20 AMP POWER CONTROL RELAY
RIB023P
Enclosed Relay 20 Amp 3PST-N/O with
208-277 Vac Coil
Wht/Brn
208-277 Vac
Wht/Brn
208-277 Vac
SPECIFICATIONS
# Relays & Contact Type:
Expected Relay Life:
Operating Temperature:
Humidity Range:
Operate Time:
Relay Status:
Dimensions:
Wires:
Approvals:
Housing Rating:
Gold Flash:
Override Switch:
Blu - N/O
Blu - N/O
Yel - N/O
Yel - N/O
Org - N/O
Org - N/O
One (1) 3PST Continuous Duty Coil
10 million cycles minimum mechanical
-30 to 140° F
5 to 95% (noncondensing)
20ms
LED On = Activated
4.00˝ x 4.00˝ x 1.80˝ with .50˝ NPT Nipple
16˝, 600V Rated
UL Listed, UL916, UL864, C-UL California
State Fire Marshal
UL Accepted for Use in Plenum, NEMA 1
No
No
Contact Ratings:
20 Amp Resistive @ 300 Vac, 28 Vdc
20 Amp Ballast @ 277-480 Vac
Not rated for Electronic Ballast
15 Amp Resistive @ 600 Vac
770 VA Pilot Duty @ 120 Vac, 1 Phase
1158 VA Pilot Duty @ 240 Vac, 1 Phase
1110 VA Pilot Duty @ 277 Vac, 1 Phase
1640 VA Pilot Duty @ 480 Vac, 1 Phase
1466 VA Pilot Duty @ 240 Vac, 3 Phase
2112 VA Pilot Duty @ 480 Vac, 3 Phase
Heavy Pilot Duty @ 600 Vac
7.5 HP @ 480 Vac, 3 Phase
5 HP @ 240 Vac, 3 Phase
3 HP @ 480-600 Vac, 1 Phase
2 HP @ 240-277 Vac, 1 Phase
1 HP @ 120 Vac, 1 Phase
Made in USA
Meets
“Buy American”
of ARRA 2009
Coil Current:
187 mA @ 208-277 Vac
Coil Voltage Input:
208-277 Vac ; 50-60 Hz
Drop Out = 60 Vac
Pull In = 160 Vac
Notes:
• Order Normally Closed by adding “-NC” to
end of model number
071417