15 AMP TRACK MOUNT CONTROL RELAYS
RIBM24C |
RIBM24S |
|
|
4.00˝ Track Mount Relay 15 Amp SPDT with |
4.00˝ Track Mount Relay 15 Amp SPST + |
Made in USA |
|
24 Vac/dc Coil |
Override with 24 Vac/dc Coil |
||
Meets |
|||
|
|
“Buy American” |
|
|
|
of ARRA 2009 |
|
|
Comm |
|
|
|
|
|
|
AUTO |
Comm |
|
Comm |
N/C |
|
OPEN |
|
|
|
|
|
|||
|
|
|
CLOSED |
|
|
|
Comm |
|
|
N/O |
|
|
|
|
|
or |
Cut |
|
|
24 Vac/dc |
|
N/C |
|
|
|
|
|
for |
|
|
|
|
|
|
|
24 Vac/dc |
N/O |
|
|
|
N/O |
Selectable
Jumpers (must cut one only)
SPECIFICATIONS
Cut for N/C
# Relays & Contact Type: One (1) SPDT Continuous Duty Coil (RIBM24C) |
Contact Ratings: |
Coil Current: |
Coil Voltage Input: |
|
Expected Relay Life: |
One (1) SPST Continuous Duty Coil (RIBM24S) |
15 Amp General Use @ 125 Vac |
26 mA @ 20 Vac |
24 Vac/dc ; 50-60 Hz |
10 million cycles minimum mechanical |
10 Amp General Use @ 277 Vac |
31 mA @ 24 Vac |
Drop Out = 3 Vac / 3.8 Vdc |
|
Operating Temperature: |
-30 to 140° F |
10 Amp Resistive @ 30 Vdc (N/O) |
48 mA @ 35 Vac |
Pull In = 20 Vac / 20 Vdc |
Humidity Range: |
5 to 95% (noncondensing) |
7 Amp Resistive @ 30 Vdc (N/C) |
14 mA @ 20 Vdc |
|
Operate Time: 6ms |
1/2 HP @ 125 Vac |
18 mA @ 24 Vdc |
|
|
Relay Status: LED On = Activated |
1 HP @ 250 Vac |
28 mA @ 35 Vdc |
|
|
Dimensions: 1.250˝ x 4.000˝ x 1.750˝ |
1/4 HP @ 277 Vac |
|
|
|
Track Mount: 4.000˝, See MT4 Series on page 152 |
C300 Pilot Duty |
Notes: |
|
|
|
MT4 Mounting Track Sold Separately |
|
• Must cut appropriate jumper to select Normally Open |
Approvals: UL Listed, UL916, UL864, C-UL |
or Normally Closed (RIBM24S) |
California State Fire Marshal |
|
Gold Flash: No |
|
Override Switch: No (RIBM24C) |
|
Yes (RIBM24S) |
|
<![endif]>RELAYS