TE-6300 Series Temperature Sensors
TE-6300 Series Temperature Sensors
Code No. LIT-1900217
Issued June 2016
Description
The TE-6300 Temperature Sensor line
provides economical solutions for a wide
variety of temperature sensing needs,
including wall-mount, outdoor-air, duct,
strap-mount, well-insertion, duct-averaging,
and Variable Air Volume (VAV) flange-mount
duct-probe applications. The TE-6300 line
offers both a metal and a plastic enclosure for
the most popular models.
Sensors are available in the following types:
• 1k ohm thin-film nickel
• 1k ohm nickel averaging
• 1k ohm thin-film platinum
• 100 ohm platinum equivalent averaging
• 1k ohm platinum equivalent averaging
• 2.2k (2,252) ohm thermistor
• 10k ohm thermistor, Johnson Controls®
Type II
Each sensor is packaged with the necessary
mounting accessories to maximize ordering
and installation ease and reduce both
commissioning time and cost.
Refer to the TE-6300 Temperature Sensors
Product Bulletin (LIT-216320) for important
product application information.
Features
• full line of versatile sensors — supports all
your temperature sensing needs from a
single supplier: wall mount, outdoor air,
duct probe, duct averaging, strap-mount,
well insertion, and flange mount duct probe
• single assembly ordering — simplifies
ordering; provides a complete assembly in
one box
• models featuring an integral NPT Adaptor
— increase sensor connection strength,
which eliminates the need for a special
adaptor
• models with a stainless steel sensor probe
— protect the sensor while increasing
corrosion resistance
• metal enclosure (TE-63xxM Models only)
— meets plenum requirements
• models featuring a retainer for the sensor
holder — allow you to lock the sensor
holder into the conduit box
• brushed stainless steel mounting plate —
offers a durable, aesthetically pleasing
design
• low profile flush mount design — provides
a tamper-proof installation ideally suited for
schools, sporting complexes, retailers,
prisons, and more
All TE-6300 series sensors are two-wire,
passive, resistance output devices.
TE-63xxA Models
The TE-63xxA (adjustable length) models:
• provide a thermoplastic mounting flange
and gland nut to adjust the length of the
probe
The performance specifications are nomina l and conf orm to accep table industr y standar ds. For ap plications a t condition s beyond th ese specification s, consult the local Johnson Controls o ffice.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2016 Johnson Controls, Inc.
• include two hex-head self-drilling screws
for mounting
• come equipped with a 10 ft (3 m)
plenum-rated cable with 1/4 in. (6.35 mm)
female insulated quick-connect
terminations on leads
TE-63xxF Models
The TE-63xxF (flush mount) models:
• provide a low profile when installed in an
electrical box
• feature thermally isolated sensor from the
wall with a foam pad
• offer a rugged stainless steel cover
• provide 22 AWG lead wires with low
voltage installation
TE-63xxM Models
The TE-63xxM (metal enclosure) models:
• come with a corrosion-protected steel
enclosure with a 0.88 in. (22 mm) hole for a
1/2 in. (12.7 mm) conduit fitting
• include two hex-head self-drilling screws
for mounting the duct and duct averaging
models
• offer (well models only) either a direct
mount or 1/2-14 NPT threaded well sensor
holder for mounting in TE-6300W Series
thermal wells (Order the thermal well
separately.)
• provide optional well sensor holders (order
separately) to mount duct models in
thermal wells.
• meet UL 1995 plenum use requirements
• offer optional accessory kit (order
separately) to replace plastic hole plug and
wiring bushing to meet International
Mechanical Code (IMC) requirements
TE-63xxP Models
The TE-63xxP (plastic enclosure) models:
• provide a thermoplastic conduit box with
1/2-14 NPT female thread for connecting to
conduit
• provide aluminum mounting plate and
1/2-14 NPT threaded hub mounting options
for the duct and duct averaging models
• use the 1/2-14 NPT female thread to mount
the Outdoor Air models directly to ridged
conduit
• provide optional sensor holders (order
separately) to mount duct models in
thermal wells
• offer an optional accessory metal cover kit
(order separately) to replace the plastic
cover to meet UL 1995 plenum use
requirements
• include a replaceable sensing probe on
duct probe, outdoor air, and well insertion
models
TE-63x4P Wall Mount Models
The TE-63x4P (plastic enclosure) models:
• come with a white thermoplastic ventilated
cover with a brushed aluminum face plate
and a steel mounting plate for surface
mounting
• include faceplates for both horizontal and
vertical mounting
• offer an accessory mounting kit for
mounting to a standard electrical box
• offer optional covers
TE-63xS Models
The TE-63xS (Strap-Mount) models:
• provide a 1/4 in. (6.35 mm) diameter
stainless steel probe without an enclosure
• include three cable ties for mounting to
pipe up to 2-5/8 in. (67 mm) diameter
• come equipped with a 10 ft (3 m) plenum
rated cable
• meet UL 1995 plenum use requirements
• offer an accessory mounting kit for
mounting to a pipe up to 11 in. (280 mm)
diameter
TE-63xxV Models
The TE-63xxV (VAV flange mount) models:
• provide a stainless steel mounting flange
with two hex-head self-drilling mounting
screws
• come equipped with a 10 ft (3 m) plenum
rated cable with 1/4 in. (6.35 mm) female
insulated quick-connect terminations on
leads
• meet UL 1995 plenum use requirements
Repair Information
If the TE-6300 Series Temperature Sensor
fails to operate within its specifications, refer
to the TE-6300 Series Temperature Sensors
Product Bulletin (LIT-216320) for a list of
repair parts available.
www.johnsoncontrols.com
1
TE-6300 Series Temperature Sensors (Continued)
Selection Chart
TE-6300 Temperature Sensor Models (Part 1 of 2)
Sensor Mounting Style Probe Length
in. (mm)
Nickel
(1k ohm)
Platinum
(1k ohm)
Adjustable
Averaging 8 ft (2.4 m) TE-6315M-1
Duct 4
Flange 4
Flush N/A TE-6310F-0
Outdoor Air 3 (76) TE-6313P-1
Strap-Mount 3 (76) TE-631S-1
Wall
Well 6 (152) TE-631AM-1
Adjustable 8
Duct 4
Flange 4
Flush N/A TE-6350F-0
Strap-Mount 3 (76) TE-635S-1
Outdoor Air 3 (76) TE-6353P-1
Wall
Well 6 (152) TE-635AM-1
1
2
2
8 (203) TE-6311A-1
17 ft (5.2 m) TE-6316M-1
(102)
8
(203)
18 (457) TE-631JM-1
(102)
8
(203)
N/A TE-6314P-1
(203)
8
(203)
(102)
(203)
8
18 (457) TE-635JM-1
(102)
8
(203)
N/A TE-6324P-1
(203)
8
Product Code
Number
TE-6315P-1
TE-6315V-2
TE-6316P-1
TE-6316V-2
TE-631GM-1
TE-6311M-1
TE-6311P-1
TE-631GV-2
TE-6311V-2
TE-6310F-1
TE-631AM-2
TE-631AP-1
TE-6312M-1
TE-6312P-1
TE-6351A-1
TE-635GM-1
TE-6351M-1
TE-6351P-1
TE-635GV-2
TE-6351V-2
TE-6350F-1
TE-635AM-2
TE-635AP-1
TE-6352M-1
TE-6352P-1
1
1
3
3
Optional Accessories (Part 1 of 2)
Product Code Number Description
F-1000-182 Thermal Conductive Grease for element wells (8 oz.)
T-4000-119 Allen Head Tool for Wall Mount Cover Screws (order in multiples of 30)
TE-1800-9600 Mounting Hardware for mounting the wall mount unit to a wall box
TE-6001-8 Element Holder for mounting an averaging sensor (order in multiples of 10)
TE-6001-13 Metal Cover and Gasket Kit (5 per package)
TE-6300-101 12 in. (305 mm) (1k ohm) Nickel Probe (cut to an appropriate length)
TE-6300-103 1/2-14 NPT Plastic Sensor Holder without retainer (order in multiples of10)
TE-6300-105 12 in. (305 mm) (1k ohm) Platinum Class A Probe (cut to an appropriate length)
TE-6300-601 8 in. (203 mm), 1k ohm Nickel Probe
TE-6300-603 3 in. (76 mm), 1k ohm Nickel Probe
TE-6300 Temperature Sensor Models (Part 2 of 2)
Sensor Mounting Style Probe Length
Platinum
Equivalent
Thermistor
(2.2k ohm)
Thermistor
(10k ohm)
Type II
1. Two TE-6001-8 Element Holders come with the platinum equivalent
averaging sensors. Order separately to use with a nickel averaging sensor .
2. Order the TE-1800-9600 Mounting Hardware separately to mou nt the wall
unit to a wallbox.
3. TE-631AM-1, TE-635AM-1, and TE-636AM-1 include TE-6300-612 brass
threadless well adaptor for retrofit to TE-6300W-103 or WZ-1000-5
thermowells.
1k ohm
Averaging
100 ohm
Averaging
Adjustable 8
Duct 8
Flange 4
Outdoor Air 3 (76) TE-6343P-1
Wall
Well 8
Adjustable 8
Duct 4
Flange 4
Flush N/A TE-6360F-0
Outdoor Air 3 (76) TE-6363P-1
Strap-Mount 3 (76) TE-636S-1
Well 6 (152) TE-636AM-1
1
1
2
1
in. (mm)
10 ft (3 m) TE-6327P-1
20 ft (6.1 m) TE-6328P-1
10 ft (3 m) TE-6337P-1
20 ft (6.1 m) TE-6338P-1
(203)
(203)
(102)
8
(203)
N/A TE-6344P-1
(203)
6 (152) TE-634AM-2
(203)
(102)
(203)
8
18 (457) TE-636JM-1
(102)
(203)
8
8
(203)
1
Number
TE-6341A-1
TE-6341P-1
TE-634GV-2
TE-6341V-2
TE-6342M-1
TE-6361A-1
TE-636GM-1
TE-6361M-1
TE-6361P-1
TE-636GV-2
TE-6361V-2
TE-6360F-1
TE-636AM-2
TE-6362M-1
Product Code
3
The performance specifications are no minal and co nform t o acceptab le ind ustry standar ds. For appl ications at condition s beyond these specifica tions, consult the local Johnson Co ntrols office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2016 Johnson Controls, Inc.
www.johnsoncontrols.com
2