Johnson Controls TCN-890x Catalog Page

Controls Group 507 E. Michigan Street
P.O. Box 423, Milwaukee, WI 53202 Code No. LIT-1900160
tcn890xs 1900160 9thcc:na - pending Rev:

TCN-890x

Electronic Room Thermostat

left ft: right ft:
standard Sect# = 0
seQ# = 8
tcb-890x cat01.tif
• thermostat includes wallbox and surface mounting plates and all installation hardware to mount directly to drywall or a standard U.S. wallbox
• models include an adjustable deadband:
- TCN-8901 has 0 to 10 VDC Reverse
Action (RA) and Direct Action (DA) outputs that feature separate proportional band adjustments
- TCN-8906 has two On/Off RA and DA
triac outputs that feature separate differential adjustments
Applications
The TCN-8900 Series features separate RA/DA outputs for automatic changeover of heating and cooling applications.
To Order
Specify the code number in the following selection chart.
Description
The TCN-8900 Series is a family of analog electronic controllers designed to control heating and/or cooling valves or dampers. The TCN-8901 has two 0 to 10 VDC proportional outputs, one for heating and one for cooling. The TCN-8906 has two On/Off
triac outputs, one for heating and one for cooling, capable of switching 0.5 A at 24 VAC.
The dual-scale setpoint dial enables the room occupant to adjust the thermostat setpoint within the range of 54 to 82°F (12 to 28°C). Johnson Controls offers an optional Dial Stop Screw Kit for applications where fixing or limiting adjustment to the temperature range is appropriate.
Features
• small, compact package provides similar look and feel to the Metastat sensors
• local setpoint provides easy wiring and installation
• globally scaled unit includes setpoint scale in both Fahrenheit and Celsius ranges 54 to 82°F (12 to 28°C)
• universal quick-mount design saves time and simplifies installation
Specifications
TCN-890x Series Electronic Room Thermostat
Power Requirements 24 VAC ±15% at 50/60 Hz, Class 2 Power Consumption 1.5 VA with No Load
Inputs
Adjust­ments
Output
Field Connectio ns Screw Terminals for 24 to 14 AWG Wire Mounting
Housing Protection NEMA 1, IP30 (IEC 60529)
Ambient Conditions
Dimensions (H x W x D) 3.15 x 3.15 x 1.30 in. (80 x 80 x 33 mm)
Agency Listings
Unoccupied Input
Set Point 54 to 82°F (12 to 28°C)
Dead Band 0 to 4F° (0 to 2C°)
Differential
Proportional
TCN-8901
TCN-8906
Operating
Storage
Remove Factory-Installed Jumpe r on Screw Terminal Block; Fixed 9F° (5C°) Nominal Offset
RA/DA Remote Cont act
(Model TCN-8906 Only) 0.4 to 4F° (0.2 to 2C°) ; Independent Adjustments for RA and DA Outputs
(Model TCN-8901 Only) 2 to 7F° (1 to 4C°); Independent Adjustments for RA and DA
Band
Outputs Analog, 0 to 10 VDC, 10 mA Maximum;
Output Normal State is Off On/Off, Triac 24 VAC, 0.5 A Maximum;
Output Normal State is Off
Standard Bases for Surface or U.S. Wallbox Mounting, Including Hardware
White Plastic Cover with Dark Gray Plastic Mounting Base
32 to 122°F (0 to 50°C) 10 to 95% RH (Noncondensing)
-4 to 158°F (-20 to 70°C) 10 to 90% RH (Noncondensing)
CE Compliance: EMC (89/336 EEC) According to the Standard E N 5008 1-1 and EN 50082-1 FCC and DOC Compliant

Selection Chart

Code Number Description Outputs (2)
TCN-8901-2161 Electronic
TCN-8906-2161
Note: Setpoint range: 54 to 82°°°°F (12 to 28°°°°C)
Room
Thermostat
0 to 10 VDC Analog R A 0 to 10 VDC Analog D A
On/Off RA Triac On/Off DA Triac
Sensor
Input
Built-in
Accessories
Code Number Description
ACC-INSL-0 Foam Pad Kit for Wallbox Mounting (10 per package ) ACC-INSL-1 Foam Pad Kit for Sur face Mo unting (10 per package) T-4000-119 Allen-Head Adjustme ntT ool (30 per package) TM-9100-8901 Dial Stop Screws Kit (100 self-tapping screws per package) TM-9100-8931 Plastic Surface Mounting Kit
Repair Parts
Code Number Description
TE-67E0-600 Replacement End Caps (10 per package) TE-67W-600 Wallbox M ounting Kit
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
1/2
© 08/02 Johnson Controls, Inc
Unoccupied Offset
Unoccupied Offset
Unoccupied Offset
Unoccupied Offset
TCN-890x Electronic Room Thermostat (Continued)

Dimensions

3.15 (80) 1.29 (33)
65 70
20
60
16
3.15
12 28
55
(80)
C
F
(tcn-890x cat06.eps)
75
24
Setpoint
80
Dial
Temperature Scale
TCN-890x Cover Dimensions, in. (mm)
tcn-890x cat07.eps)
2.37 (60.3)
UP
2.37
(60.3)
12
3
5 6
4
10
8
9
12
11
7
2.40
(60.9)

Control Sequence Diagrams

tcn-890x cat04.eps
Unoccupied Offset
100%
Output
Unoccupied Offset Unoccupied Offset
0%
UnoccupiedUnoccupied
RA Output (Heating) DA Output (Cooling)
TCN-8901 0 to 10 VDC Control Sequence
tcn-890x cat05.eps
Unoccupied Offset
On
Output
Unoccupied Offset Unoccupied Offset
Controls Group 507 E. Michigan Street P.O. Box 423, Milwaukee, WI 53202 Code No. LIT-1900160
Unoccupied Offset
Temperature
RA PB
Setpoint
DA
DBDB
PB
OccupiedOccupied
UnoccupiedUnoccupiedUnoccupiedUnoccupied
Unoccupied Offset
Temperature
2.43 (61.7)
TCN-890x Base Dimensions, in. (mm)
tcn-890x cat08.eps)
3.07 (78)
4.65 (118)
1.26 (32)
3.28
(83.4)
TCN-890x Wallplate Dimensions, in. (mm)
Wiring Diagrams
24 VAC
0to10V Heating Actuator
0to10V Cooling Actuator
RA/DA Contact
Unoccupied Contact
Do Not Connect
Factory Installed Jumper
Do Not Connect
Do Not Connect
Wiring the TCN-8901, 0 to 10 V
1
2
3
4
5
6
7
8
9
10
11
12
Internal Connection (Pins 4, 8, and 11)
Off
UnoccupiedUnoccupied
tcn-890x cat02.eps
TCN-8901
24 VAC
24 VAC Common
RA Output
Common
DA Output
RA/DA Input
Common
Unoccupied Input
Common
Sensor
DBDB
RA DIF
OccupiedOccupied OccupiedOccupied
Setpoint
DA DIF
TCN-8906 On/Off Control Sequence
tcn-890x cat03.eps
24 VAC
On/Off Heating Actuator
On/Off Cooling Actuator
RA/DA Contact
Unoccupied Contact
Do Not Connect
Factory Installed Jumper
Do Not Connect
Do Not Connect
Internal Connection (Pins 1 and 4, 8 and 11)
Wiring the TCN-8906, On/Off
Temperature
DA Output (Cooling)RA Output (Heating)
1
2
3
4
5
6
7
8
9
10
11
12
UnoccupiedUnoccupied
TCN-8906
24 VAC
24 VAC Common
RA Output
24 VAC
DA Output
RA/DA Input
Common
Unoccupied Input
Common
Sensor
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
2/2
© 08/02 Johnson Controls, Inc