or the effects of radiant heat.
Keep electrical wiring as short as possible to minimize temperature error.
Mounting the Temperature Sensor
Mount the temperature sensor as follows:
1. Remove the appropriate knockout on the standard utility conduit box for the application.
2. Make the wiring connection to the system components.
Note: To make wiring easier, the sensor may be suspended from the conduit box using the rubber band.
Note: Level the sensor for appearance; however, the sensor functions normally when not level.
3. Mount the sensor to the wallbox or electrical box using the screws provided.
Wiring
For 1k ohm nickel temperature sensors, wire resistance can cause approximately 1F° (0.56C°) of error for every 250 ft (76 m) run of 18 AWG wire, or every 100 ft (31 m) run of 22 AWG wire. For 1k ohm platinum temperature sensors, wire resistance can cause approximately 1F° (0.56C°) of error for every 150 ft (46 m) run of 18 AWG wire, or every 50 ft (15 m) run of 22 AWG wire. To minimize error due to field wiring, limit the total resistance of all nickel temperature sensor wiring to 3 ohms, and all 1k ohm platinum temperature sensor wiring to 2 ohms.
The 10k ohm thermistor applications tolerate relatively long wiring before the wire resistance adds significantly to the total resistance measured at the controller. As a general rule, a 150 ft (46 m) two-wire 18 AWG run contributes 2 ohms of error, or less than 1F° (0.56C°) error over the sensor operating temperature range.
Refer to the appropriate controller documentation for recommended sensor wiring.
CAUTION: Risk of Property Damage.
Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment.
MISE EN GARDE : Risque de dégâts matériels.
Ne pas mettre le système sous tension avant d'avoir vérifié tous les raccords de câblage. Des fils formant un court-circuit ou connectés de façon incorrecte risquent d'endommager irrémédiablement l'équipement.
IMPORTANT: Use copper conductors only. Make all wiring connections in accordance with local, national, and regional regulations. Do not exceed the TE-6300F Series Flush Mount Temperature Sensor’s electrical ratings.
Wiring Recommendations
IMPORTANT: Use proper Electrostatic Discharge (ESD) precautions during installation and operation to avoid damaging the electronic circuits. Use electrical tape to wrap the ends of the wire leads a minimum of 1 in. (25 mm), as well as to cover the wire nuts.
Use the wire nuts provided for connecting the lead wires to the controller wiring.
TE-6300F Series Flush Mount Sensors Installation Instructions2