10 AMP PILOT CONTROL RELAYS
RIBL3C
Enclosed Relays 10 Amp 3 SPST-N/O with
10-30 Vac/dc Coil
RELAY 1
RELAY 2
RELAY 3
Blk
Blk
Blu
Blu
Yel
Yel
Wht/Blk
RELAY 1
Wht/Blu
RELAY 2
Wht/Yel
RELAY 3
Wht/Red
COMM
• All relay coils use the same common
• All relay coils 10-30 Vac/dc
SPECIFICATIONS
# Relays & Contact Type:
Expected Relay Life:
Operating Temperature:
Humidity Range:
Operate Time:
Relay Status:
Dimensions:
Wires:
Approvals:
Housing Rating:
Gold Flash:
Override Switch:
Three (3) SPST Continuous Duty Coil (RIBL3C)
Three (3) SPST + One (1) SPDT Continuous
Duty Coil (RIBL4C)
10 million cycles minimum mechanical
-30 to 140° F
5 to 95% (noncondensing)
20ms
LED On = Activated
4.00˝ x 4.00˝ x 1.80˝ with .50˝ NPT nipple
16˝, 600V Rated
UL Listed, UL916, UL864, C-UL
California State Fire Marshal
UL Accepted for Use in Plenum, NEMA 1
es
Y
No
RIBL4C
Enclosed Relays 10 Amp 3 SPST-N/O +
1 SPDT with 10-30 Vac/dc Coil
Wht/Blk
RELAY 1
Wht/Blu
RELAY 2
Wht/Yel
RELAY 3
Wht/Brn
RELAY 4
Wht/Red
COMM
• All relay coils use the same common
• All relay coils 10-30 Vac/dc
Contact Ratings:
10 Amp Resistive @ 277 Vac
10 Amp Resistive @ 28 Vdc
480 VA Pilot Duty @ 240-277 Vac
480 VA Ballast @ 277 Vac
Not rated for Electronic Ballast
600 Watt Tungsten @ 120 Vac (N/O)
240 Watt Tungsten @ 120 Vac (N/C)
1/3 HP @ 120-240 Vac (N/O)
1/6 HP @ 120-240 Vac (N/C)
1/4 HP @ 277 Vac (N/O)
1/8 HP @ 277 Vac (N/C)
RELAY 1
RELAY 2
RELAY 3
RELAY 4
Blk
Blk
Blu
Blu
Yel
Yel
Gry
Prp
Brn
Made in USA
Meets
“Buy American”
of ARRA 2009
Coil Current:
33 mA @ 10 Vac
35 mA @ 12 Vac
46 mA @ 24 Vac
55 mA @ 30 Vac
13 mA @ 10 Vdc
15 mA @ 12 Vdc
18 mA @ 24 Vdc
20 mA @ 30 Vdc
Coil Voltage Input:
10-30 Vac/dc ; 50-60 Hz
Drop Out = 2.1 Vac / 2.8 Vdc
Pull In = 9 Vac / 10 Vdc
Notes:
• Order Normally Closed by adding “-NC”
to end of model number
071417