AC TRANSDUCERS
RIBXK420 Series
Enclosed Self-Powered Solid Core 20, 50, and 100 Amp Current Transducers with Loop
Powered 4-20 mA Output (Pre-Wired)
1.460”
.500”
Diameter
1.863”
Black (–)
1.008”
Red (+)
Wire Clamp
Removable Mounting Tab
SPECIFICATIONS
Operating Temperature:
Humidity Range:
Sensor Type:
Sensor Range:
Accuracy:
Linearity:
Max Output Current:
Max Sense Voltage:
Approvals:
Mounting/Installation:
-30 to 140° F
5 to 95% (noncondensing)
Wires:
Red (positive) & Black (negative), 16˝, 18 AWG, 600V Rated
Internal, with 4-20 mA Transmitter Output
0-20 Amps, 0-50 Amps, or 0-100 Amps
(See Selection Guide Below)
96.4% FS
99% FS (25%-100% Span)
30 mA
600 Vac
UL Listed, UL916, UL864, C-UL, California State Fire Marshal
Removable mounting tab provided. The wire clamp locks against the
wire being monitored, securing the unit in place.
RIBXKTV SERIES SELECTION GUIDE
Model# Sensing Range Sensor Output
RIBXK420-20 0-20 Amps Loop Powered 4-20 mA Transmitter (Pre-Wired)
RIBXK420-50 0-50 Amps Loop Powered 4-20 mA Transmitter (Pre-Wired)
RIBXK420-100 0-100 Amps Loop Powered 4-20 mA Transmitter (Pre-Wired)
2.050”
Made in USA
Meets
“Buy American”
of ARRA 2009
Output Load
Resistance
-
+
Supply Voltage
+
-
Red +
Black
RIBXK420
-
OUTPUT LOAD RESISTANCE SUPPLY VOLTAGE
Maximum Minimum Maximum
700 ohms 26 Vdc 35 Vdc
600 ohms 24 Vdc 35 Vdc
500 ohms 21 Vdc 35 Vdc
400 ohms 19 Vdc 30 Vdc
300 ohms 17 Vdc 30 Vdc
250 ohms 16 Vdc 28 Vdc
200 ohms 14 Vdc 28 Vdc
100 ohms 12 Vdc 28 Vdc
50 ohms 11 Vdc 28 Vdc
102615