Johnson Controls RIBT2401B, RIBT2402B Data Sheet

RELAYS
20 AMP POWER CONTROL RELAYS
RIBT2401B
Enclosed Relay Hi/Low Separation 20 Amp SPDT with 24 Vac/dc/120 Vac Coil
Blu
120 Vac
24 Vac/dc
Comm
SPECIFICATIONS
# Relays & Contact Type:
Expected Relay Life:
Operating Temperature:
Humidity Range:
Operate Time:
Relay Status:
Dimensions:
Wires:
Approvals:
Housing Rating:
Gold Flash:
Override Switch:
N/C
Comm
Org
N/O
One (1) SPDT Continuous Duty Coil 10 million cycles minimum mechanical
-30 to 140° F 5 to 95% (noncondensing) 18ms LED On = Activated
4.00˝ x 4.00˝ x 1.80˝ with .50˝ NPT Nipple 16˝, 600V Rated UL Listed, UL916, UL864, C-UL California State Fire Marshal UL Accepted for Use in Plenum, NEMA 1 No No
RIBT2402B
Enclosed Relay Hi/Low Separation 20 Amp SPDT with 24 Vac/dc/208-277 Vac Coil
208-277 Vac
24 Vac/dc
Comm
Contact Ratings:
20 Amp Resistive @ 277 Vac 5 Amp Resistive @ 480 Vac 20 Amp Ballast @ 277 Vac 16 Amp Electronic Ballast @ 277 Vac (N/O) 10 Amp Tungsten @ 120 Vac (N/O) 770 VA Pilot Duty @ 120 Vac 1,110 VA Pilot Duty @ 277 Vac 2 HP @ 277 Vac 1 HP @ 120 Vac
Blu N/C
Comm
Org
N/O
Made in USA
Meets
Buy American
of ARRA 2009
Coil Current:
50 mA @ 18 Vac 83 mA @ 24 Vac 47 mA @ 120 Vac (RIBT2401B)
33 mA @ 22 Vdc 35 mA @ 24 Vdc 47 mA @ 30 Vdc
69 mA @ 208-277 Vac (RIBT2402B)
Coil Voltage Input:
24 Vac/dc ; 120 Vac ; 50-60 Hz (RIBT2401B) 24 Vac/dc ; 208-277 Vac ; 50-60 Hz (RIBT2402B) Drop Out = 2.1 Vac / 3.8 Vdc Pull In = 18 Vac / 22 Vdc
071717