Johnson Controls S1-HDSTACK01 User Manual

ACCESSORY KIT INSTALLATION MANUAL
S1-HDSTACK01 - STACKING RACK
FOR USE WITH MODELS TCHD / YCHD
IN STAL LA TION
1. This kit is designed to stack two horizontal discharge units. It will handle both sizes of horizontal discharge unit foot print.
2. The stacking kit must be assembled and anchored securely before any horizontal discharge units are placed on the stacking frame.
NOTE - ALL ANCHORING HARDWARE IS FIELD SUPPLIED
CONCRETE WALL
3. Horizontal discharge units should be mounted so that the front of the units are closest to the front edge of the stacking frame. This will allow proper air circulation around the back of the unit.
4. See hardware details for proper location of bolts, nuts, and washers.
CONCRETE BLOCK WALL
TOP SHELF
MINIMUM (2) 3/8" Ø HILTI KWIK BOLTS III
2 ½" MIN I MUM EMBEDMENT
WOOD STUD WALL
4X BLOCKING CONTINUOUS
TOP SHELF
MINIMUM (5) 3/8" Ø LAG BOLTS
TOP SHELF
A. SOLID GROUTED
MINIMUM (2) 3/8" Ø HILTI KWIK BOLTS III
B. HOLLOW CELL
(2) 3/8" Ø ALL THREAD IN HILTI HIT HY-20 EPOXY
A. 2 ½" MIN I MUM EMBEDMENT B. 3 ½" MIN I MUM EMBEDMENT
STEEL STUD WALL
18 GAUGE BLOCKING W/ (2) #8 SMS EACH END AS NEEDED
TOP SHELF
MINIMUM (6) #10 SMS
3" MIN I MUM EMBEDMENT
CON CRETE PLATFORM
(5) 7/16" Ø HOLES FOR CONNECTING TO WALL (EXCEPT FOR STEEL ATTACHMENT)
MIN I MUM (2 EACH FLANGE) 3/8" Ø HILTI KWIK BOLTS III
2 ½" MIN I MUM EMBEDMENT
STACKING RACK
3" TYP FLANGE W/(2) 7/16" Ø HOLES FOR ANCHORING TO CONCRETE PLATFORM (TYP OPPOSITE SIDE)
18 GAUGE MINIMUM
CONCRETE PLATFORM
Johnson Controls Unitary Products 433082-UAI-A-0112
433082-UAI-A-0112
ITEM DE SCRIP TION QTY
1
2
3
4
5
6
Not Shown
Not Shown
Not Shown
Not Shown
Chan nel As sem bly
Bot tom Shelf
Cor ner Post
Top Shelf
Side Brace
Back Brace
3/8" X 1" Hex Head Bolt
3/8" Flat Washer
3/8" Lock Nut
Spacer Wall
64
79
2
2
4
1
4
2
FRONT END
2
2
47" I.D.54"
1 ½" TYP.
5/16 " X 1 SLOTTED HOLE W/ ¼" Ø SAE GRADE 8 BOLT (TYP. EACH STRAP)
3 ½"
47"
3 ½"
47
13
48
" I.D.
16
13
54
" O.D.
16
(2) ¼" Ø SAE GRADE 8 BOLT (TYP. 8)
¼" Ø SAE GRADE 8 BOLT (TYP. 4 PER STRAP)
21" I.D.
27" O.D.
13
"
16
21"
3 TYP.
A'
2-9
2"
3 ½"
SEC TION A-A'
5
1
"
8
Sub ject to change with out no tice. Printed in U.S.A. Copy right © 2012 by Johnson Controls, Inc. All rights re served.
John son Con trols Uni tary Prod ucts
A
5005 York Drive
Nor man OK 73069
3"
2"
2-9
433082-UAI-A-0112/YKISTRK01
Supersedes: Nothing
Loading...