20 AMP POWER CONTROL RELAYS
RIB2401SBC
Enclosed Relay 20 Amp SPDT + Override with
24 Vac/dc/120 Vac Coil
Wht/Blk
120 Vac
ated
Yel
Comm
Blu
N/C
Org
N/O
Wht/Blu
24 Vac/dc
Wht/Yel
Comm
AUTO
N/C
CLOSED
SPECIFICATIONS
# Relays & Contact Type:
Expected Relay Life:
Operating Temperature:
Humidity Range:
Operate Time:
Relay Status:
Dimensions:
Wires:
Approvals:
Housing Rating:
Gold Flash:
Override Switch:
MANUAL
OPEN
N/O
CLOSED
One (1) SPDT Continuous Duty Coil
10 million cycles minimum mechanical
-30 to 140° F
5 to 95% (noncondensing)
18ms
LED On = Activated
2.30˝ x 3.20˝ x 1.80˝ with .50˝ NPT Nipple
16˝, 600V R
UL Listed, UL916, UL864, C-UL California
State Fire Marshal
UL Accepted for Use in Plenum, NEMA 1
No
Yes (2)
RIB2402SBC
Enclosed Relay 20 Amp SPDT + Override with
24 Vac/dc/208-277 Vac Coil
Wht/Brn
208-277 Vac
Wht/Blu
24 Vac/dc
Wht/Yel
Comm
MANUAL
AUTO
OPEN
N/C
N/O
CLOSED
CLOSED
Contact Ratings:
20 Amp Resistive @ 277 Vac
20 Amp Ballast @ 277 Vac (N/O)
10 Amp Ballast @ 277 Vac (N/C)
Not rated for Electronic Ballast
10 Amp Tungsten @ 120 Vac (N/O)
770 VA Pilot Duty @ 120 Vac
1,110 VA Pilot Duty @ 277 Vac
2 HP @ 277 Vac
1 HP @ 120 Vac
Yel
Comm
Blu
N/C
Org
N/O
“Buy American”
Coil Current:
50 mA @ 18 Vac
83 mA @ 24 Vac
47 mA @ 120 Vac (RIB2401SBC)
33 mA @ 22 Vdc
35 mA @ 24 Vdc
47 mA @ 30 Vdc
69 mA @ 208-277 Vac (RIB2402SBC)
Coil Voltage Input:
24 Vac/dc ; 120 Vac ; 50-60 Hz (RIB2401SBC)
24 Vac/dc ; 208-277 Vac ; 50-60 Hz (RIB2402SBC)
Drop Out = 2.1 Vac / 3.8 Vdc
Pull In = 18 Vac / 22 Vdc
Made in USA
Meets
of ARRA 2009
071417