P28 and P128 Series Lube Oil Controls
with Built-in Time Delay Relay
Manual or automatic reset models are available with factory set and sealed time delays of 30, 45, 60, 90, or 120 seconds (all time delays may not be available on all models). The P128 is the same control as the P28 but with 1/4 inch male flare pressure connections.
Master Catalog 125
Pressure Controls Section P
Product/Technical Bulletin P28
Issue Date 0498
Figure 1: P128AA
Features and Benefits
Built-in Time Delay Relay with Ambient Compensation
Trip-free Manual Reset Provides manual reset that cannot be overridden
Replaceable Time Delay Relay Assembly
Available with Runlight and Alarm Terminals
Minimizes timing fluctuations due to temperature variations
by pressing and holding the reset button
Allows easy field replacement of the time delay relay and terminal board
Allows the control to be wired for normal oil pressure runlight signals and shutdown alarm circuits for remote monitoring of oil pressure status
© 1998 Johnson Controls, Inc.
Part No. 24-7664-605, Rev. A Code No. LIT-125420
1
ntroduction
I
!
WARNING: Personal injury hazard. All
P28 and P128 controls are designed as lubrication protection controls. Failure of the P28 or P128 could allow the refrigeration compressor to be damaged in a way that may not be apparent upon visual inspection. Follow proper procedures and the compressor manufacturer’s instructions, as well as any warning signs on or around the equipment, when discharging and disassembling the compressor.
Environmental damage hazard. If leakage of sensed
media (such as refrigerant or oil) can be harmful to the environment, or hazardous in any way, user must provide for proper containment.
The P28 and P128 controls measure the net oil pressure available to circulate oil throughout a pressure-lubricated refrigeration system. The net oil pressure is the difference between the oil pressure at the pump discharge and the refrigerant pressure in the compressor crankcase.
Example: If the oil pressure pump discharge reading
is 90 psi (621 kPa) and the crankcase pressure is 70 psi (483 kPa), the net oil pressure is 20 psi (138 kPa).
The P28 and P128 have a built-in time delay relay. This relay allows the oil pressure to build up for the time delay period before the compressor trips. This also prevents nuisance lockouts due to intermittent loss of oil pressure. The time delay relay is a “trip free” device. The manual reset cannot be overridden by pressing and holding the reset button.
Manual reset models are available with time delays of 30, 45, 60, 90, or 120 seconds. Automatic reset models are available with a 90-second time delay. The time delay relay is compensated to minimize the effect of ambient temperature variations. However, the time delay relay will be affected by voltage variations.
Dimensions
Figure 2: P28 or P128 Dimensions (in./mm)
peration
O
When the compressor starts, the timer is energized because the net oil pressure of the system is zero. During normal operation, the net oil pressure should build up to the pressure switch’s cut-out setting (scale setting) plus the switch differential (3 to 5 psi [21 to 34 kPa]) within the required time delay, causing the time delay relay to de-energize.
If the net oil pressure does not rise to the cut-out pressure setting plus the switch differential within the required time delay, the time delay relay trips and stops the compressor.
If the net oil pressure drops below the cut-out pressure setting during the compressor’s run cycle, the time delay relay energizes. If the net oil pressure returns within the time delay, the time delay relay de-energizes and the compressor continues to operate normally. If the net oil pressure does not return within the time delay, the control shuts down and locks out the compressor.
2 P—P28 and P128 Series Lube Oil Controls with Built-in Time Delay Relay Product/Technical Bulletin
Example: Net oil pressure (oil pump pressure minus
crankcase pressure) required to the bearings is 9 psi (62 kPa). The control scale setting should be 9 psi (62 kPa). The switch differential is 5 psi (34 kPa). Upon initial start of the compressor, the time delay relay energizes. If the net oil pressure does not build up to 14 psi (97 kPa), or the scale setting (9 psi) plus the switch differential (5 psi), during the time delay, the control breaks the circuit to the compressor. If the pressure of 14 psi (97 kPa) is reached during the time delay, the time delay relay de-energizes and the compressor continues to operate normally.
nstallation
I
Mounting
Pressure Connections
!
CAUTION: Equipment damage hazard.
Avoid sharp bends or kinks in the capillary or tubing to avoid damage to the capillary.
Coil and secure excess capillary or tubing. Because harmonic vibration can break the capillary or tubing, some slack must be provided.
Do not allow the capillary or tubing to rub against metal surfaces where friction can cause damage.
When using a control with 1/4 in. / 6.4 mm tubing, a pulsation damper must be used. Pulsation can cause excessive wear and damage the control.
!
CAUTION: Equipment damage hazard.
A P28AN or P28DN control used for ammonia service must be mounted separately from the electrical cabinet. An ammonia leak could damage the electrical circuitry.
Do not use Johnson Controls/Penn Ecosafe® hose tubing in applications with ammonia or other corrosive refrigerants. Corrosion could cause tube breakage and refrigerant leakage.
Use only the mounting screws supplied with the control. Damage to internal components may occur if other screws are used.
The P28 and P128 controls are not position sensitive and can be mounted in any position.
Use the two mounting screw holes located on the back of the control case to mount the control directly to a wall or panel board. Mount the control so that the pressure connections on the bellows are above the crankcase liquid level of the equipment being controlled.
Note: When mounting the control to a
compressor is required, a mounting bracket (Part No. 271-51) is available.
1. Purge all tubing and lines before connecting the pressure control.
2. Connect the oil pressure line pump discharge to the pressure connector labeled “OIL.”
3. Connect the crankcase pressure line to the pressure connector labeled “LOW.”
4. Coil and secure excess capillary or tubing to avoid vibration.
Wiring
!
WARNING: Shock hazard. Disconnect
all power supplies before making wiring connections to avoid electrical shock or damage to the equipment.
Make all wiring connections using copper conductors only.
Wire in accordance with National Electric Code and local regulations. For maximum electrical rating of the control, see the label inside the control cover.
Use the terminal screws furnished (8-32 x 1/4 in. binder head). Substitution of other screws may cause faulty connections.
See Figures 3 through 10 for typical wiring diagrams or refer to the compressor manufacturer’s specifications.
P—P28 and P128 Series Lube Oil Controls with Built-in Time Delay Relay Product/Technical Bulletin 3