Johnson Controls RH Series Engineering Manual

FORM 146.00-EG5 (616)
MODEL RH
GEOTHERMAL HYDRONIC HEAT PUMP
ENGINEERING GUIDE
1.5–6 Tons
R-410A Refrigerant
Table of Contents
The Hydronic Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
Inside the Hydronic Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Water Quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
The Aurora Base Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-12
Application Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13-19
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Antifreeze Correction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
RH SERIES ENGINEERING GUIDE
AHRI/ISO 13256-2 Performance Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Pressure Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Reference Calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Legend and Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Performance Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26-39
Wiring Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40-45
Accessories and Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46-47
Engineering Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48-49
Revision Guide. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
RH SERIES ENGINEERING GUIDE
Model Nomenclature
1-4
5-7 8 9 10 11 12
RHSW 050 R 0 0 A C
Model
RHSW – RH Series Hydronic
Heat Pump
Unit Capacity
018, 025, 040, 050, 060, 075
Reversible Option
H- Heating Only R- Reversible
Voltage
0 – 208-230/60/1 (Commercial) 2 – 265/60/1 (025 & 050 only) 3 – 208-230/60/3 (040-075) 4 – 460/60/3 (025-075) 5 – 575/60/3 (040-075)
Hot Water Option
0 – No Hot Water Generation, No IntelliStart 2 – Hot Water Generation, No IntelliStart 3 – No Hot Water Generation, IntelliStart 5 – Hot Water Generation, IntelliStart
1,3
13
C
14-15
SS *
16
Vintage
* – Factory Use Only
Future Option
SS – Standard
Load Coax
C – Copper
N – Cupronickel
Source Coax
C – Copper N – Cupronickel
Controls Option
A – Aurora™ Base Controls (ABC)
Rev.: 10 June 2016
2
NOTES: 1 – Available on 040, 050, 060, and 075 only. Hot water generator requires field installed external pump kit.
2 – 018 and 025 heating only models are available only with copper double wall vented load coax for potable water,
and are not designed to be converted to dedicated cooling units.
 3 – IntelliStart not available on 265/60/1 and 575/60/3 voltages.
RH Series hydronic units are Safety listed under UL1995 thru ETL and performance tested in accordance with standard AHRI/ISO 13256-2. AHRI does not currently certify water-to-water products under AHRI/ ISO 13256-2.
4
4
The Single Hydronic Series
RH SERIES ENGINEERING GUIDE
Features
High efficiency copper coaxial
heat exchanger (vented
double walled available only
on 018 and 025 "heating only"
models)
Optional IntelliStart
reduces starting current
by 60-70%
Field switchable control
box (end to end) for
application flexibility
Insulated and corrosion
resistant cabinet to
reduce noise
Aurora controls
Aurora "Base" Controls
Dual isolation compressor
mounts to reduce noise
and vibration
Captive FPT water connections
eliminate 'egg-shaping' backup
Discharge Muffler Helps quiet compressor gas pulsations
Zero ODP and low GWP R-410A refrigerant
Optional Hot Water Generator available on
040-075
High efficiency copper or cupronickel coaxial heat exchangers
Full refrigerant suction tube, heat exchanger, and waterline insulation to prevent
condensation at low loop temperatures
High efficiency scroll compressors for improved
reliability
Compressor sound blankets for reduced noise
Standard waterlines out the front (field switchable to back via control box)
wrench
What’s New?
• AuroraTM Communicating Control Features
- Traditional Safety Sensors: HP, LP, condensate overflow, freeze detection loop, freeze detection load.
- Communicating Modular Design: Communicating modular design for flexibility and expandability
5
RH SERIES ENGINEERING GUIDE
Single Hydronic Series cont.
High Efficiency
Large oversized water-to-water refrigerant heat exchangers and scroll compressors provide extremely efficient operation. The Aurora Controls extend this innovation and performance.
Operating Efficiencies
• Environmentally friendly R-410A refrigerant reduces ozone depletion.
• An optional hot water generator is available on 040, 050, 060, and 075 to generate hot water at considerable savings while improving overall system efficiency.
• High-stability bidirectional expansion valve provides superior performance.
• Efficient scroll compressors operate quietly.
• Oversized coaxial tube water-to-refrigerant heat exchanger increases efficiency.
Standard Features
• Heavy gauge cabinet
• Quiet scroll compressors in all models
• All interior cabinet surfaces are insulated with
[12.7 mm] thick 1
1
2 lb. [681 g] density, surface coated,
1
2 in.
acoustic type glass fiber insulation.
• Optional IntelliStart
®
to reduce starting current
(208-230/60/1)
• Field switchable control box
• Ultra-compact cabinet
• Multi-density laminate lined compressor blanket designed to suppress low frequency noise.
• Discharge line mufflers to help quiet compressor discharge gas pulsations.
Product Quality
• Heavy-gauge steel cabinets are finished with a durable polyester powder coat paint for long lasting beauty and service.
• All refrigerant brazing is performed in a nitrogen atmosphere.
• The 018H and 025H are available with load side copper vented double wall coaxial heat exchangers.
• Coaxial heat exchangers, refrigerant suction lines, hot water generator, and all water pipes are fully insulated to reduce condensation problems in low temperature operation.
• Computer controlled deep vacuum and refrigerant charging system.
• All joints are leak detected for maximum leak rate of less than
• Computer bar code equipped assembly line ensures all components are correct.
• All units are computer run-tested with water to verify both function and performance.
• Safety features include high- and low-pressure refrigerant controls to protect the compressor; hot water high-limit hot water generator pump shutdown.
1
4 oz. per year.
Easy Maintenance and Service Advantages
• Removable compressor access panels.
• Quick attach wiring harnesses are used throughout for fast servicing.
• High and low pressure refrigerant service ports.
Options and Accessories
• Optional hot water generator with externally mounted pump (230/60/1) and water heater plumbing connector.
• Closed loop, source side, circulating pump kit
• Closed loop, load side, circulating pump kit
• Water connection kits
• Geo-Storage Tank (80-120 Gal.)
• IntelliStart
• HydroZone, tank control with outdoor reset
• HydroLogic
• HydroStat, communicating set point control
Application Flexibility
• Designed to operate with entering source temperature of 25°F and leaving load temperatures of 40°F to 130°F. See the capacity tables to see allowable operating conditions per model.
• Source side flow rates as low as 1.5 GPM/ton for well water, 50°F [10°C] min. EWT.
• Dedicated heating and heat pump models available.
• Dedicated non-reversible models are shipped as heating only; field convertible to cooling only.
• Modularized unit design and primary/secondary controls for optimum capacity matching and staging.
• Stackable for space conservation (to a maximum 3 units high).
• Compact size allows installation in confined spaces.
• Front or rear plumbing connections.
• Control Panel location is reversible.
6
Inside The Single Hydronic Series
RH SERIES ENGINEERING GUIDE
Refrigerant
Our products all feature zero ozone depletion and low global warming potential R-410A refrigerant.
Cabinet
All units are constructed of corrosion resistant galvanized sheet metal with powder coat paint rated for more than 1000 hours of salt spray. Lift-out access panels provide access to the compressor section from two sides.
Compressors
High efficiency R-410A scroll compressors are used on every model. Scrolls provide both the highest efficiency available and great reliability.
Electrical Box
The control box is "field" movable from front to back for ease of application. Separate knockouts for low voltage, and two for power on, front and back, allow easy access to the control box. Large 75VA transformer assures adequate controls power for accessories.
Water Connections
Flush mount FPT water connection fittings allow one wrench leak-free connections and do not require a backup wrench. Factory installed water line thermistors can be viewed through the microprocessor interface tool.
Thermostatic Expansion Valve
All models utilize a balanced port bidirectional thermostatic expansion valve (TXV) for refrigerant metering. This allows precise refrigerant flow in a wide range of entering water variation (25 to 120°F [-7 to 49°C]) found in geothermal systems. The TXV is located in the compressor compartment for easy access.
Service Connections and Serviceability
Two Schrader service ports are provided for each unit. The suction side and discharge side ports are for field charging and servicing access. All valves are 7/16 in. SAE connections.
4-Way Reversing Valve
Units feature a reliable all-brass pilot operated refrigerant reversing valve. The reversing valve operation is limited to change of mode by the control to enhance reliability.
IntelliStart
The optional IntelliStart single phase soft starter will reduce the normal start current (LRA) by 60-70%. This allows the heat pump to go off-grid. Using IntelliStart also provides a substantial reduction in light flicker, reduces start-up noise, and improves the compressor's start behavior. IntelliStart is available in a field retrofit kit or as a factory installed option. IntelliStart is available on 208-230/60/1 voltage.
Water-to-Refrigerant Heat Exchanger Coil
Large oversized coaxial refrigerant­to-water heat exchangers provide unparalleled efficiency. The coaxes are designed for low pressure drop and low flow rates. All coaxes are pressure rated to 450 psi water side and 600 psi on the refrigerant side. Refrigerant-to-water heat exchangers will be coated with ThermaShield to prevent condensation in low temperature loop operation. Vented, double walled heat exchanger suitable for potable water systems are standard on 018-025 heating only models.
7
RH SERIES ENGINEERING GUIDE
Water Quality
General
Water-to-water heat pumps may be successfully applied in a wide range of residential and light commercial applications. It is the responsibility of the system designer and installing contractor to ensure that acceptable water quality is present and that all applicable codes have been met in these installations. Failure to adhere to the guidelines in the water quality table could result in loss of warranty.
Application
These heat pumps are not intended for direct coupling to swimming pools and spas. If used for this type of applica­tion, a secondary heat exchanger must be used. Failure to supply a secondary heat exchanger for this application will result in warranty exclusion for primary heat exchanger cor­rosion or failure.
Water Treatment
Do not use untreated or improperly treated water. Equipment damage may occur. The use of improperly treated or untreated water in this equipment may result in scaling, erosion, corrosion, algae or slime. The services of a qualified water treatment specialist should be engaged to determine what treatment, if any, is required. The product warranty specifically excludes liability for corrosion, erosion or deterioration of equipment.
The heat exchangers and water lines in the units are copper or cupronickel tube. There may be other materials in the building’s piping system that the designer may need to take into consideration when deciding the parameters of the water quality.
If an antifreeze or water treatment solution is to be used, the designer should confirm it does not have a detrimental effect on the materials in the system.
Contaminated Water
In applications where the water quality cannot be held to prescribed limits, the use of a secondary or intermediate heat exchanger is recommended to separate the unit from the contaminated water.
The following table outlines the water quality guidelines for unit heat exchangers. If these conditions are exceeded, a secondary heat exchanger is required. Failure to supply a secondary heat exchanger where needed will result in a warranty exclusion for primary heat exchanger corrosion or failure.
WARNING: Must have intermediate heat exchanger when used in pool and spa applications.
Water Quality Guidelines
Material Copper 90/10 Cupronickel 316 Stainless Steel
pH Acidity/Alkalinity
Scaling
Corrosion
Iron Fouling
(Biological Growth)
Erosion
NOTES: Grains = ppm divided by 17
mg/L is equivalent to ppm
Calcium and
Magnesium Carbonate
Hydrogen Sulfide
Chlorine Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Chlorides Less than 20 ppm Less than 125 ppm Less than 300 ppm
Carbon Dioxide Less than 50 ppm 10 - 50 ppm 10 - 50 ppm
Ammonia Less than 2 ppm Less than 2 ppm Less than 20 ppm
Ammonia Chloride Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Ammonia Nitrate Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Ammonia Hydroxide Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Ammonia Sulfate Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Total Dissolved Solids (TDS) Less than 1000 ppm 1000 - 1500 ppm 1000 - 1500 ppm
LSI Index +0.5 to -0.5 +0.5 to -0.5 +0.5 to -0.5
Iron, FE
Bacterial Iron Potential
Iron Oxide
Suspended Solids
Threshold Velocity
(Fresh Water)
Less than 0.5 ppm (rotten egg
Sulfates Less than 125 ppm Less than 125 ppm Less than 200 ppm
2
+ (Ferrous)
smell appears at 0.5 ppm)
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
7 - 9 7 - 9 7 - 9
(Total Hardness)
less than 350 ppm
< 0.2 ppm < 0.2 ppm < 0.2 ppm
< 6 ft/sec < 6 ft/sec < 6 ft/sec
(Total Hardness)
less than 350 ppm
10 - 50 ppm Less than 1 ppm
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
(Total Hardness)
less than 350 ppm
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
2/22/12
8
RH SERIES ENGINEERING GUIDE
The Aurora Base Control System
Aurora ‘Base’ Control
The Aurora ‘Base’ Control (ABC) System is a complete residential and commercial comfort system that brings all aspects of the HVAC system into one cohesive module network. The ABC features microprocessor control and HP, LP, condensate and freeze detection, over/ under voltage faults, along with communicating thermostat capability for complete fault detection text at the thermostat.
Aurora uses the Modbus communication protocol to communicate between modules. Each module contains the logic to control all features that are connected to the module. The Aurora ‘Base’ Control (ABC) has two Modbus channels. The rst channel is congured as a master for connecting to devices such as a communicating thermostat, expansion board, or other satellite devices. The second channel is congured as a satellite for connecting the Aurora Interface Diagnostics T
Aurora Control Features Description Aurora ‘Base’
Microprocessor Compressor Control
Base Hot Water Generator
Operation
Base Loop Pump Control
Microprocessor control of compressor for timings with FP1, HP, LP, Condensate, assignable Acc relay
Compressor Contactor powers Hot Water Generator Pump with inline circuit breaker and thermostat limit.
Compressor Contactor powers Loop Pump with inline circuit breaker and no loop pump linking capability.
ool (AID Tool).
Service Device Description Aurora ‘Base’
Allows setup, monitoring and troubleshooting of any Aurora Control.
NOTE: Although the ABC has basic compatibility with all Aurora, new product features may not be available on older AID Tools. To simplify the basic compatibility ensure the
Aurora Interface and Diagnostics
(AID) Tool
Add On Thermostats and Zoning Description Aurora ‘Base’
HydroStat
HZO
HZC
version of AID is at least the same or greater than the ABC software version.
Communicating controller for one hydronic heat pump. Optional
Non-communicating controller for up to four heat pumps. Optional
Non-communicating controller for one hydronic heat pump Optional
For Service
(Ver. 1.xx or greater)
9
RH SERIES ENGINEERING GUIDE
The Aurora Base Control System cont.
Aurora ‘Base’ Control
NOTE: Refer to the Aurora Base Control Application and
Troubleshooting Guide and the Instruction Guide: Aurora Interface and Diagnostics (AID) Tool for additional information.
Control Features
Random start at power up
Anti-short cycle protection
High and low pressure cutouts
Loss of charge
Water coil freeze detection
Over/under voltage protection
Load shed
Emergency shutdown
Diagnostic LED
Test mode push button switch
Alarm output
Accessory output with N.O. and N.C.
Modbus communication (master)
Modbus communication (satellite)
Field Selectable Options via Hardware
DIP Switch (SW1) – Test/Conguration Button (See SW1
Operation Table)
Test Mode
The control is placed in the test mode by holding the push button switch SW1 for 2 - 5 seconds. In test mode most of the control timings will be shortened by a factor of sixteen (16). LED3 (green) will ash at 1 second on and 1 second o. Additionally, when entering test mode LED1 (red) will ash the last lockout one time. Test mode will automatically time out after 30 minutes. Test mode can be exited by pressing and holding the SW1 button for 2 to 5 seconds or
y cycling the power. NOTE: Test mode will automatically
b be exited after 30 minutes.
Reset Conguration Mode
The control is placed in reset conguration mode by holding the push button switch SW1 for 50 to 60 seconds. This will reset all conguration settings and the EEPROM back to the factory default settings. LED3 (green) will turn o when entering reset conguration mode. Once LED3 (green) turns o, release SW1 and the control will reset.
DIP Switch (SW2)
SW2-1 (Source) FP1 Selection – Low water coil temperature
limit setting for freeze detection. On = 30°F;
O = 15°F.
SW2-2 (Load) FP2 Selection – On = 30°F; O = 15 ° F SW2-3 RV – O/B - thermostat type. Heat pump
thermostats with “O” output in cooling or “B” output in Heating can be selected. On = O; O = B.
SW2-4 Access Relay Operation (P2) and 2-5
Access Relay Operation SW2-4 SW2-5
Cycle with Blower n/a
Cycle with Compressor OFF OFF
Water Valve Slow Opening ON OFF
Cycle with Comm. T-stat Hum Cmd n/a
Cycle with Blower - (Not used on water-to-water) Cycle with Compressor - The accessory relay will cycle
with the compressor output.
Water Valve Slow Opening - The accessory relay will cycle and delay both the blower and compressor output for 90 seconds.
SW2-6 CC Operation – selection of single or dual capacity
compressor. On = Single Stage; O = Dual Capacity
SW2-7 Lockout and Alarm Outputs (P2) – selection of a
continuous or pulsed output for both the LO and ALM Outputs. On = Continuous; O = Pulsed
SW2-8 Future Use
Alarm Jumper Clip Selection
From the factory, ALM is connected to 24 VAC via JW2. By cutting JW2, ALM becomes a dry contact connected to ALG.
Field Selectable Options via Software
(Selectable via the Aurora AID Tool)
Safety Features
The following safety features are provided to protect the compressor, heat exchangers, wiring and other components from damage caused by operation outside of design conditions.
Fuse – a 3 amp automotive type plug-in fuse provides protection against short circuit or overload conditions.
Anti-Short Cycle Protection – 4 minute anti-short cycle protection for the compressor.
Random Start – 5 to 80 second random start upon power up.
10
The Aurora Base Control System cont.
RH SERIES ENGINEERING GUIDE
Fault Retry – in the fault condition, the control will stage off the outputs and then “try again” to satisfy the thermostat Y input call. Once the thermostat input calls are satisfied, the control will continue on as if no fault occurred. If 3 consecutive faults occur without satisfying the thermostat Y input call, then the control will go to Lockout mode.
Lockout – The Alarm output (ALM) and Lockout output (L) will be turned on. The fault type identification display LED1 (Red) shall flash the fault code. To reset lockout conditions with SW2-8 On, thermostat inputs “Y1”, “Y2”, and “W” must be removed for at least 3 seconds. To reset lockout conditions with SW2-8 Off, thermostat inputs “Y1”, “Y2”, “W”, and “DH” must be removed for at least 3 seconds. Lockout may also be reset by turning power off for at least 30 seconds or by enabling the emergency shutdown input for at least 3 seconds.
High Pressure – fault is recognized when the Normally Closed High Pressure Switch, P4-9/10 opens, no matter how momentarily. The High Pressure Switch is electrically in series with the Compressor Contactor and serves as a hard­wired limit switch if an overpressure condition should occur.
Low Pressure - fault is recognized when the Normally Closed Low Pressure Switch, P4-7/8 is continuously open for 30 seconds. Closure of the LPS any time during the 30 second recognition time restarts the 30 second continuous open requirement. A continuously open LPS shall not be recognized during the 2 minute startup bypass time.
Loss of Charge – fault is recognized when the Normally Closed Low Pressure Switch, P4-7/8 is open prior to the compressor starting.
Freeze Detection (Source Coax) - set points shall be either 30°F or 15°F. When the thermistor temperature drops below the selected set point, the control shall begin counting down the 30 seconds delay. If the thermistor value rises above the selected set point, then the count should reset. The resistance value must remain below the selected set point for the entire length of the appropriate delay to be recognized as a fault. This fault will be ignored for the initial 2 minutes of the compressor run time.
Freeze Detection (Load Coax) - uses the FP2 input to protect against ice formation on the coax. The FP2 input will operate exactly like FP1.
Over/Under Voltage Shutdown - An over/under voltage condition exists when the control voltage is outside the range of 18 VAC to 30 VAC. If the over/under voltage shutdown lasts for 15 minutes, the lockout and alarm relay will be energized. Over/under voltage shutdown is self­resetting in that if the voltage comes back within range of 18 VAC to 30 VAC for at least 0.5 seconds, then normal operation is restored.
Operation Description
Power Up - The unit will not operate until all the inputs and safety controls are checked for normal conditions. The unit has a 5 to 80 second random start delay at power up. Then the compressor has a 4 minute anti-short cycle delay after the random start delay.
Standby In standby mode, Y1, Y2, W, DH, and G are not active. Input O may be active. The blower and compressor will be off.
Heating Operation
Heating, 1st Stage (Y1) - The compressor is energized 10 seconds after the Y1 input is received.
Cooling Operation
In all cooling operations, the reversing valve directly tracks the O input. Thus, anytime the O input is present, the reversing valve will be energized.
Cooling, 1st Stage (Y1, O) - The compressor is energized 10 seconds after the Y1 input is received.
Emergency Shutdown - Four (4) seconds after a valid ES input, P2-7 is present, all control outputs will be turned off and remain off until the emergency shutdown input is no longer present. The first time that the compressor is started after the control exits the emergency shutdown mode, there will be an anti-short cycle delay followed by a random start delay. Input must be tied to common to activate.
Load Shed - The LS input disables all outputs with the exception of the blower output. When the LS input has been cleared, the anti-short cycle timer and random start timer will be initiated. Input must be tied to common to activate.
11
RH SERIES ENGINEERING GUIDE
The Aurora Base Control System cont.
Aurora ‘Base’ Control LED Displays
These three LEDs display the status, configuration, and fault codes for the control. These can also be read in plain English via the Aurora AID Tool.
Status LED (LED3, Green)
Description of Operation Fault LED, Green
Normal Mode ON Control is Non-functional OFF Test Mode Slow Flash Lockout Active Fast Flash Dehumidification Mode Flash Code 2 (Future Use) Flash Code 3 (Future Use) Flash Code 4 Load Shed Flash Code 5 ESD Flash Code 6 (Future Use) Flash Code 7
Fault LED (LED1, Red)
Red Fault LED
LED Flash
Code*
Lockout
Normal - No Faults OFF – Fault - Input 1 No Auto Fault - High Pressure 2 Yes Hard or Soft Fault - Low Pressure 3 Yes Hard or Soft Fault - Freeze Detection FP2 4 Yes Hard or Soft Fault - Freeze Detection FP1 5 Yes Hard or Soft Fault - Condensate Overflow 7 Yes Hard or Soft
ABC Basic Faults
Fault - Over/Under Voltage 8 No Auto Fault - FP1 & FP2 Sensor Error 11 Yes Hard or Soft
NOTE: All codes >11 use long flash for tens digit and short flash for the ones digit. 20, 30, 40, 50, etc. are skipped.
Reset/
Remove
ABC Control Board Layout
C
CFM
CC
Y1
CC2
CC2
F
G
JW2 ­Alarm
FP2
FP2 FP1 FP1
REV
REV
CCG
PWM
HP HP LP LP
G LO HI
CC FG
F
R
ECM PWM
P4
P13
Fact ory
SW1 Test
RV – K1
CC – K2
P5
P2
ES
CC Hi – K3
Fact ory
Fan – K4
Alarm – K5
Acc – K6
LS
ALG
ALM
ACC c
ACC n c
ACC n o
FP1 – 15oF/30oF
FP2 – 15
RV – B/O
Fault
ACC – Dip 4
CC – Dual/Single
G
L – Pulse/Continuous
Status
ACC – Dip 5
Reheat/Normal
LED3
AURORA BASE
CONTROL™
Fact ory Use
P11
P9
Factory Fan Connection
C
R
LO
O/B
Field ConnectionsField Connections
P1
R
C
LO
O/B
o
F/30oF
G
G
Y1
Y1
Off
On
LED2LED1
1
YR
2
3
Config
4 5
6 7 8
SW2
Com1
Com2
W
Y2
DH
W
Y2
DH
3A-Fuse
G
G
RR
EH1
EH2
P3
C
EH1
C
Fact ory
CO
N/A
(+)
P6
(-)
R
RS485 Exp
C
P7
RS 485
P8
RS485 NET
CC
C
Aurora Interface and Diagnostics (AID) Tool
The Aurora Interface and Diagnostics (AID) Tool is a device that is a member of the Aurora network. The AID Tool is used to troubleshoot equipment which uses the Aurora control via Modbus RTU communication. The AID Tool provides diagnostics, fault management, ECM setup, and system configuration capabilities to the Aurora family of controls. An AID Tool is recommended, although not required, for ECM airflow settings. The AID Tool simply plugs into the exterior of the cabinet in the AID Tool port.
12
Application Notes
RH SERIES ENGINEERING GUIDE
The Closed Loop Heat Pump Concept
The basic principle of a water source heat pump is the transfer of heat into water from the space during cooling, or the transfer of heat from water into the space during heating. Extremely high levels of energy efficiency are achieved as electricity is used only to move heat, not to produce it. Using our typical water-to-water heat pump one unit of electricity will move four to five units of heat.
When multiple water source heat pumps are combined on a common circulating loop, the ultimate in energy efficiency is created: The water-to-water units on cooling mode are adding heat to the loop which the units in heating mode can absorb, thus removing heat from the area where cooling is needed, recovering and redistributing that heat for possible utilization elsewhere in the system. In modern commercial structures, this characteristic of heat recovery from core area heat generated by lighting, office equipment, computers, solar radiation, people or other sources, is an important factor in the high efficiency and low operating costs of our closed source heat pump systems.
Return Water
Water-to-water
Unit
Water-to-water
Unit
low because units can be added to the loop on an "as needed basis"- perfect for speculative buildings. Installed costs are low since units are self-contained and can be located adjacent to the occupied space, requiring minimal ductwork. Maintenance can be done on individual units without system shut-down. Conditions remain comfortable since each unit operates separately, allowing cooling in one area and heating in another. Tenant spaces can be finished and added as needed. Power billing to tenants is also convenient since each unit can be individually metered: each pays for what each uses. Nighttime and/or weekend uses of certain areas are possible without heating or cooling the entire facility. A decentralized system also means if one unit should fault, the rest of the system will continue to operate normally, as well as eliminating air cross-contamination problems and expensive high pressure duct systems requiring an inefficient electric resistance reheat mode.
The Best Approach
There are a number of proven choices in the type of system which would be best for any given application. Most often considered are:
Vertical - Closed Loop/Ground Source
Heater/
Rejector
Pumps
Water-to-water
Unit
Water-to-water
Unit
Supply Water
Water-to-water
Unit
Water-to-water
Unit
In the event that a building's net heating and cooling requirements create loop temperature extremes, our units have the extended range capacity and versatility to maintain a comfortable environment for all building areas. Excess heat can be stored for later utilization or be added or removed in one of three ways; by ground-source heat exchanger loops: plate heat exchangers connected to other water sources, or conventional cooler/boiler configurations. Your sales representative has the expertise and computer software to assist in determining optimum system type for specific applications.
The Closed Loop Advantage
A properly applied water source heat pump system offers many advantages over other systems. First costs are
Closed Loop/Ground-Source Systems utilize the stable temperatures of the earth to maintain proper water source temperatures (via vertical or horizontal closed loop heat exchangers) for our extended range heat pump system. Sizes range from a single unit through many hundreds of units. When net cooling requirements cause closed loop water temperatures to rise, heat is dissipated into the cooler earth through buried high strength plastic pipe "heat exchangers." Conversely if net space heating demands cause loop heat absorption beyond that heat recovered from building core areas, the loop temperature will fall causing heat to be extracted from the earth. Due to the extended loop temperatures, AHRI/ISO 13256-1 Ground Loop Heat Pumps are required for this application.
13
RH SERIES ENGINEERING GUIDE
Application Notes cont.
Because auxiliary equipment such as a fossil fuel boiler and cooling tower are not required to maintain the loop temperature, operating and maintenance costs are very low. Ground-source systems are most applicable in residential and light commercial buildings where both heating and cooling are desired, and on larger envelope dominated structures where core heat recovery will not meet overall heating loads. Both vertical and horizontally installed closed-loops can be used. The land space required for the "heat exchangers" is 100-250 sq. ft./ton on vertical (drilled) installations and 750-1500 sq. ft./ton for horizontal (trenched) installations. Closed loop heat exchangers can be located under parking areas or even under the building itself.
On large multi-unit systems, sizing the closed loop heat exchanger to meet only the net heating loads and assisting in the summer with a closed circuit cooling tower may be the most cost effective choice.
Surface Water - Closed Loop/Ground Source
Plate Heat Exchanger - Closed Loop/Ground Water
• Closed Loop/Ground Water Plate Heat Exchanger Systems utilize lake, ocean, well water or other water
sources to maintain closed loop water temperatures in multi-unit systems. A plate frame heat exchanger isolates the units from any contaminating effects of the water source, and allows periodic cleaning of the heat exchanger during off peak hours.
Operation and benefits are similar to those for ground­source systems. Due to the extended loop temperatures, AHRI/ISO 13256-1 Ground Loop Heat Pumps are required for this application. Closed loop plate heat exchanger systems are applicable in commercial, marine, or industrial structures where the many benefits of a water source heat pump system are desired, regardless of whether the load is heating or cooling dominated.
• Closed Loop/Ground-Source Surface Water Systems also utilize the stable temperatures of Surface Water to maintain proper water source temperatures for our extended range heat pump systems. These systems have all of the advantages of horizontal and vertical closed loop systems. Due to the extended loop temperatures, AHRI/ISO 13256-1 Ground Water or Ground Loop Heat Pumps are required for this application.
In cooling dominated structures, the ground-source surface water systems can be very cost effective especially where local building codes require water retention ponds for short term storage of surface run-off. Sizing requirements for the surface water is a minimum of 500 sq. ft./ton of surface area at a minimum depth of 8 feet. Your sales representative should be contacted when designs for heating dominated structures are required.
14
Application Notes cont.
RH SERIES ENGINEERING GUIDE
Cooler/Boiler - Closed Loop
• Closed Loop /Cooler-Boiler Systems utilize a closed heat
recovering loop with multiple water source heat pumps in the more conventional manner. Typically a boiler is employed to maintain closed loop temperatures above 60°F and a cooling tower to maintain loop temperatures below 90°F. These systems are applicable in medium to large buildings regardless of whether the load is heating or cooling dominated. Due to the moderate loop temperatures, AHRI/ISO 13256-1 Water Loop Heat Pumps are required for this application.
Typical Application Piping
30 psi
RELIEF VALVE
Back Flow Preventer /
Pressure Relief Valve
Dielectric
Unions
Dielectric
Unions
NOTES: * A 30 psi pressure relief valve (Part No: SRV30) should be used in
hydronic applications. ** Vent valve or P/T port at highest point in return line prior to ball valve.
Pressure
Gauge
GEO
STORAGE
TANK
1-1/2 in. FPT
Dip Tube
Ball Valve
Expansion
Tank
Air
Vent
Air
Separator
Ball Valve
LOAD PUMP
FROM
HWG
5 Series
Hydronic Unit
TO
HWG
HYDRONIC
PUMP
Source OUT
P/T PortsP/T Ports
Source IN
LOAD
HOT
(Piped in
series to
an electric
water heater)
Vent Valve/
P/T Port**
DOMESTIC
COLD
15
RH SERIES ENGINEERING GUIDE
Application Notes cont.
Heating with hot water is versatile because there are many ways of distributing the heat through the building. The options range from heavy cast iron radiators seen in older buildings to modern, baseboard-style convection radiation, and from invisible radiant floor heating to forced air systems using fan coil units.
A boiler is often used to make domestic hot water and to heat swimming pools or hot tubs.
The various distribution systems have all been used successfully with a geothermal heat pump system. When designing or retrofitting an existing hydronic heating system, however, the water temperature produced by the heat pump is a major consideration.
In general, heat pumps are not designed to produce water above 130°F. The efficiency decreases as the temperature difference ( loop) and the supply water (to the distribution system) increases. Figure 1 illustrates the effect of source and load temperatures on the system. The heating capacity of the heat pump also decreases as the temperature difference increases.
When using the various types of hydronic heat distribution systems, the temperature limits of the geothermal system must be considered. In new construction, the distribution system can easily be designed with the temperature limits in mind. In retrofits, care must be taken to address the operating temperature limits of the existing distribution system.
Figure 1: As the Performance (COP) decreases. When the system produces 130°F water from a 30°F earth loop, the the COP is approximately 2.5. If the system is producing water at 90°F, the
3.8, an increase of over 50%.
ΔT) between the heat load (generally the earth
ΔT increases, the Coefficient of
ΔT is 100°F, and
ΔT is 60°F and the COP rises to about
10
8
6
COP
4
Baseboard Radiation
In existing systems, baseboard radiation is typically designed to operate with 160° to 240°F water or steam. Baseboard units are typically copper pipe with aluminum fins along the length of the pipe, as shown in Figure 2. A decorative cover is normally fitted over the fin tube.
The operation of a baseboard radiation system depends on setting up a convection current in the room: air is warmed by the fin tube, rises and is displaced by cool air.
The heating capacity of a baseboard system is a factor of the area of copper tube and fins exposed to the air and the temperature difference between the air and the fin tube. The velocity and volume of water flowing through the baseboard affects the temperature of the copper and fins. Baseboard units are normally rated in heat output/ length of baseboard at a standard water temperature and flow. Manufacturers can provide charts which will give the capacities at temperatures and flows below the standard. Figure 3 shows approximate heating capacities for fin tube radiation using water from 100° to 130°F water.
Baseboards are available using two or three fin tubes tiered above one another in the same cabinet. With the additional surface area, the air can be heated enough to set up a convection current with water temperatures as low as 110° to 130°F (see Figure 3).
It is important to ensure that the heat output of the system is adequate to meet the heat loss of the room or building at the temperatures the geothermal system is capable of producing.
Baseboard radiation is limited to space heating. Cooling is typically provided by a separate, forced air distribution system.
Figure 2: Baseboard radiators are typically constructed of copper tube with closely spaced aluminum fins attached to provide more surface area to dissipate heat. Some of the factors affecting the amount of heat given off by fin tube radiators are the water temperature, water velocity, air temperature, and fin spacing and size.
/Zc[W\c[4W\a
2
0
0 20 40 60 80 100
Temperature Difference (°F)
3\QZ]ac`S
1]^^S` BcPS
4W\BcPS
16
Loading...
+ 36 hidden pages