Johnson Controls RIBTU2C, RIBTH2C Data Sheet

Johnson Controls RIBTU2C, RIBTH2C Data Sheet

10 AMP PILOT CONTROL RELAYS

RIBTU2C

Enclosed Relays Hi/Low Separation 10 Amp 2 SPDT with 10-30 Vac/dc/120 Vac Coil

Comm

Comm

10-30 Vac/dc

10-30 Vac/dc

120 Vac

120 Vac

Blu - N/C

Brn - N/O

Yel - Comm

Prp - Comm

Org - N/O

Gry - N/C

RIBTH2C

 

 

Enclosed Relays Hi/Low Separation 10 Amp

 

2 SPDT with 10-30 Vac/dc/208-277 Vac Coil

<![if ! IE]>

<![endif]>RELAYS

Comm

Comm

10-30 Vac/dc

10-30 Vac/dc

 

208-277 Vac

208-277 Vac

 

 

 

Made in USA

 

 

Meets

 

 

Buy American

 

 

of ARRA 2009

Blu - N/C

Brn - N/O

 

Yel - Comm

Prp - Comm

 

Org - N/O

Gry - N/C

 

SPECIFICATIONS

# Relays & Contact Type:

Two (2) SPDT Continuous Duty Coil

Contact Ratings:

Coil Current:

13 mA @ 10 Vdc

Expected Relay Life:

10 million cycles minimum mechanical

10 Amp Resistive @ 277 Vac

33 mA @ 10 Vac

Operating Temperature:

-30 to 140° F

10 Amp Resistive @ 28 Vdc

35 mA @ 12 Vac

15 mA @ 12 Vdc

Humidity Range:

5 to 95% (noncondensing)

480 VA Pilot Duty @ 240-277 Vac

46 mA @ 24 Vac

18 mA @ 24 Vdc

Operate Time: 20ms

480 VA Ballast @ 277 Vac

55 mA @ 30 Vac

20 mA @ 30 Vdc

Relay Status: LED On = Activated

Not rated for Electronic Ballast

28 mA @ 120 Vac (RIBTU2C)

Dimensions: 4.00˝ x 4.00˝ x 1.80˝ with .50˝ NPT nipple

600 Watt Tungsten @ 120 Vac (N/O)

39 mA @ 208-277 Vac (RIBTH2C)

Wires: 16˝, 600V Rated

240 Watt Tungsten @ 120 Vac (N/C)

Coil Voltage Input:

 

Approvals: UL Listed, UL916, UL864, C-UL California

1/3 HP @ 120-240 Vac (N/O)

 

10-30 Vac/dc ; 120 Vac ; 50-60 Hz (RIBTU2C)

 

State Fire Marshal

1/6 HP @ 120-240 Vac (N/C)

 

10-30 Vac/dc ; 208-277 Vac ; 50-60 Hz (RIBTH2C)

Housing Rating: UL Accepted for Use in Plenum, NEMA 1

1/4 HP @ 277 Vac (N/O)

Drop Out = 2.1 Vac / 2.8 Vdc

Gold Flash: Yes

1/8 HP @ 277 Vac (N/C)

Pull In = 9 Vac / 10 Vdc

Override Switch: No

 

 

 

 

071717

Loading...