AC CURRENT SWITCHES
RIBXRF
Enclosed Self-Powered Solid Ring Remote
Fixed 1.25-150 Amp AC Sensor
Sensor Contact
SPECIFICATIONS
Operating Temperature:
Humidity Range:
Dimensions:
Remote Dimensions:
Wire Length:
Approvals:
Housing Rating:
Current
Sensor
Circuitry
AXKT
CT
Gry
Gry
-30 to 140˚ F
5 to 95% (noncondensing)
4.00˝ x 4.00˝ x 1.80˝ with .50˝ NPT Nipple
1.863˝ x 1.460˝, .500˝ I
16˝, 600V Rated
UL Listed, UL916, UL864, C-UL, California
State Fire Marshal
UL Accepted for Use in Plenum, NEMA 1
Wire
Being
Monitored
RIBXRA
Enclosed Self-Powered Solid Ring Remote
Adjustable 1.25-150 Amp AC Sensor
Wire
Being
Monitored
Current
Sensor Contact
Sensor
Circuitry
FUNCTIONAL DEVICES CERTIFIED FOR USE WITH ECMS
Sensor Threshold:
nside Diameter
Sensor Range:
Max Sense Voltage:
Sensor Contact Status:
AXKT
CT
Gry
Gry
Sensor Type:
External, with contact status
Fixed, 1.25 Amps (RIBXRF)
Adjustable, 1.25-150 Amps (RIBXRA)
1.25-150 Amps
600 Vac
Current below threshold: Open / LED OFF
Current above threshold: Closed / LED ON
Made in USA
Meets
“Buy American”
of ARRA 2009
Sensor Contact:
• Solid State Contact
• 30 Vac/dc, .4 Amp Max.
• When sensor contact is o
(open), leakage
<30 uA @ 30Vac/dc
When sensor contact is on
•
(closed), voltage drop
< .3 Vac/dc @ .1 Amp
< 1.6
Vac/dc @ .4 Amp
071717