Johnson Controls RIB013P Data Sheet

RELAYS
Wht/Blk 120 Vac
Wht/Blk 120 Vac
Blu - N/O
Blu - N/O
Yel - N/O
Yel - N/O
20 AMP POWER CONTROL RELAY
RIB013P
Enclosed Relay 20 Amp 3PST-N/O with 120 Vac Coil
SPECIFICATIONS
# Relays & Contact Type:
Expected Relay Life:
Operating Temperature:
Humidity Range:
Operate Time:
Relay Status:
Dimensions:
Approvals:
Housing Rating:
Gold Flash:
Override Switch:
One (1) 3PST Continuous Duty Coil 10 million cycles minimum mechanical
-30 to 140° F 5 to 95% (noncondensing) 20ms LED On = Activated
4.00˝ x 4.00˝ x 1.80˝ with .50˝ NPT Nipple 16˝, 600V Rated
Wires:
UL Listed, UL916, UL864, C-UL California State Fire Marshal UL Accepted for Use in Plenum, NEMA 1 No No
Contact Ratings:
20 Amp Resistive @ 300 Vac, 28 Vdc 20 Amp Ballast @ 277-480 Vac
Not rated for Electronic Ballast
15 Amp Resistive @ 600 Vac 770 VA Pilot Duty @ 120 Vac, 1 Phase 1158 VA Pilot Duty @ 240 Vac, 1 Phase 1110 VA Pilot Duty @ 277 Vac, 1 Phase 1640 VA Pilot Duty @ 480 Vac, 1 Phase 1466 VA Pilot Duty @ 240 Vac, 3 Phase 2112 VA Pilot Duty @ 480 Vac, 3 Phase Heavy Pilot Duty @ 600 Vac
7.5 HP @ 480 Vac, 3 Phase 5 HP @ 240 Vac, 3 Phase 3 HP @ 480-600 Vac, 1 Phase 2 HP @ 240-277 Vac, 1 Phase 1 HP @ 120 Vac, 1 Phase
Made in USA
Meets
Buy American
of ARRA 2009
Coil Current:
154 mA @ 120 Vac
Coil Voltage Input:
120 Vac ; 50-60 Hz Drop Out = 35 Vac Pull In = 85 Vac
Notes:
Order Normally Closed by adding “-NC” to
end of model number
071417
Loading...