Johnson Controls RIBXG Series Data Sheet

CURRENT
SENSORS
AC CURRENT SWITCHES
RIBXG Series
Enclosed Self-Powered Split Core AC Sensors
2.000”
.52” x .52” – Opening for
Wire Being Monitored
2.520”
1.100”
1.750”
Removable Mounting Tab
Threshold Adjust
2.000”
Sensor Contact
LED 2 LED 1 (if present)
RIBXGA
Wire Being Monitored
Wht/Yel
Wht/Yel
RIBXGTF
Wire Being
Monitored
Made in USA
Meets
Buy American
of ARRA 2009
SPECIFICATIONS
Operating Temperature:
Humidity Range:
Max Sense Voltage:
Approvals:
Mounting/Installation:
-30 to 140° F 5 to 95% (noncondensing) 600 Vac UL Listed, UL916, UL864, C-UL, California State Fire Marshal Removable mounting tab provided. The wire clamp locks against the wire being
FUNCTIONAL DEVICES CERTIFIED FOR USE WITH ECMS
Sensor Contact:
Solid State Contact
When sensor contact is o (open), leakage
<30 uA @ 30Vac/dc
When sensor contact is on (closed), voltage drop
< .3 Vac/dc @ .1 Amp < 1.6 Vac/dc @ .4 Amp
monitored, securing the unit in place.
Sensor Contact Status:
Current below threshold: Open Current above threshold: Closed
SELFCALIBRATING AC SWITCHES (Models with -SCAL Sux)
Sensor Contact
LED 1
DIP Switch
The SCAL unit begins the 30 second self-calibration process the rst time current is applied in the operating range. The threshold is then set. Subsequent calibrations may be performed by moving SW1 to the position opposite of its current position with or without current applied (hands can be safely away from live voltage). Once current begins owing, or if it already is, the calibration process will begin. At the end of the 30 seconds, amperage will be read and set as the threshold. SW2 in the ON position provides a 15% (+/-3%) dierential. In the OFF position, it provides a 25% (+/-3%) dierential. SW2 can be selected at anytime and does not aect the threshold setting. Current in-range closes the sensor contact. Current above or below range opens the sensor contact.
Example: With a current of 10 amps set as the threshold and a 15% dierential, sensor contact will be closed between 8.5 amps and 11.5 amps and open outside of this range. A small amount of hysteresis is provided to prevent dithering near the dierential limits.
-SCAL LED TABLE
LED O No Current
Two Winks Current Below Range
Three Winks Current In Range
Four Winks Current Above Range
Continuous Winks Calibration in Progress
RIBXGA-SCAL
RIBXGTA-SCAL
Made in USA
Meets
Buy American
of ARRA 2009
RIBXG SERIES SELECTION GUIDE
Model#
RIBXGF .35-150 Amp Split Core Fixed, .35 Amp Solid State Switch SPST 30 Vac/dc .4 Amps Max Wht/Yel 16˝ 18 AWG Wire Leads
RIBXGFL* .75-150 Amp Split Core Fixed, .75 Amp Solid State Switch SPST 30 Vac/dc .4 Amps Max Wht/Yel 16˝ 18 AWG Wire Leads O ver Trip Point
RIBXGTF .35-150 Amp Split Core Fixed, .35 Amp Solid State Switch SPST 30 Vac/dc .4 Amps Max Terminal Strip, Accepts #14-22 AWG Wire
RIBXGTFL* .75-150 Amp Split Core Fixed, .75 Amp Solid State Switch SPST 30 Vac/dc .4 Amps Max Terminal Strip, Accepts #14-22 AWG Wire Over Trip Point
RIBXGA .75-150 Amp Split Core Adjustable Solid State Switch SPST 30 Vac/dc .4 Amps Max Wht/Yel 16˝ 18 AWG Wire Leads Over Trip Point Under Trip Point
RIBXGTA .75-150 Amp Split Core Adjustable Solid State Switch SPST 30 Vac/dc .4 Amps Max Terminal Strip, Accepts #14-22 AWG Wire Over Trip Point Under Trip Point
RIBXGA-SCAL 3-150 Amp Split Core Self-Cal. Solid State Switch SPST 30 Vac/dc .4 Amps Max Wht/Yel 16˝ 18 AWG Wire Leads See -SCAL Table
RIBXGTA-SCAL 3-150 Amp Split Core Self-Cal. Solid State Switch SPST 30 Vac/dc .4 Amps Max Terminal Strip, Accepts #14-22 AWG Wire See -SCAL Table
* = Not approved by California State Fire Marshal
Sensing
Range
Type Threshold
Sensor Contact
Type
Switching
Voltage
Range
Maximum Switching
Current
Sensor Contact
Termination
LED 1 LED 2