Johnson Controls RIB2402D Data Sheet

RELAYS
10 AMP PILOT CONTROL RELAYS
RIB2401D
Enclosed Relay 10 Amp DPDT with 24 Vac/dc/120 Vac Coil
Wht/Blk 120 Vac
Wht/Blu
24 Vac/dc
Wht/Yel
Comm
SPECIFICATIONS
# Relays & Contact Type:
Expected Relay Life:
Operating Temperature:
Humidity Range:
Operate Time:
Dimensions:
Approvals:
Housing Rating:
Gold Flash:
Override Switch:
One (1) DPDT Continuous Duty Coil 10 million cycles minimum mechanical
-30 to 140° F 5 to 95% (noncondensing) 8ms LED On = Activated
1.70˝ x 2.80˝ x 1.50˝ with .50˝ NPT nipple 16˝, 600V Rated
Wires:
UL Listed, UL916, UL864, C-UL California State Fire Marshal UL Accepted for Use in Plenum, NEMA 1 No No
Blu N/C
Yel
Comm
Org
N/O
Gry N/C
Prp
Comm
Brn N/O
RIB2402D
Enclosed Relay 10 Amp DPDT with 24 Vac/dc/208-277 Vac Coil
Blu
Wht/Brn
208-277 Vac
Wht/Blu
24 Vac/dc
Wht/Yel
Comm
Contact Ratings:
10 Amp Resistive @ 30 Vdc 10 Amp General Use @ 277 Vac 1/2 HP @ 120/240 Vac (N/O) 1/3 HP @ 120/240 Vac (N/C) B300 Pilot Duty 120 Vac 30A Make 3A Break (360 VA) 240 Vac 15 A Make 1.5A Break (360 VA) 208 Vac 17.3A Make 1.73A Break (360 VA) 277 Vac 13A Make 1.3A Break (360 VA) 24 Vac 30A Make 5A Break (120VA) 5A Max
N/C
Yel
Comm
Org
N/O
Gry N/C
Prp
Comm
Brn N/O
Coil Current:
24 mA @ 18 Vac 32 mA @ 24 Vac 40 mA @ 30 Vac
20 mA @ 20 Vdc 24 mA @ 24 Vdc
36 mA @ 30 Vdc 31 mA @ 120 Vac (RIB2401D) 36 mA @ 208-277 Vac (RIB2402D)
Coil Voltage Input:
24 Vac/dc ; 120 Vac ; 50-60 Hz (RIB2401D) 24 Vac/dc ; 208-277 Vac ; 50-60 Hz (RIB2402D) Drop Out = 3 Vac / 3.8 Vdc Pull In = 18 Vac / 20 Vdc
Made in USA
Meets
Buy American
of ARRA 2009
RIB2401D-RD RIB2402D-RD
Red housing
RIB2401D-N4 RIB2402D-N4
NEMA 4X housing,
UL508 only
071417