Johnson Controls RIBM2401SBC, RIBM2402SBC Data Sheet

RELAYS
20 AMP TRACK MOUNT CONTROL RELAYS
RIBM2401SBC
4.00˝ Track Mount Relay 20 Amp SPDT + Override with 24 Vac/dc/120 Vac Coil
Comm
24 Vac/dc
120 Vac
SPECIFICATIONS
# Relays & Contact Type:
Expected Relay Life:
Operating Temperature:
Humidity Range:
Operate Time:
Relay Status:
Dimensions:
Track Mount:
Approvals:
Gold Flash:
Override Switch:
N/C
OPEN
AUTO
MANUAL
N/O
Comm
One (1) SPDT Continuous Duty Coil 10 million cycles minimum mechanical
-30 to 140° F 5 to 95% (noncondensing) 18ms LED On = Activated
2.350˝ x 4.000˝ x 1.750˝
4.000˝, See MT4 Series on page 152
MT4 Mounting Track Sold Separately
UL Listed, UL916, UL864, C-UL California State Fire Marshal No Yes (2)
N/O
N/C
RIBM2402SBC
4.00˝ Track Mount Relay 20 Amp SPDT + Override with 24 Vac/dc/208-277 Vac Coil
Comm
24 Vac/dc
N/C
OPEN
AUTO
MANUAL
N/O
Comm
Contact Ratings:
20 Amp Resistive @ 277 Vac 20 Amp Ballast @ 277 Vac (N/O) 10 Amp Ballast @ 277 Vac (N/C)
Not rated for Electronic Ballast
10 Amp Tungsten @ 120 Vac (N/O) 1110 VA Pilot Duty @ 277 Vac 770 VA Pilot Duty @ 120 Vac 2 HP @ 277 Vac 1 HP @ 120 Vac
208-277 Vac
N/O
N/C
Coil Current:
50 mA @ 18 Vac 83 mA @ 24 Vac 47 mA @ 120 Vac (RIBM2401SBC)
33 mA @ 22 Vdc 35 mA @ 24 Vdc 47 mA @ 30 Vdc
69 mA @ 208-277 Vac (RIBM2402SBC)
Coil Voltage Input:
24 Vac/dc ; 120 Vac ; 50-60 Hz (RIBM2401SBC) 24 Vac/dc ; 208-277 Vac ; 50-60 Hz (RIBM2402SBC) Drop Out = 2.1 Vac / 3.8 Vdc Pull In = 18 Vac / 22 Vdc
Made in USA
Meets
Buy American
of ARRA 2009
071417