Johnson Controls RIBD2421C Data Sheet

RELAYS
10 AMP PILOT CONTROL RELAY
RIBD2421C
Enclosed Time Delay Relay 10 Amp SPDT with 24 Vac/dc/120-277 Vac Coil
Wht/Brn
120-277 Vac
Wht/Blu
24 Vac/dc
Wht/Yel
SPECIFICATIONS
# Relays & Contact Type:
Expected Relay Life:
Operating Temperature:
Humidity Range:
Operate Time:
Relay Status:
Time Delay Status:
Timing Mode:
Timing Range:
Timing Adjustment:
Timing Tolerance:
Timing Repeatability:
Temperature Timing Variance:
Voltage Timing Variance:
Recycle Time:
Dimensions:
Wires:
Approvals:
Housing Rating:
Gold Flash:
Override Switch:
Blu N/C
Yel
Org
N/O
One (1) SPDT Continuous Duty Coil 10 million cycles minimum mechanical
-30 to 140° F 5 to 95% (noncondensing) 6ms after time delay RED LED On = Activated PINK LED FLASHING = Timing Delay On Make (N/O) 6 seconds - 20 minutes 4 position DIP switch for range selection and single turn potentiometer for timing adjustment within range Switches 1& 2 = +10% Switches 3 & 4 = +5% +1% +1% +1% 750ms Maximum
4.00˝ x 4.00˝ x 1.80˝ with .50˝ NPT nipple 16˝, 600V Rated UL Listed, UL916, UL864, C-UL California State Fire Marshal +UL Accepted for Use in Plenum, NEMA 1 No No
Contact Ratings:
10 Amp General Use @ 277 Vac 10 Amp Resistive @ 30 Vdc (N/O) 7 Amp Resistive @ 30 Vdc (N/C)
Input Current:
66 mA @ 24 Vac 38 mA @ 24 Vdc 40 mA @ 120-277 Vac
Coil Voltage Input:
24 Vac/dc ; 120-277 Vac ; 50-60 Hz Drop Out = 3 Vac / 3.8 Vdc
Pull In = 20 Vac / 20 Vdc 1/2 HP @ 125 Vac 1 HP @ 250 Vac 1/4 HP @ 277 Vac C300 Pilot Duty
Range Selection
1 2 3 4
Timing Adjustment
Only Close
C
D
B
A
E
1 Switch
TIMING TABLE
Switch
Ranges
Close
Dip Switch
A B C D E
6s-20s 1 6s 9s 13s 16s 20s
22s-1min15s 2 22s 36s 50s 1min4s 1min15s
1min30s-5min 3 1min30s 2min10s 3min20s 4min16s 5min
6min-20min 4 6min 9min 13min20s 17min20s 20min
Potentiometer Setting
Made in USA
Meets
Buy American
of ARRA 2009
Depressed for closed
Depressed for open
Coil
N/O
N/C
Timing Diagram
Time Delay Time Delay Time Delay
Time Delay Time Delay Time Delay
Load 1
(Thermostat
Controlled Heater,
for example)
Load 2 stays on selected amount of time after Load 1 goes o.
Time Delay Application
In this example, voltage can be
any voltage from 120-277 Vac.
Blu
Yel
®
RIB
Select RIB® with coil input
appropriate to sense Load 1.
Wht/Yel
Neutral
Wht/Brn
RIBD2421C
Blu
Yel
Load 2
(Circulating Fan,
for example)
071417