RELAY & AC CURRENT SWITCH COMBOS
RIBXLC Series
Enclosed Relay/AC Sensor Combinations, SPDT with 10-30 Vac/dc Coil
RIBXLCA, RIBXLCF, RIBXLCEA
Sensor Feedback
Current Sensor
Status
10-30 Vac/dc
Comm
+
Blu - N/C
Yel - Comm
Org - N/O
RIBXLCV, RIBXLCEV^
10-30 Vac/dc
Comm
V
V
0-10 Vdc
0-5 Vdc
Comm
Blu - N/C
Yel - Comm
Org - N/O
Made in USA
Meets
“Buy American”
of ARRA 2009
RIBXLCRA, RIBXLCRF
Sensor Feedback
Current Sensor
Status
10-30 Vac/dc
Comm
SPECIFICATIONS
# Relays & Contact Type:
Expected Relay Life:
Operating Temperature:
Humidity Range:
Operate Time:
Relay Status:
Dimensions:
Wire Length:
Approvals:
Housing Rating:
Gold Flash:
Override Switch:
+
Current
Sensor
Circuitry
Blu - N/C
Yel - Comm
Org - N/O
Wire Being
Monitored
AXKT
CT
Gry
Gry
FUNCTIONAL DEVICES CERTIFIED FOR USE WITH ECMS
One (1) SPDT Continuous Duty Coil
10 million cycles minimum mechanical
-30 to 140° F
5 to 95% (noncondensing)
20ms
Red LED On = Activated
4.00˝ x 4.00˝ x 1.80˝ with .50˝ NPT Nipple
16˝, 600V R
UL Listed, UL916, UL864, C-UL California
State Fire Marshal
UL Accepted for Use in Plenum, NEMA 1
Yes
No
ated
RIBXLCJA, RIBXLCJF
Sensor Feedback
Current Sensor
Status
10-30 Vac/dc
Comm
+
Current
Sensor
Circuitry
Blu - N/C
Yel - Comm
Org - N/O
Coil Current:
33 mA @ 10 Vac
35 mA @ 12 Vac
46 mA @ 24 Vac
55 mA @ 30 Vac
13 mA @ 10 Vdc
15 mA @ 12 Vdc
18 mA @ 24 Vdc
20 mA @ 30 Vdc
Coil Voltage Input:
10-30 Vac/dc ; 50-60 Hz
Drop Out = 2.1 Vac / 2.8 Vdc
Pull In = 9 Vac / 10 Vdc
Wire Being
Monitored
AXGT
CT
Gry
+ Sensor Contact:
• When current sensor status is o (open), leakage
<30 uA @ 30Vac/dc
When current sensor status is on (closed), voltage drop
•
< .3 Vac/dc @ .1 Amp
< 1.6 Vac/dc @ .4 Amp
^ Sensor Feedback Output:
• Voltage output is proportional to current sensor range.
• Min. Input Impedance = 30K ohms
• Accuracy +/– 3% full scale
• Vripple < 10m Vac
Notes:
• Models AXKT and AXGT CT remotes do not have contact
closure circuitry and only work in conjunction with
RIBXLCA
RIBXLCR and RIBXLCJ models, respectively.
RIBXLC SERIES SELECTION GUIDE
Model# Sensing Range Type * Threshold Sensor Output Remote Style Resistive Contact Ratings
ECMS
RIBXLCF .50-10 Amps
ECMS
RIBXLCA .50-10 Amps
RIBXLCV 0-10 Amps
RIBXLCRF 1.25-150 Amps
RIBXLCRA 1.25-150 Amps
RIBXLCJF 3-150 Amps
RIBXLCJA 3-150 Amps
ECMS
ECMS
ECMS
ECMS
RIBXLCEA .125-5 Amps
RIBXLCEV 0-5 Amps
Internal
w/ contact status
Internal
w/ contact status
Internal
w/ voltage output
External
w/ contact status
External
w/ contact status
External
w/ contact status
External
w/ contact status
Internal
w/ contact status
Internal
w/ voltage output
Fixed, .50 Amp
Adjustable
Analog
Fixed, 1.25 Amp
Adjustable
Fixed, 3 Amp
Adjustable
Adjustable
Analog
* = Internal current sensor monitors current through common contact of relay.
= FDI Certied for use with electronically commutated motors
ECMS
Solid State Contact
30 Vac/dc, 0.4 Amp
Solid State Contact
30 Vac/dc, 0.4 Amp
0-5 Vdc
0-10 Vdc
Solid State Contact
30 Vac/dc, 0.4 Amp
Solid State Contact
30 Vac/dc, 0.4 Amp
Solid State Contact
30 Vac/dc, 0.4 Amp
Solid State Contact
30 Vac/dc, 0.4 Amp
Solid State Contact
30 Vac/dc, 0.4 Amp
0-5 Vdc
0-10 Vdc
Model AXKT: (Solid
Core Remote CT)
Model AXKT: (Solid
Core Remote CT)
Model AXGT: (Split
Core Remote CT)
Model AXGT: (Split
Core Remote CT)
10 Amp
10 Amp
10 Amp
10 Amp
10 Amp
10 Amp
10 Amp
10 Amp Resistive @ 120-277 Vac
10 Amp Resistive @ 28 Vdc
480 VA Pilot Duty @ 240-277 Vac
480 VA Ballast @ 277 Vac
Not rated for Electronic Ballast
600 Watt Tungsten @ 120 Vac (N/O)
240 Watt Tungsten @ 120 Vac (N/C)
1/3 HP @ 120-240 Vac (N/O)
1/6 HP @ 120-240 Vac (N/C)
1/4 HP @ 277 Vac (N/O)
1/8 HP @ 277 Vac (N/C)
5 Amp Resistive @ 277 Vac
345 VA Pilot Duty @ 120/240 Vac (N/O)
5 Amp
268 VA Pilot Duty @ 277 Vac (N/O)
211 VA Pilot Duty @ 120/240 Vac (N/C)
175 VA Pilot Duty @ 277 Vac (N/C)
1/3 HP @ 120-240 Vac (N/O)
1/6 HP @ 120-240 Vac (N/C)
5 Amp
1/4 HP @ 277 Vac (N/O)
1/8 HP @ 277 Vac (N/C)
071717