Johnson Controls RIBL3C, RIBL4C Data Sheet

0 (0)
Johnson Controls RIBL3C, RIBL4C Data Sheet

10 AMP PILOT CONTROL RELAYS

RIBL3C

RIBL4C

Enclosed Relays 10 Amp 3 SPST-N/O with

Enclosed Relays 10 Amp 3 SPST-N/O +

10-30 Vac/dc Coil

1 SPDT with 10-30 Vac/dc Coil

Wht/Blk

Blk

 

RELAY 1

RELAY 1

 

 

Blk

Wht/Blu

Blu

 

RELAY 2

RELAY 2

 

 

Blu

Wht/Yel

Yel

 

RELAY 3

RELAY 3

 

 

Yel

Wht/Red

 

COMM

 

All relay coils use the same common

All relay coils 10-30Vac/dc

Wht/Blk

 

Blk

 

 

RELAY 1

RELAY 1

 

 

Blk

Wht/Blu

 

Blu

RELAY 2

RELAY 2

 

 

Blu

Wht/Yel

 

Yel

RELAY 3

RELAY 3

 

 

Yel

Wht/Brn

 

Gry

RELAY 4

 

 

 

RELAY 4

Prp

Wht/Red

 

 

COMM

 

Brn

 

 

All relay coils use the same common

All relay coils 10-30Vac/dc

Made in USA

Meets

Buy American

of ARRA 2009

SPECIFICATIONS

# Relays & Contact Type: Three (3) SPST Continuous Duty Coil (RIBL3C)

Contact Ratings:

 

Three (3) SPST + One (1) SPDT Continuous

10 Amp Resistive @ 277 Vac

Expected Relay Life:

Duty Coil (RIBL4C)

10 Amp Resistive @ 28 Vdc

10 million cycles minimum mechanical

480 VA Pilot Duty @ 240-277 Vac

Operating Temperature:

-30 to 140° F

480 VA Ballast @ 277 Vac

Humidity Range:

5 to 95% (noncondensing)

Not rated for Electronic Ballast

Operate Time: 20ms

600 Watt Tungsten @ 120 Vac (N/O)

Relay Status: LED On = Activated

240 Watt Tungsten @ 120 Vac (N/C)

Dimensions: 4.00˝ x 4.00˝ x 1.80˝ with .50˝ NPT nipple

1/3 HP @ 120-240 Vac (N/O)

Wires: 16˝, 600V Rated

1/6 HP @ 120-240 Vac (N/C)

Approvals: UL Listed, UL916, UL864, C-UL

1/4 HP @ 277 Vac (N/O)

 

California State Fire Marshal

1/8 HP @ 277 Vac (N/C)

Housing Rating: UL Accepted for Use in Plenum, NEMA 1

 

Gold Flash: Yes

Override Switch: No

Coil Current:

13 mA @ 10 Vdc

33 mA @ 10 Vac

35 mA @ 12 Vac

15 mA @ 12 Vdc

46 mA @ 24 Vac

18 mA @ 24 Vdc

55 mA @ 30 Vac

20 mA @ 30 Vdc

Coil Voltage Input:

10-30 Vac/dc ; 50-60 Hz Drop Out = 2.1 Vac / 2.8 Vdc Pull In = 9 Vac / 10 Vdc

Notes:

Order Normally Closed by adding “-NC” to end of model number

<![if ! IE]>

<![endif]>RELAYS

071417

Loading...