Johnson Controls RHP14J 184S21, RHP14J 244S21, RHP14J 364S21, RHP14J 424S21, RHP14J 304S21 Technical Manual

...
RHP SERIES SPLIT -SYSTEM HEAT PUMPS
14.5 SEER – R-410A – 1 PHASE
1.5 THRU 5 NOMINAL TONS
MODELS: RHP14J18 THRU 60
Due to continuous product improvement, specif ic a t io ns are subject to change without notice.
www.upgnet.com
Additional rating information can be found at
www.ahridirectory.org
WARRANTY SUMMARY*
Extended 10-Y ears limited parts warranty. Standard 10-Years limited compressor warranty. Extended 10-Years limited parts warranty requires online
registration within 90 days of purchase for replacement or closing for new home construction.
*Does not apply to R-22 models, 3-Phase models, or internet sales.
See Limited Warranty certificate in User's Information Manual for details.
®
TECHNICAL GUIDE
TECHNICAL GUIDE
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
810754-UTG-C-0214
DESCRIPTION
The 14.5 SEER Series unit is the outdoor part of a versatile cli­mate system. It is designed with a matching indoor coil compo­nent from Johnson Controls Unitary Products. Available for typical applications this climate system is supported with acces­sories and documents to serve specific functions.
FEATURES
Small Footprint - The compact footprint is a perfect fit for any application.
Quality Condenser Coils - The coil is constructed of copper tubing and enhanced aluminum fins for increased perfor­mance.
Coil Protection - Coils are protected from damage by a slot­ted, stamped steel coil guard.
Protected Compressor - Compressors are protected inter­nally by a high pressure relief valve and a temperature sen­sor, and externally by the system high and low pressure switches. A factory installed liquid line filter-drier further pro­tects the compressor against moisture and debris. The 5-ton system utilizes a two-stage compressor.
Environmentally Friendly Refrigerant - The R-410A refrig- erant delivers environmentally friendly performance with zero ozone depletion.
Durable Finish - An automotive quality finish provides the ultimate protection from harmful UV rays and rust-creep, ensuring a long-lasting, high quality apprearance. A powde r paint top coat is applied over a baked on primer using a gal­vanized, zinc coated steel base material.
Lower Installed Cost - Installation time and costs are reduced by easy power and control wiring connections. The unit is factory charged for a 15-foot lineset. The small base dimension means less space is required on the ground or roof.
Top Discharge - Warm air from the top mounted fan is blown up, away from the structure and any landscaping. This allows compact location on multi-unit applications.
Low Operating Sound Levels - The upward air flow carries the normal operating noise away from the living area. The rigid top panel effectively isolates any motor sound. Isolator mounted compressor and the condenser coil muffle the nor­mal fan motor and compressor operating sounds.
Low Maintenance - Long life, permanently lubricated motor­bearings need no annual servicing.
Easy Service Access - Fully exposed refrigerant connec­tions and a single panel covering the electrical controls make for easy servicing of the unit.
Secured Service Valves - Secured, re-usable service valves are provided on both the liquid and vapor sweat con­nections for ease of evacuating and charging.
Advanced System Control - These heat pumps feature a demand-defrost control system to provide optimal comfort and reliable operation over a wide range of conditions.
Agency Listed - Safety certified by CSA to UL 1995 / CSA
22.2. Performance certified to ANSI/AHRI Standard 210/240 in accordance with the Unitary Small Equipment certification program.
810754-UTG-C-0214
B
C
A
Physical and Electrical Data
MODEL
RHP14J
184S21
Unit Supply Voltage 208-230V, 1 60Hz Normal Voltage Range
Minimum Circuit Ampacity Max. Overcurrent Device Amps Min. Overcurrent Device Amps
Compressor Amps
Crankcase Heater Factory External Discharge Muffler Factory External Check Valve
HS Kit Required with TXV Fan Diameter Inches
Fan Motor
Coil
Liquid Line Set OD (Field Installed) Vapor Line Set OD (Field Installed)
Unit Charge (Lbs. - Oz.) Charge Per Foot, Oz.
1
2
3
Type Rated Load Locked Rotor
4
Rated HP Rated Load Amps Nominal RPM Nominal CFM Face Area Sq. Ft. Rows Deep Fins / Inch
5
11.9 17.6 17.3 19.7 23.7 28.5 35.3 20 30 30 30 40 50 60
15 20 20 20 25 30 40
Scroll Scroll Scroll Recip Scroll Scroll 2-Stage Scroll
9.0 13.4 12.8 14.7 17.9 21.8 35.3
48.0 58.3 64.0 74.0 112.0 117.0 118.0
No No No Yes No No No
Yes Yes Yes
No No No No No No No No No Yes No No No
24 22 24 24 24 24 24
1/10 1/8 1/4 1/4 1/4 1/4 1/4
0.7 0.8 1.3 1.3 1.3 1.3 1.3
825 1075 850 850 850 850 850
2000 2000 3900 3800 3600 3500 3800
15.72 19.17 23.58 23.58 23.58 23.58 23.58 1 1 1 1 1 2 2
22 22 22 22 22 18 18 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/4 3/4 3/4 3/4 7/8 7/8 1-1/8
6 - 15 7 - 14 9 - 14 10 - 6 11 - 4 13 - 1 14 - 2
0.62 0.62 0.62 0.62 0.67 0.67 0.75
Operating Weight Lbs. 145 145 176 193 198 248 290
1. Rated in accordance with AHRI Standard 110-2012, utilization range “A”.
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. See Hard Start Kit Accessory Insta llation Manual for Hard Start Kit part number for each model.
5. The Unit Charge is correct for the outdoor unit, smallest matched indoor un it, and 15 fe et of ref rig erant t ubing . For tubin g leng ths other than 15 fe et, add or sub­tract the amount of refrigerant, using the difference in length multiplied by the per foot value.
RHP14J
244S21
RHP14J
304S21
RHP14J
364S21
187 to 252
Combined
DM/CV
RHP14J
424S21
RHP14J
484S21
Yes Yes Yes
RHP14J
604S21
2 Johnson Controls Unitary Products
Unit
Model
Dimensions
(Inches)
A B C Liquid Vapor
Refrigerant Connection
Service Valve Size
18 28-1/4 34 34 24 40-1/4 29-1/2 29-1/2 30 40-1/4 34 34 36 40-1/4 34 34
3/8
42 40-1/4 34 34 48 40-1/4 34 34
60 40-1/4 34 34
* Adapter Fitting Required for 1-1/8" Lilneset. All dimensions are in inches and are subject to change without notice.
Overall height is from bottom of base pan to top of fan guard. Overall length and width include screw heads.
3/4
7/8
7/8
*
810754-UTG-C-0214
System Charge for Various Matched Systems
Outdoor Unit RHP14J184S21 RHP14J244S21 RHP14J304S21 RHP14J364S21 RHP14J424S21 RHP14J484S21 RHP14J604S21
1,2
Required Orifice or TXV
Indoor Unit
3,4,5
RFCX24BE .051 / TXV + 0 .059 / TXV + 0 – RFCX30BE .051 / TXV + 0 .059 / TXV + 0 – RFCX36CE .063 / TXV + 0 .071 / TXV + 0 – RFCX42DE .071 / TXV + 5 – RFCX48DE .071 / TXV + 25 .075 / TXV + 0 TXV + 0 – RFCX60DE TXV + 8 TXV + 10 TXV + 0 RFCX24BP .051 / TXV + 0 .059 / TXV + 0 – RFCX36BP .063 / TXV + 0 .071 / TXV + 0 – RFCX42CP .071 / TXV + 5 – RFCX48DP .075 / TXV + 0 TXV + 0 – RFCX60DP – FC/MC/PC32 .051 / TXV + 0 .059 / TXV + 0 – FC/MC/PC35 .051 / TXV + 0 .059 / TXV + 0 – FC/MC/PC37 .051 / TXV + 13 .059 / TXV + 12 .063 / TXV + 0 .071 / TXV + 0 – FC/MC/PC43 .051 / TXV + 13 .059 / TXV + 12 .063 / TXV + 0 .071 / TXV + 0 – FC/MC/PC48 .071 / TXV + 5 – FC/MC/PC60 .071 / TXV + 25 .075 / TXV + 0 TXV + 0 – FC/MC62 TXV + 8 TXV + 10 TXV + 0 FC64 TXV + 29 TXV + 8 UC48 .071 / TXV + 23 – UC60 .071 / TXV + 38 .075 / TXV + 4 – Some of the combinations shown in the above System Charge table require Advanced Main Air Circulating Fan indoor product. For approved coil
only matches, please see the “COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils” table.
FOOTNOTES:
1. For applications requiring a TXV use S1-1TVM*** series kit.
2. Approved orifice(s) shipped with outdoor unit.
3. Systems matched with furnaces or air handlers not equipped with blower-off delays may require blo w er Time Delay Kit S1-2FD06700224.
4. PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.
5. Refer to Cooling and Heating Performance Data tables for actual performance for specified system matches.
PROCEDURES:
1. Unit factory charge listed on the unit nameplate includ es refrigerant for the o ut door unit, the smallest matched indoor uni t, and 15 feet of interconnect ing line t ubing.
2. Verify the TXV or orifice and additional charge required for specific matched indoor unit in the system using the above table.
3. Add additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in Physical and Electrical Data Table.
4. For indoor matches requiring additional charge, the refrigerant needs to be weighed in for specific matched indoor unit and lineset length.
5. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + charge adder for matched indoor unit + charge adder for line set.
.051/4F1 .059/4G1 .063/4G1 .071/4H1 .075/4J1 4P1 4K1
Additional Charge, Oz
Johnson Controls Unitary Products 3
810754-UTG-C-0214
COOLING CAPACITY - With Air Handler Coils
UNIT
MODEL
AIR HANDLER
MODEL WIDTH
COIL
MODEL
1
RATED
CFM
TOTAL SENS.
14.5 SEER HP WITH AIR HANDLERS
RFCX24BE 17.5 585 18.0 13.3 14.50 12.00
RHP14J184S21
RFCX30BE 17.5 660 18.0 13.1 15.00 12.50 RFCX24BP 17.5 675 18.0 13.1 13.00 11.00 RFCX24BE 17.5 825 23.0 17.4 15.00 12.50
RHP14J244S21
RFCX30BE 17.5 800 23.0 17.4 15.00 12.50 RFCX24BP 17.5 740 22.2 16.0 13.25 11.35
RHP14J304S21
RFCX36CE 21.0 1000 30.0 21.7 15.00 12.50 RFCX36BP 17.5 1060 28.8 22.0 13.25 11.35 RFCX36CE 21.0 1275 36.0 27.4 14.50 12.00 RFCX42DE 24.5 1275 36.0 26.4 15.00 12.50
RHP14J364S21
RFCX48DE 24.5 1195 35.8 26.6 14.50 12.00 RFCX36BP 17.5 1245 35.4 26.2 13.00 11.00 RFCX42CP 21.0 1230 35.6 26.4 13.35 11.45 RFCX48DE 24.5 1125 39.5 27.0 15.00 12.50
RHP14J424S21
RFCX60DE 24.5 1350 39.0 28.8 14.50 12.00 RFCX48DP 24.5 1320 39.5 28.4 13.25 11.35 RFCX48DE 24.5 1295 45.5 30.8 14.00 12.00
RHP14J484S21
RFCX60DE 24.5 1310 47.0 31.6 15.00 12.50 RFCX48DP 24.5 1320 44.5 30.2 13.25 11.35
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ANSI/AHRI Standard 210/240. Cooling MBH based on 80 °F entering air temperature, 50% RH (Relative Humidity), and rated air flow. EER (Energy Efficiency Ratio) is the total cooling output in BTUs at 95 °F outdoor ambient divided by the total electric power in watt-hours at those conditions. SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTUs during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period.
1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number. — = Not applicable. MA Modular Air Handlers use Coil Only Ratings.
COOLING
NET MBH
SEER EER
COOLING CAPACITY - With Air Handler Coils
UNIT
MODEL
AIR HANDLER
MODEL WIDTH
COIL
MODEL
STAGE
1
RATED
CFM
TOTAL SENS.
14.5 SEER HP WITH AIR HANDLERS
RHP14J604S21 RFCX60DE 24.5
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ANSI /AHRI Standard 210/240. Cooling MBH based on 80 °F entering air temperature, 50% RH (Relative Humidity), and rated air flow. EER (Energy Efficiency Ratio) is the total cooling output in BTUs at 95 °F outdoor ambient divided by the total electric power in watt-hours at those conditions. SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTUs during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period.
1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number. — = Not applicable.
MA Modular Air Handlers use Coil Only Ratings.
1 1160 46.0 29.8 2 1835 57.0 41.0
COOLING
NET MBH
SEER EER
15.00 12.20
4 Johnson Controls Unitary Products
COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils (Coil Only Ratings)
COIL
UNIT MODEL
MODEL WIDTH
CFM RANGE
(Min.-max.)
STAGE
RATED
CFM
TOTAL SENS.
14.5 SEER HP COIL ONLY RATINGS
FC/MC/PC32 14.5 450 - 750 600 18.0 12.6 13.25 11.35
RHP14J184S21
FC/MC/PC35 17.5,21.0 450 - 750 600 18.0 12.6 13.20 11.35 FC/MC/PC37 14.5 450 - 750 600 18.0 13.2 13.25 11.35 FC/MC/PC43 17.5,21.0 450 - 750 600 18.0 13.2 13.25 11.35 FC/MC/PC32 14.5 600 - 1000 800 22.2 16.3 13.25 11.35
RHP14J244S21
FC/MC/PC35 17.5,21.0 600 - 1000 800 22.4 16.3 13.20 11.35 FC/MC/PC37 14.5 600 - 1000 800 22.4 16.6 13.25 11.35 FC/MC/PC43 17.5,21.0 600 - 1000 800 22.4 16.6 13.25 11.35
RHP14J304S21
FC/MC/PC37 14.5 800 - 1200 1000 28.6 21.6 13.25 11.35 FC/MC/PC43 17.5,21.0 800 - 1200 1000 28.4 21.6 13.50 11.35 FC/MC/PC37 14.5 1000 - 1400 1200 35.0 25.6 13.00 11.00 FC/MC/PC43 17.5,21.0 1000 - 1400 1200 35.0 25.8 13.00 11.00
RHP14J364S21
FC/MC/PC48 21.0,24.5 1000 - 1400 1200 35.2 25.8 13.35 11.45 FC/MC/PC60 21.0,24.5 1000 - 1400 1200 35.6 26.0 13.35 11.45
UC48 21.0,24.5 1000 - 1400 1200 35.0 26.0 13.25 11.35 UC60 21.0,24.5 1000 - 1400 1200 35.0 25.6 13.25 11.35
RHP14J424S21
FC/MC/PC60 21.0,24.5 1200 - 1600 1200 39.0 27.0 13.25 11.35
FC/MC62 24.5 1200 - 1600 1400 38.0 27.8 13.00 11.00
FC/MC/PC60 21.0, 24.5 1400 - 1800 1400 45.5 31.6 13.25 11.35
RHP14J484S21
FC/MC62 24.5 1400 - 1800 1600 48.0 34.2 14.00 12.00
FC64 24.5 1400 - 1800 1400 48.0 32.0 14.00 12.00
RHP14J604S21
1. Requires a S1-2FD06700224 Blower Time Delay unless a standard furnace is equipped with one. MA Modular Air Handlers use Coil Only Ratings. Furnaces that are listed individually in the above table, such as the RGF1L*P, RGF19*P, and RGF1L*E use Coil Only Ratings.
FC/MC62 24.5 1150 - 1550 1 1350 48.0 31.8 13.30 11.35 FC/MC62 24.5 1600 - 2000 2 1800 56.5 39.5 13.30 11.35
COOLING
NET MBH
810754-UTG-C-0214
1
SEER
EER
COOLING CAPACITY - With High Efficiency Motor Furnaces
UNIT
MODEL
FURNACE
MODEL WIDTH
COIL
MODEL
1
RATED
CFM
TOTAL SENS.
14.5 SEER HP WITH HIGH EFFICIENCY MOTOR FURNACES
RHP14J184S21
RGF19*AE10 14.5 FC/MC/PC32A 600 18.0 13.5 14.50 12.50 RGF19*AE10 14.5 FC/MC/PC37A 600 18.0 13.4 13.50 11.35 RGF19*AE10 14.5 FC/MC/PC32A 775 22.2 16.5 13.25 11.35 RGF19*AE10 14.5 FC/MC/PC37A 800 22.4 16.8 13.50 11.35 RGF19*BE12 17.5 FC/MC/PC35B 800 22.4 16.7 13.70 11.35
RHP14J244S21
RGF19*BE12 17.5 FC/MC/PC43B 800 22.6 16.9 14.00 12.00 RGF19*CE16 21.0 FC/MC/PC35C 800 22.4 16.6 13.50 11.35 RGF19*CE16 21.0 FC/MC/PC43C 800 22.6 16.8 13.50 11.35 RGF19*CE20 21.0 FC/MC/PC35C 800 22.6 16.7 14.20 12.00 RGF19*CE20 21.0 FC/MC/PC43C 800 22.8 17.0 14.20 12.00
RHP14J304S21
RGF19*BE12 17.5 FC/MC/PC43B 975 29.0 21.6 15.10 12.50 RGF19*CE16 21.0 FC/MC/PC43C 1000 29.0 21.6 15.10 12.50
For notes see Page 6.
Johnson Controls Unitary Products 5
COOLING
NET MBH
2
SEER EER
810754-UTG-C-0214
COOLING CAP ACITY - With High Efficiency Motor Furnaces (Continued)
UNIT
MODEL
MODEL WIDTH
FURNACE
14.5 SEER HP WITH HIGH EFFICIENCY MOTOR FURNACES
RGF19*BE12 17.5 FC/MC/PC43B 1125 35.8 25.4 13.25 11.35 RGF19*CE16 21.0 FC/MC/PC43C 1175 36.0 25.4 13.70 11.35 RGF19*CE16 21.0 FC/MC/PC48C 1150 36.0 25.6 14.50 12.00 RGF19*CE16 21.0 FC/PC60C 1175 35.8 25.4 14.50 12.00 RGF19*CE16 21.0 UC48C 1150 36.0 25.6 14.50 12.00 RGF19*CE16 21.0 UC60C 1175 35.6 25.4 14.20 12.00 RGF19*CE20 21.0 FC/MC/PC43C 1150 36.0 25.6 13.70 11.35
RHP14J364S21
RGF19*CE20 21.0 FC/MC/PC48C 1150 36.0 25.6 14.50 12.00 RGF19*CE20 21.0 FC/PC60C 1150 35.8 25.4 14.50 12.00 RGF19*CE20 21.0 UC48C 1150 36.0 25.6 14.50 12.00 RGF19*CE20 21.0 UC60C 1150 35.6 25.4 14.50 12.00 RGF19*DE20 24.5 FC/MC/PC48D 1175 36.0 25.8 14.50 12.00 RGF19*DE20 24.5 FC/MC/PC60D 1175 36.0 25.4 14.50 12.00 RGF19*DE20 24.5 UC48D 1175 36.0 25.8 14.50 12.00 RGF19*DE20 24.5 UC60D 1175 35.6 25.4 14.50 12.00 RGF19*CE16 21.0 FC/MC62D 1400 38.5 28.0 13.15 11.00 RGF19*CE16 21.0 FC/PC60C 1400 39.5 28.6 13.50 11.35
RHP14J424S21
RGF19*CE20 21.0 FC/MC62D 1350 39.0 28.4 13.70 11.35 RGF19*DE20 24.5 FC/MC/PC60D 1325 40.0 29.0 14.20 12.00 RGF19*DE20 24.5 FC/MC62D 1325 39.0 28.4 13.70 11.35 RGF19*DE20 24.5 UC60D 1325 37.2 27.8 13.25 11.35 RGF19*CE16 21.0 FC/MC62D 1400 47.0 32.2 14.20 12.00 RGF19*CE16 21.0 FC/PC60C 1400 45.0 30.8 13.50 11.35 RGF19*CE16 21.0 FC64D 1400 48.0 32.6 14.50 12.50
RHP14J484S21
RGF19*CE20 21.0 FC/MC62D 1350 47.5 32.4 15.00 12.50 RGF19*CE20 21.0 FC64D 1350 48.0 33.0 15.10 12.50 RGF19*DE20 24.5 FC/MC/PC60D 1325 45.5 31.2 14.20 12.00 RGF19*DE20 24.5 FC/MC62D 1325 47.5 32.4 15.00 12.50 RGF19*DE20 24.5 FC64D 1325 48.0 33.0 15.10 12.50
1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.
2. High Efficiency Motor Furnaces have B.O.D (Blower on Delay) standard. Furnaces that are listed individually in the above table, such as the RGF1L*P, RGF19*P, and RGF1L*E use Coil Only Ratings.
COIL
MODEL
1
RATED
CFM
TOTAL SENS.
COOLING
NET MBH
2
SEER EER
COOLING CAPACITY - With High Efficiency Motor Furnaces
UNIT
MODEL
RGF19*CE20 21.0 FC/MC62D
RGF19*CE20 21.0 FC64D
RHP14J604S21
RGF19*DE20 24.5 FC/MC62D
RGF19*DE20 24.5 FC64D
1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.
2. High Efficiency Motor Furnaces have B.O.D (Blower on Delay) standard. Furnaces that are listed individually in the above table, such as the RGF1L*P, RGF19*P, and RGF1L*E use Coil Only Ratings.
6 Johnson Controls Unitary Products
FURNACE
MODEL WIDTH
14.5 SEER HP WITH HIGH EFFICIENCY MOTOR FURNACES
COIL
MODEL
1
STAGE
RATED
CFM
TOTAL SENS.
1 1085 46.0 29.4 2 1550 55.5 38.0 1 1085 48.0 30.6 2 1550 57.0 39.0 1 1085 46.0 29.4 2 1550 56.0 38.0 1 1070 48.0 30.6 2 1525 57.0 39.0
NET MBH
2
COOLING
SEER EER
14.20 11.80
14.50 12.00
14.20 12.00
14.50 12.00
810754-UTG-C-0214
HEATING CAPACITY - With Air Handler Coils
UNIT
MODEL*
AIR
HANDLER
COIL
MODEL
1
47F17F HSPF
HEATING
MBH COP KW MBH COP KW STD
14.5 SEER HP WITH AIR HANDLERS
RFCX24BE 18.0 3.82 1.38 11.0 2.50 1.29 8.20
RHP14J184S21
RFCX30BE 18.03.881.3610.92.541.268.50 RFCX24BP 18.0 3.56 1.52 11.4 2.34 1.43 7.75 RFCX24BE 22.23.681.7713.72.441.658.50
RHP14J244S21
RFCX30BE 22.23.681.7713.72.441.658.50 RFCX24BP 22.43.421.9213.92.301.777.75
RHP14J304S21
RFCX36CE 30.04.082.1520.42.622.289.00 RFCX36BP 30.03.762.4219.42.502.277.75 RFCX36CE 34.6 3.80 2.67 20.2 2.80 2.11 8.50 RFCX42DE 34.6 3.80 2.67 20.2 2.80 2.11 9.00
RHP14J364S21
RFCX48DE 33.83.742.6519.82.782.098.50 RFCX36BP 35.03.522.9120.82.582.368.20 RFCX42CP 34.83.562.8620.82.622.338.20 RFCX48DE 39.53.703.1325.42.662.809.00
RHP14J424S21
RFCX60DE 39.03.783.0225.42.682.788.50 RFCX48DP 40.53.523.3726.42.503.098.50 RFCX48DE 47.03.444.0028.82.443.468.20
RHP14J484S21
RFCX60DE 47.03.723.7030.42.623.409.00 RFCX48DP 48.03.224.3729.62.263.847.80
1. Rated CFM same as for cooling.
2. Heating MBH based on AHRI standards of 70 °F DB (Dry Bulb) entering indoor air, 72% RH (Relative Humidity) outdoor air with 25 feet of interconnecting piping and no supplemental electric heat operation.
COP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by the total electric power input during the same period. — = Not Applicable. MA Modular Air Handlers use Coil Only Ratings.
2
HEATING CAPACITY - With Air Handler Coils
UNIT
MODEL
AIR
HANDLER
COIL
MODEL
1
STAGE
RATED
CFM
HEATING
NET MBH
47 OD 17 OD
14.5 SEER HP WITH AIR HANDLERS
1116043.0– –3.36
RHP14J604S21 RFCX60DE
2 1835 58.0 40.0 9.00 3.70
2* 1160 55.0 39.5 8.85 3.00
1. Rated CFM same as for cooling.
2. Heating MBH based on AHRI standards of 70 °F DB (Dry Bulb) entering indoor air, 72% RH (Relative Humidity) outdoor air with 25 feet of interconnecting piping and no supplemental electric heat operation.
* Notates “Hot Heat Pump” performance. These ratings are not AHRI Listed. COP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by the total electric power input during the same period. — = Not Applicable. MA Modular Air Handlers use Coil Only Ratings.
2
HSPF COP @ 47
Johnson Controls Unitary Products 7
810754-UTG-C-0214
HEATING CAPACITY - Upflow, Downflow, and Horizontal Furnaces and Coils (Coil Only Ratings)
UNIT
MODEL*
COIL
MODEL
1
47 F 17 FHSPF
HEATING
MBH COP KW MBH COP KW STD
14.5 SEER HP COIL ONLY RATINGS
FC/MC/PC32 18.0 3.56 1.52 11.4 2.34 1.43 7.75
RHP14J184S21
FC/MC/PC35 18.0 3.52 1.56 11.3 2.34 1.45 7.70 FC/MC/PC37 18.0 3.62 1.50 11.3 2.40 1.38 7.75 FC/MC/PC43 18.0 3.62 1.50 11.3 2.40 1.38 7.75 FC/MC/PC32 22.83.401.9614.22.261.847.75
RHP14J244S21
FC/MC/PC35 22.63.381.9915.42.261.867.70 FC/MC/PC37 22.83.401.9614.22.261.847.75 FC/MC/PC43 22.83.401.9614.22.261.847.75
RHP14J304S21
FC/MC/PC37 30.03.722.4319.32.482.288.00 FC/MC/PC43 30.03.702.4319.42.582.228.00 FC/MC/PC37 35.03.522.9120.82.582.368.20 FC/MC/PC43 35.03.522.9120.82.582.368.20
RHP14J364S21
FC/MC/PC48 34.83.522.9020.82.602.348.20 FC/MC/PC60 35.43.642.8521.22.662.348.20
UC48 36.03.702.8521.42.662.367.80 UC60 36.03.682.8720.82.602.347.80
RHP14J424S21
FC/MC/PC60 40.53.523.3726.02.523.028.50
FC/MC62 40.03.543.3126.22.523.058.50
FC/MC/PC60 48.03.444.0929.62.383.647.80
RHP14J484S21
FC/MC62 48.03.763.7431.42.583.578.20
FC64 48.03.763.7431.62.603.568.20
1. Rated CFM same as for cooling.
2. Heating MBH based on AHRI standards of 70 °F DB (Dry Bulb) entering indoor air, 72% RH (Relative Humidity) outdoor air with 25 feet of interconnecting piping and no supplemental electric heat operation.
COP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by the total electric power input
during the same period. MA Modular Air Handlers use Coil Only Ratings. Furnaces that are listed individually in the above table, such as the RGF1L*P, RGF19*P, and RGF1L*E use Coil Only Ratings. — = Not Applicable.
2
HEATING CAPACITY - With Upflow, Downflow, & Horizontal Furnaces and Coils (Coil Only Ratings)
UNIT
MODEL*
RHP14J604S21 FC/MC62
1. Rated CFM same as for cooling.
2. Heating MBH based on AHRI standards of 70° DB (Dry Bulb) entering indoor air, 72% RH (Relative Humidity) outdoor air with 25 feet of interconnecting piping and no supplemental electric heat operation.
* Notates “Hot Heat Pump” performance. These ratings are not AHRI Listed. COP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by the total electric power input during the same period. MA Modular Air Handlers use Coil Only Ratings. Furnaces that are listed individually in the above table, such as the RGF1L*P, RGF19*P, and RGF1L*E use Coil Only Ratings. — = Not Applicable.
8 Johnson Controls Unitary Products
COIL
MODEL
1
2
HSPF COP @ 47
STAGE
RATED
CFM
HEATING
NET MBH
47 OD 17 OD
14.5 SEER HP COIL ONLY RATINGS
1 1350 43.5 3.42 2 1800 60 40.5 8.4 3.58
2* 1350 57 40.0 8.6 3.36