Johnson Controls R310A Series Catalog Page

R310A Series Current Sensing Switch
Code No. LIT-1900005 Issued November 13, 2015
R310A Series Current Sensing Switch
Description
The R310A replaces the R10A used with Johnson Controls/PENN® time delay oil failure cutout controls such as the P28, P45, and P445. These applications incorporate internal line breaking overload protection, where lockout due to overload cycling is unacceptable or undesirable. The R310A switch is not intended to detect breakage of belts.
The R310A is molded in a high dielectric material, which permits mounting inside a starter or contactor.
Refer to the R310A Series Current Sensing Switch Product Bulletin (LIT-121536) for important product application information.
Features
• small size allows mounting in small enclosure
• solid-state switching contains no moving parts to fail
• low 0.5 ampere activation allows monitoring of most small equipment circuit loads
• high 200 ampere monitoring capacity allows monitoring of heavy duty equipment
• large 0.70 in. (18 mm) diameter sensor hole accepts large diameter wire sizes and multiple coilings of smaller diameter wire sizes
Selection Chart
Product Code Number Description
R310AD-1C Current Sensing Switch
Voltage switching capacity: 0 to 30 VAC Used with: P445 Electronic Lube Oil Control
R310AE-2C Current Sensing Switch
Voltage switching capacity: 120 to 240 VAC Used with: P28 and P45 Electromechanical Lube Oil Controls
Applications
The R310A Current Sensing Switch is designed to sense alternating current in a conductor that passes through its opening. The R310A sensor closes an electronic switch if the alternating current in the conductor exceeds 0.5 amperes. Thus, the R310A switch may be used for several purposes:
• switch a pilot circuit
• energize a run signal on a device such as a fan, motor, or pump
• monitor motors and electrical loads for proper operation
• monitor on/off status of process motors
The R310A Series Current Sensing Switch is available in two models. The R310AD-1 switch is for use in low-voltage applications, such as with the P445 Electronic Lube Oil Control. The R310AE-2 switch is for use in high-voltage applications, such as with the P28 and P45 Electromechanical Lube Oil Controls.
The R310A switch avoids nuisance lockouts by sensing the lack of current flow to the motor. Regardless of the reason for motor shutdown, the lube oil control time delay circuit is de-energized when the current flow in the motor supply line drops below 0.5 amperes.
In a typical application, the lube oil control does not lock out when the control circuit shuts off the compressor. However, if the compressor overheats and the internal thermal overload circuits open, the compressor shuts itself down, which causes the oil pressure to drop. This drop in oil pressure will energize the lube oil control heater (P28, P45) or timer (P445), causing a
Technical Specifications
R310A Series Current Sensing Switch
Switch Action SPST, normally open Current Sensing
Range Switch Threshold R310AD-1C 0.5 Amperes
Sensor Supply Voltage Induced from monitored conductor,
Switching Capacity (General Purpose)
Output Polarity Non-polarity sensitive output Enclosure NEMA 1 Ambient Operating Conditions 5 to 140°F (-15 to 60°C);
Ambient Storage Conditions -40 to 158°F (-40 to 70°C);
Dimensions (H x W x D) 2.34 x 1.85 x 0.875 in.
Sensor Hole Size 7/10 in. (17 mm) Diameter Agency Listings UL Guide NRNT
nuisance lockout. In this situation, the R310 switch senses the lack of current to the motor, and is used to de-energize the time delay heater (P28, P45) or electronic timer (P445) before a nuisance lockout occurs.
Repair Information
If the R310A Series Current Sensing Switch fails to operate within its specifications, replace the unit. For a replacement switch, co ntact the nearest Johnson
R310AD-1C 0.5 to 200 Amperes R310AE-2C 0.75 to 200 Amperes
R310AE-2C 0.75 Amperes
R310AD-1C 0.1A at 30 VAC/DC R310AE-2C 0.5 at 250 VAC/DC
Controls®
isolation 600 VAC RMS
0 to 95% RH, noncondensing
0 to 95% RH
(59 x 46 x 22 mm)
cUL Guide NRNT7
representative.
The performance specifications are nomina l and conf orm to accep table industr y standar ds. For ap plications a t condition s beyond th ese specification s, consult the local Johnson Controls o ffice. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc.