10 AMP PILOT CONTROL RELAYS
RIB2401C
Enclosed Relay 10 Amp SPDT with
24 Vac/dc/120 Vac Coil
SPECIFICATIONS
# Relays & Contact Type:
Expected Relay Life:
Operating Temperature:
Humidity Range:
Operate Time:
Relay Status:
Dimensions:
Approvals:
Housing Rating:
Gold Flash:
Override Switch:
One (1) SPDT Continuous Duty Coil
10 million cycles minimum mechanical
-30 to 140° F
5 to 95% (noncondensing)
6ms
LED On = Activated
1.70” x 2.80” x 1.50” with .50” NPT nipple
Wires:
, 600V Rated
16”
UL Listed, UL916, UL864, C-UL Canada
California State Fire Marshal
UL Accepted for Use in Plenum, NEMA 1
No
No
Contact Ratings:
10 Amp General Use @ 277 Vac
10 Amp Resistive @ 30 Vdc (N/O)
7 Amp Resistive @ 30 Vdc (N/C)
1/2 HP @ 125 Vac
1 HP @ 250 Vac
1/4 HP @ 277 Vac
470 VA Pilot Duty @ 125 Vac
770 VA Pilot Duty @ 250 Vac
Coil Current:
24 mA @ 20 Vac
28 mA @ 24 Vac
44 mA @ 35 Vac
28 mA @ 120 Vac
13 mA @ 20 Vdc
16 mA @ 24 Vdc
25 mA @ 35 Vdc
RIB2401C-RD
• Red housing
RIB2401C-N4
• NEMA 4X housing
Coil Voltage Input:
24 Vac/dc ; 120 Vac ; 50-60 Hz
Drop Out = 3.0 Vac / 3.8 Vdc
Pull In = 20 Vac / 20 Vdc