Johnson Controls TE-631xM, TE-635xM, TE-634xM, TE-6300M Series, TE-636xM Installation Instructions Manual

Figure 1: Sensor Dimensions, in. (mm)
0.875 (22.2)
Side View
1.20
(30.5)
1.87
(47.5)
4.73 (120.1) maximum
7.73 (196.3) maximum
Figure 2: Installing the Well Insertion Sensor
F
I
G
:
s
n
s
_
i
n
s
t
or
Sensor
Probe
TE-6300W-101 TE-6300W-102
Thermowell
Direct Mount for
Set Screw
1/2 in.
NPT
Threaded Mount for
Well Adaptor
Set Screw
TE-6300W-110 Thermowell
TE-6300M Series Well Insertion Temperature Sensors
24- 4034-182, Rev. G
Installation Instructions
TE-631xM, TE-635xM, TE-634xM, TE-636xM
Refer to the QuickLIT website for the most up-to-date version of this document.
Part No. 24-4034-182, Rev. G
Issued March 2016
Applications
IMPORTANT: The TE-6300M Series Well Insertion
Temperature Sensors are intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the sensor could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the sensor.
IMPORTANT : Le TE-6300M Series Well Insertion Temperature Sensor est destiné à transmettre des données entrantes à un équipement dans des conditions normales de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du sensor risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de con tr ôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du sensor.
Dimensions
1.80 (45.7)
1.87 (47.5)
0.60 (15.2)
Front View
Mounting
Location Considerations
Consider the following mounting location guidelines:
Keep electrical wiring as short as possible to minimize temperature error.
Mounting the Temperature Sensor
See Figure 2 and mount the temperature sensor:
6 in. (152 mm) Probe Models
m
i d
_
s
n
s : G
I F
Installation
IMPORTANT: Do not install the TE-6300M Series
Well Insertion Temperature Sensor in ambient temperatures beyond the specified -50 to 220°F (-46 to 104°C) temperature range. Installing the temperature sensor in ambient temperatures beyond this range may damage the unit and void the warranty.
8 in. (203 mm) Probe Models
TE-6300M Series Well Insertion Temperature Sensors Installation Instructions 1
Note: The Johnson Controls® TE-6300W-101
!
thermowell contains thermal compound. The TE-6300W-102 and TE6300W-110 do not contain thermal compound. Add thermal compound (F-1000-182, or equivalent) before inserting the probe if the well does not include thermal compound. For proper sensor function, mount the well so that any condensation that forms drains out of the probe.
1. If the thermowell is:
Direct Mount (TE-63xAM-2), loosen the set screw
Threaded (TE-63x2M), screw the well adaptor into the thermowell and loosen the well adaptor set screw
2. Insert the sensor probe into the thermowell until it touches the bottom.
3. Pull back the probe approximately 1/8 in. (3 mm) and then tighten the set screw.
4. Wire the sensor to the controller.
5. Reposition the cover and tighten the cover screws.
Wiring
For 1k ohm nickel temperature sensors, wire resistance can cause about 1F° (0.56C°) of error for every 250 ft (76 m) run of 18 AWG (1.0 mm diameter) wire, or every 100 ft (31 m) run of 22 AWG (0.6 mm diameter) wire.
For 1k ohm platinum temperature sensors, wire resistance can cause about 1F (0.56C) of error for every 150 ft (46 m) run of 18 AWG (1.0 mm diameter) wire, or every 50 ft (15 m) run of 22 AWG (0.6 mm diameter) wire. To minimize error due to field wiring, limit total resistance of all nickel temperature sensor wiring to 3 ohms, and all platinum temperature sensor wiring to 2 ohms.The 2.2k and 10k ohm
thermistor applications permit wiring to be relatively long before wire resistance adds significantly to total resistance measured at the controller. As a general rule, a 150 ft (46 m) two-wire 18 AWG (1.0 mm diameter) run contributes 2 ohms of error, or less than 1F (0.56C) error over the sensor operating temperature range.
Refer to the appropriate controller documentation for recommended sensor wiring. Secure the wiring bushing or conduit only to the temperature sensor base. See Table 1 for an explanation of the lead wiring color convention
Table 1: Lead Wiring Color Code
Sensor Type Lead Color
1k ohm Nickel White 1k ohm Platinum White with Blue Stripe
2.2k ohm Thermistor Red 10k ohm Thermistor White with Green Stripe
CAUTION: Risk of Property Damage.
Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment.
MISE EN GARDE : Risque de dégâts matériels.
Ne pas mettre le système sous tension avant d'avoir vérifié tous les raccords de câblage. Des fils formant un court-circuit ou connectés de façon incorrecte risquent d'endommager irrémédiablement l'équipement.
IMPORTANT: Use copper conductors only. Make all wiring connections in accordance with local, national, and regional regulations. Do not exceed the TE-6300M Series Well Insertion Temperature Sensor’s electrical ratings.
TE-6300M Series Well Insertion Temperature Sensors Installation Instructions2
Repair Information
If the TE-6300M Series Well Insertion Temperature Sensor
fails to operate within its specifications, replace the unit. For a replacement sensor, contact the nearest Johnson Control s representative.