Johnson Controls RIB01P Data Sheet

RELAYS
20 AMP POWER CONTROL RELAY
RIB01P
Enclosed Relay 20 Amp DPDT with 120 Vac Coil
Blu
Wht/Blk 120 Vac
Wht/Blk 120 Vac
SPECIFICATIONS
# Relays & Contact Type:
Expected Relay Life:
Operating Temperature:
Humidity Range:
Operate Time:
Relay Status:
Dimensions:
Wires:
Approvals:
Housing Rating:
Gold Flash:
Override Switch:
N/C
Yel
Org
N/O
Gry N/C
Prp
Brn N/O
One (1) DPDT Continuous Duty Coil 10 million cycles minimum mechanical
-30 to 140° F 5 to 95% (noncondensing) 18ms LED On = Activated
4.00˝ x 4.00˝ x 1.80˝ with .50˝ NPT Nipple 16˝, 600V Rated UL Listed, UL916, UL864, C-UL California State Fire Marshal UL Accepted for Use in Plenum, NEMA 1 Yes No
Contact Ratings:
20 Amp Resistive @ 300 Vac 20 Amp Resistive @ 28 Vdc 20 Amp Ballast @ 277-480 Vac
Not rated for Electronic Ballast
15 Amp Resistive @ 600 Vac 770 VA Pilot Duty @ 120 Vac 1158 VA Pilot Duty @ 240 Vac 1109 VA Pilot Duty @ 277 Vac 1640 VA Pilot Duty @ 480 Vac Heavy Pilot Duty @ 600 Vac 3 HP @ 480-600 Vac 2 HP @ 240-277 Vac 1 HP @ 120 Vac
Coil Current:
105 mA @ 120 Vac
Made in USA
Buy American
of ARRA 2009
Coil Voltage Input:
120 Vac ; 50-60 Hz Drop Out = 35 Vac Pull In = 85 Vac
Meets
041417