Johnson Controls RIBT24P Data Sheet

RELAYS
20 AMP POWER CONTROL RELAY
RIBT24P
Enclosed Relay Hi/Low Separation 20 Amp DPDT with 24 Vac/dc Coil
Blu - N/C
Yel - Comm
24 Vac/dc Comm
SPECIFICATIONS
# Relays & Contact Type:
Expected Relay Life:
Operating Temperature:
Humidity Range:
Operate Time:
Relay Status:
Dimensions:
Wires:
Approvals:
Housing Rating:
Gold Flash:
Override Switch:
Org - N/O
Gry - N/C
Brn - N/O
One (1) DPDT Continuous Duty Coil 10 million cycles minimum mechanical
-30 to 140° F 5 to 95% (noncondensing) 18ms LED On = Activated
4.00˝ x 4.00˝ x 1.80˝ with .50˝ NPT Nipple 16˝, 600V R
ated UL Listed, UL916, UL864, C-UL California State Fire Marshal UL Accepted for Use in Plenum, NEMA 1 Yes No
Contact Ratings:
20 Amp Resistive @ 300 Vac 20 Amp Resistive @ 28 Vdc 20 Amp Ballast @ 277-480 Vac
Not rated for Electronic Ballast
15 Amp Resistive @ 600 Vac 770 VA Pilot Duty @ 120 Vac 1158 VA Pilot Duty @ 240 Vac 1109 VA Pilot Duty @ 277 Vac 1640 VA Pilot Duty @ 480 Vac Heavy Pilot Duty @ 600 Vac 3 HP @ 480-600 Vac 2 HP @ 240-277 Vac 1 HP @ 120 Vac
Coil Current:
110 mA @ 20 Vac 138 mA @ 24 Vac 55 mA @ 20 Vdc 55 mA @ 24 Vdc 77 mA @ 30 Vdc
Made in USA
Meets
Buy American
of ARRA 2009
Coil Voltage Input:
24 Vac/dc ; 50-60 Hz Drop Out = 3 Vac / 3.8 Vdc Pull In = 20 Vac / 20 Vdc
071717