System 450™ Series Modular Control Systems with Standard Control Modules Technical Bulletin3
System 450™ Series Modular Control Systems with Standard Control Modules Technical Bulletin4
System 450™ Series Modular Control Systems with
Standard Control Modules
Technical Bulletin
Document Introduction
This document describes System 450™ features and functions, and provides
guidelines and instructions for designing, selecting, installing, setting up, and
troubleshooting System 450 control systems that use System 450 standard control
modules or the System 450 control module with Hybrid Analog Output
(C450CBN-x, C450CCN-x, C450CPN-x, C450CQN-x, and C450CPW-100
models).
This document also provides information and instructions for selecting, installing,
and setting up sensors, expansion modules, and the power module in your control
systems with standard control modules or the hybrid analog control module.
This document also provides System 450 Technical Specifications on page 67 and
references to System 450 Related Documentation.
In this document, control module refers to the System 450 standard control
modules noted previously and the System 450 hybrid analog output control
module. Hybrid analog output refers only to the System 450 hybrid analog
output control module (C450CPW-100).
Note: For information regarding System 450 reset control modules
(C450RxN-x) and control systems that use reset control modules, refer to
the System 450 Series Modular Control Systems with Reset Control Modules Technical Bulletin (LIT-12011842).
Note: For information regarding System 450 control modules with network
communications, refer to the System 450 Series Modular Control Systems
with Communications Control Modules Technical Bulletin (LIT-12011826).
Related Documentation
T able 1 provides references to System 450 related documentation, including sensor
installation instructions.
Table 1: Related Documentation (Part 1 of 2)
For Information OnSee DocumentLIT or Part Number
System 450 Series Features, Benefits,
Models, and Technical Specifications
System 450 Series Features, Benefits,
Models, and Technical Specifications
Installing, Wiring, and Setting up
System 450 Control Modules with Relay
Output
Installing, Wiring, and Setting up
System 450 Control Modules with
Analog Output
System 450 Series Modular Control
Product Bulletin
System 450 Series Modular Control
Catalog Page
System 450 Series Control Modules with
Relay Outputs Installation Instructions
System 450™ Series Control Modules with
Analog Outputs Installation Instructions
LIT-12011458
LIT-1900549
Part No. 24-7664-2675
Part No. 24-7664-2853
System 450™ Series Modular Control Systems with Standard Control Modules Technical Bulletin5
Table 1: Related Documentation (Part 2 of 2)
For Information OnSee DocumentLIT or Part Number
Installing, Wiring, and Setting up
System 450 Control Modules with
Hybrid Analog Output and High Input
Signal Selection
Installing and Wiring System 450
Expansion Modules with Relay Output
Installing and Wiring System 450
Expansion Modules with Analog Output
Installing and Wiring the System 450
Power Module
Installing and Wiring the A99 Series
Temperature Sensors
Installing and Wiring the TE-6000 Series
Temperature Sensing Elements
Installing and Wiring the TE-6300P
Series Temperature Sensors
Installing and Wiring the TE-6300M
Series Well Insertion Temperature
Sensors
Installing and Wiring the TE-6300P
Series Outdoor Air Temperature
Sensors
Installing and Wiring the TE-6300V
Series Flange Mount Duct Averaging
Temperature Sensors
Installing and Wiring the TE-6300P
Series Wall Mount Temperature Sensors
Installing and Wiring the TE-6300M
Series Duct Averaging Temperature
Sensors
Installing and Wiring the TE-6300F
Series Flush Mount Sensors
Installing and Wiring the TE-6300A
Series Adjustable Length Duct Probe
Temperature Sensors
Installing and Wiring the TE-6300V
Series Flange Mount Duct Probe
Temperature Sensors
Installing and Wiring the TE-6300M
Series Duct Probe Temperature Sensors
Installing and Wiring the TE-6800 Series
Temperature Sensors
Installing and Wiring the P499 Series
Electronic Pressure Transducers
Installing and Wiring the HE-67xx
Humidity Sensors and Humidity with
Temperature Sensors
Installing and Wiring Setra Systems
Model 265 Differential Pressure
Transducers
System 450 Series Control Module with
Hybrid Analog Output and High Input
Signal Selection Installation Instructions
System 450 Series Expansion Modules
with Relay Outputs Installation Instructions
System 450 Series Expansion Modules
with Analog Outputs Installation
Instructions
System 450 Series Power Module
Installation Instructions
A99B Series Temperature Sensors
Product/Technical Bulletin
TE-6000 Series Temperature Sensing
Elements Installation Instructions
TE-6300P Series Temperature Sensors
Installation Instructions
TE-6300M Series Well Insertion
Temperature Sensors Installation
Instructions
TE-6300P Series Outdoor Air Temperature
Sensors Installation Instructions
TE-6300V Series Flange Mount Duct
Averaging Temperature Sensors
Installation Instructions
TE-6300P Series Wall Mount Temperature
Sensors Installation Instructions
TE-6300M Series Duct Averaging
Temperature Sensors Installation
Instructions
TE-6300F Series Flush Mount Sensors
Installation Instructions
TE-6300A Series Adjustable Length Duct
Probe Temperature Sensors Installation
Instructions
TE-6300V Series Flange Mount Duct
Probe Temperature Sensors Installation
Instructions
TE-6300M Series Duct Probe Temperature
Sensors Installation Instructions
TE-6800 Series Temperature Sensors
Installation Instructions
P499 Series Electronic Pressure
Transducers Product/Technical Bulletin
TrueRH Series HE-67xx Humidity Element
with Temperature Sensor Installation
Instructions
Setra Systems Model 265 Differential
Pressure Transducer Installation Guide
Part No. 24-7664-2802
Part No. 24-7664-2683
Part No. 24-7664-2799
Part No. 24-7664-2691
LIT-125186
Part No. 24-7664-1636
Part No. 24-4034-26
Part No. 24-4034-107
Part No. 24-4034-182
Part No. 24-4034-190
Part No. 24-4034-220
Part No. 24-4034-204
Part No. 24-4034-174
Part No. 24-4034-255
Part No. 24-4034-247
Part No. 24-4034-212
Part No. 24-4034-166
Part No. 24-10409-1
LIT-12011190
Part
No
. 24-7664-2659
Part No. 24-9527-7
Search QuickLIT
Product Information
website for Setra
System Model 265.
System 450™ Series Modular Control Systems with Standard Control Modules Technical Bulletin6
System 450 Overview
The System 450 Series is a family of compact digital electronic control, expansion,
and power modules that are easily assembled and set up to provide reliable on/off
and proportional control of temperature, pressure, and humidity conditions in a
wide variety of HVACR and commercial/industrial process applications.
The System 450 Series is designed to replace System 350 Series and System 27
Series control systems and provides more features and greater flexibility with far
fewer model variations. Most System 350 and System 27 modules are designed for
single condition applications (either temperature, pressure, or humidity) and
cannot be configured to control multiple conditions with a single control system.
Depending on the control module model used, a single System 450 control system
can monitor and control both temperature and humidity, or temperature, pressure,
and humidity simultaneously.
Note: System 450 modules are not compatible with System 350 or System 27
modules, but you can build all of the System 350 and System 27 control
systems and many more with System 450 modules, usually with fewer
modules.
The System 450 Series has several model variations; each module is designed to be
multi-purpose, adaptable, and completely field configurable for temperature,
pressure, and humidity applications. The System 450 Series allows you to build a
wide range of inexpensive, compact, durable, and versatile custom control systems
that allow you to monitor and control multiple control loops in your controlled
system. A System 450 control system can monitor temperature, pressure, and
humidity simultaneously and control up to ten outputs (analog outputs, relay
outputs, or both) based on the monitored conditions.
Note: System 450 communications control modules, System 450 standard
control modules, and the System 450 control module with hybrid analog
output can monitor and control temperature, pressure, and humidity
applications simultaneously. System 450 reset control modules can
monitor and control temperature and humidity applications simultaneously.
A System 450 standard control system includes:
•a single System 450 standard control module, which provides the control
system UI for setting up, monitoring, and controlling your system and the
sensor wiring terminals for connecting the sensors to your control system.
•one to ten outputs provided by the control module and expansion modules.
Each output provides either on/off control or a proportional analog signal
(0 to 10 VDC or 4 to 20 mA) to the equipment in your controlled system.
•one to three sensors or transducers, which are hard-wired directly to the control
module and provide input signals for monitoring and controlling your system
equipment.
•an optional power module to provide power to the connected control module
and expansion modules.
System 450™ Series Modular Control Systems with Standard Control Modules Technical Bulletin7
See Table 11 on page 62 for a list of System 450 modules that can be used in
Figure 1: System 450 Standard Control System Connected
as a Room Heating and Cooling Control System with
Condenser Fan Speed Control
* Connect cable shields
at only one point to any
“C” terminal on the
Input Terminal Block.
standard and hybrid analog output control systems. Refer to the System 450 Series
Modular Controls Product Bulletin (LIT-12011458) for a complete list and
description of the System 450 modules, compatible sensors and transducers, and
accessories.
Figure 1 shows an example System 450 standard control system connected as a
room heating and cooling control system with condenser fan speed control.
Figure 3 on page 12 shows the System 450 UI Main Screens, System Status
screens, and System Setup Screens for the heating and cooling control system
shown in Figure 1.
System 450™ Series Modular Control Systems with Standard Control Modules Technical Bulletin8
System 450 Standard Control Modules
A System 450 standard control system can provide the following types of control
to your application equipment:
•On/Off Control, including multi-stage control for temperature, pressure, and
humidity applications. (See Relay Outputs on page 18 for more information.)
•Proportional Analog Control, including multi-stage control for temperature,
pressure, and humidity applications. (See Analog Outputs on page 20 for more
information.)
•Combination of On/Off Relay and Analog Output Control, with up to 10
outputs per control system and any combination of relay and analog outputs.
•Multi-Stage Control (Relay or Analog) for temperature, pressure, and
humidity applications.
•Multi-Purpose Control, including simultaneous control of temperature,
pressure, and humidity conditions.
•Stand-Alone Control. A single standard control module can be quickly and
easily configured to replace a wide variety of specialized controls in the field.
•Direct and Reverse Action Proportional Control. See Direct and Reverse Control Actions for Analog Outputs on page 20 for more information.
•Proportional Plus Integral Control. See Proportional Plus Integral Control and Integration Constants on page 23 for more information.
•High Input Signal Selection allows you to monitor a condition with two or
three identical sensors at different locations in your controlled system and
control system outputs according to the highest condition value sensed by the
sensors. See High Input Signal Selection on page 24 for more information.
•Differential Control allows you to monitor and control a condition dif ferential
in a controlled system; for example, the water pressure drop across an in-line
water filter. See Differential Control on page 25 for more information.
•Hybrid Analog Output Control on C450CPW-100 control modules enables
an analog VDC output to transition to a pulse output at low signal levels,
providing more efficient low-speed control of Electronically Commutated
(EC) motors in condenser fan applications. (See Hybrid Analog Output on
page 14 for more information.)
Note: System 450 standard control modules do not include reset control,
real-time clock, setback scheduling control, or load balancing capabilities.
These features are available on the System 450 reset control modules only.
Refer to the System 450 Control Systems with Reset Control Modules T echnical Bulletin (LIT-12011842) for more information about reset control
modules and reset control systems. Only the C450CPW-100 model
provides a hybrid analog output for direct control of EC motors. See
Hybrid Analog Output
on page 14 for more information.
System 450™ Series Modular Control Systems with Standard Control Modules Technical Bulletin9
Control Modules and User Interface
Figure 2: System 450 Control Module with Analog Outputs Showing LCD and
Four-Button Touchpad User Interface
M
4
Output Number:
with the status or setup value shown
on the screen. Output numbers are
automatically determined by the outputs'
physical positions (left to right) in the
module assembly. (Here, 4 = Output 4.)
Control Ramp Icon:
Displays whether an
or reverse acting, and whether the output
signal strength is at minimum or maximum
when the sensed property is at Setpoint .
The control ramp icon displayed is
determined by the output's SP, EP, OSP,
and OEP setup values.
Menu Button:
Press to move through the
sensor and output setup start screens.
When moving through the status or setup
screens, press to return to the status start
screen or setup start screen.
M
M
Status or Setup Identifier:
or
OSP
Displays the
unit of measurement, output, sensor number,
setup parameter for the displayed stat us or
setup value. (Here, the setup identifier
represents % output signal strength at setpoint.)
Up and Down Buttons:
Press or to select
a different value for any flashing value in the
setup value field. In the Main (sensor status)
screens, press and hold both and for
5 seconds to access the Setup Start screens.
Status or Setup Value:
or
Displays the current
input status, output status setup parameter
value for the displayed input sensor, output
and/or setup parameter. select
a different parameter value when the value
is flashing. (Here, 100 = 100%.)
Press or to
Expansion Modules indicate if the associated
output is partially on (between 0 an 10V), the
LED blinks. The higher the output signal
strength, the longer the LED is on.
In the Main screens,
the (flashing) setup value and go to the
next setup screen.
Each System 450 standard control system requires a single control module.
System 450 control modules have an LCD that enables you to set up and monitor
your control system, along with a four-button touchpad for navigating the control
system status and setup screens, and setting up the system parameters. Figure 2
shows a standard control module and describes the various features of the
System 450 control system UI for standard control modules.
LED:
Green LEDs on Control Module and
relay or analog output is on or off. If the analog
100
value that identifies the output associated
Displays a numerical
OSP
analog output (only) is set as direct acting
FIG:sys450_comm_module_ui
Next Button:
press to scroll through the system status
screens. In a setup screen, press to save
Standard System 450 control modules are available with one or two relay outputs
or with one or two analog outputs and the standard System 450 firmware. See
Table 11 on page 62 for model descriptions and System 450 Standard Control Modules on page 9 for more information.
The System 450 control module with hybrid analog output has a single analog
output that can be configured as a hybrid analog output to optimize and extend the
controlled speed range of variable speed EC motors. See Hybrid Analog Output
page 14 for more information.
All System 450 control modules can control both relay outputs and analog outputs,
regardless of the type of outputs that the control module has onboard. You set up
all of the sensors and all of the outputs (relay and analog), including the expansion
module outputs, in the control module UI. A standard control module can also be
configured as a simple stand-alone control system when your application requires
only one or two relay outputs, or one or two analog outputs.
System 450™ Series Modular Control Systems with Standard Control Modules Technical Bulletin10
on
During normal operation, the LCD displays the Main System 450 screens (Sensor
Status screens), which automatically scroll through and display the status of the
hardwired and functional sensors in your control system. You can also view the
status of all the outputs in your control system and access the System Setup screens
from the Main screens in the System 450 UI. See on page 40 for more
information.
The System 450 System Status screens display the status of each output in the
control system (in addition to the sensor status screens). A relay output status is
displayed as On or OFF. See Relay Outputs on page 18 for more information. An
analog output status is displayed as a percentage of the total output signal strength
(0 to 100%). The analog output status screens also display an icon that indicates
the control action of the output. See Analog Outputs on page 20 for more
information.
The System Setup screens in the System 450 UI enable you to easily set up the
system sensors and all of the system outputs for your control system. See on page
40 for more detailed procedures for setting up your control system.
Figure 3 illustrates the System 450 UI navigation paths, parameter designations,
and values for the control system example (shown in Figure 1) using a System 450
standard control module. Figure 3 shows the Main screens (sensor status screens),
the System Status screens, the System Setup screens, and the Output Setup screens
for an example System 450 standard control application.
System 450™ Series Modular Control Systems with Standard Control Modules Technical Bulletin11
.
Figure 3: System 450 UI Menu Flow Chart Example Showing Navigation Paths and
Example Settings in the Main, System Status, Sensor Setup, and Output Setup Screens
for the Room Heating and Cooling Control System with Condenser Fan Speed Control
Application Shown in Figure 1
M
FIG:menu_flw_chrt
232
PSI
1
Main Screen
Sensor 2 Status
74
°F
2
Sensor 1 Status
Relay Output 2
Status
OFF
OUT
2
Output Relay
2
OFF
Relay Output 1
Status
OUT
1
Output Relay
1
On
Analog Output
Status
64
OUT
3
Output Signal
at % of Ran
64
Sensor 3
Statu s
– – – –
3
Sensor
Not Set Up
3
Sensor 2
Status
74ºF
2
at Sensor
74
232
PSI
1
Sensor 1
Status
232 psi
1
at Sensor
Sensor Setup
Screens
System Status
Screens
Main Screens
(Sensor Status)
Relay Output 1
Cooling
Equipment
Setup Screens
Press and hol d +
for 5 seconds to go to
the Setup St art screen s.
Press to scroll through
Sensor Status screens and
Output Status screens.
SENS
Sensor Type
Setup Start
Select Sensor 2
Type
°F
Sensor Type
(-40 to 250ºF)
ºF
Select Sensor 3
Typ e
No
Sensor Type
Selected
Select Se nsor 1
Typ e
P500
Sn-1
Sn-2Sn-3
Select
Temperature (only)
Offset De grees
-3
OFFS
2
During normal operation, the display automati
for all sensors set up in the UI.
After a 2 minute pause in any setup or status
Main (Sensor Status) screens.
Press in any Setup screen to go to the ass
Press + simultaneously in any Setup Sta
M
On
°F
2
Relay Output
Setu p Star t
OUTR
1
Sensor 2
1
Selected for
Relay Output
Relay
Output
1
Select Relay ON
Val ue
ON
1
78
Relay Output
at ºF
1
ON 78
OFF
1
Select Relay OFF
Val ue
Relay Output
at ºF
1
OFF 75
Select Minimum
Relay ON Time
ONT
1
0
Relay Output
Seconds
(Minimum)
1
ON 0
Se
R
OF
Select
Sensor
Sn-2
SENS
1
Up to ten
Outputs can
be connected
and set up.
M
OUTA
3
OutputAnalog
Setup Start
Analog
Output
3
M
Analog Output 3
Condenser
Fan Speed
Control
Setup Screens
M
Select
Sensor
SENS
3
Sensor 1
3
Selected for
Analog Output
Sn-1
Relay Output
Setup Start
OUTR
2
Sensor 2
2
Selected for
Relay Output
Relay
Output
2
Select Relay ON
Val ue
ON
2
Relay Output
at ºF
2
ON 65
OFF
2
Select Relay O
Val ue
Relay Outp
at
OFF 7
Selec t
Sensor
Sn-2
SENS
2
M
Relay Output 2
Heating
Equipmen t
Setup Screens
65
1
1
Sn-2
OFF
120
SENS
1
SNF
1
OFFT
2
Sensor (Sn-2)
1
Relay Output
1
elay Output
Edit
Input Sensor
set up and displayed.
three Sensors can be
Up to ten Outputs and
The current status of each sensor and output is displayed.
cally scrolls through the Sensor Status screens
ociated Setup Start screen.
rt screen to return to autoscrolling through the Main screen s.
screen (below), the display returns to autoscrolling through the
Main Screen
Press to manua lly scroll thr ough the sensor and output status es.
3
3
ge
Failure Mode
Select Sensor
lect MinimumRelay OFF Time
Controls
if
OFF
Seconds
F 120
Edit
Input Sensor
Relay Output
Failure Mode
Select Sensor
Sensor 2 Fails
(Minimum)
Select Minimum
Relay O FF Time
Relay ON Time
Select Minimum
FF
System 450™ Series Modular Control Systems with Standard Control Modules Technical Bulletin12
2
Sn-2
2
OFF
30
2
0
SENS
SNF
2
OFFT
ONT
2
Sensor (Sn-2)
2
Relay Output
2
Relay Output
2
Relay Output
2
ut
2
Controls Relay
if
OFF
Seconds
OFF 30
Seconds
ON 0
ºF
0
Sensor 2 Fails
(Minimum)
(Minimum)
Select % Output
Select % Output
Edit
Select Sensor
Select Integration
Signal Value
Signal Value
Select Prop. Band
Prop. Band
Select
Input Sensor
Failure Mode
Constant Value
at End Point
at Setpoint
End Po int Value
Setpoint Value
3
Sn-1
3
OFF
3
0
3
90
3
10
3
250
3
200
SENS
SNF
I-C
OEP
OSP
EP
SP
1
Controls
Sensor (Sn-1)
3
if
OFF
Analog Output
3
Integration
No
Analog Output
90
of Range at
Output is %
10
of Range at
Output is %
3
Prop. Band
Analog Output
3
Prop. Band
Analog Output
3
Analog Output
Sensor 1 Fails
Constant
Value
End Point
Value
Setpoint
250
End Point psi
200
Setpoint psi
Expansion Modules, Module Assemblies, and Outputs
Figure 4: System 450 Module Assembly Example Showing Standard Control
Module Positions, Output Positions, and Output Numbers
System 450 expansion modules provide additional outputs to expand your control
systems and meet your specific application requirements.
A System 450 control system can provide up to ten outputs, which can be any
combination of relay and analog outputs. Expansion modules are available with
one or two relay outputs, or with one or two analog outputs. See Table 11 on
page 62 for information on the System 450 modules that can be used in a standard
control system.
Module Assemblies, Output Types, and Output Numbers
You can easily plug System 450 modules together using the 6-pin connectors
located on the sides of the modules’ housings and mount these module assemblies
on standard 35 mm DIN rail (recommended) or directly to a hard, even surface.
See Mounting
on page 36 for more information.
Figure 4 shows a System 450 module assembly example, the module positions, the
output types, and the automatically assigned output numbers used in the System
Setup screens in the control module UI.
The control module is always mounted on the left side of the module assembly . If a
System 450 power module is used, the power module is always plugged into the
right side of the control module. If expansion modules are used, they can be
plugged into the assembly in any order on the right side of the power module (or
the right side of the control module, if a power module is not used in the
assembly). See Assembling System 450 Modules
on page 35 for more information.
System 450™ Series Modular Control Systems with Standard Control Modules Technical Bulletin13
Each time a System 450 module assembly is powered on, the control module polls
Figure 5: Pulse Signal with Pulse Level = 25% and Logical Output = 12.5%
all of the modules to identify output type (relay or analog) and then assigns an
output number (1 to 9 and 0 = 10) to each output, starting with the first output on
the first expansion module connected to the right of the control module (Figure 4).
Output numbers are displayed on the control module LCD to identify the output
you are viewing as you navigate the system status and setup screens in the
System 450 UI (Figure 2).
Hybrid Analog Output
The C450CPW-100 control module is designed for use with variable speed
Electronically Commutated (EC) fan motors on a wide variety of refrigeration and
HVAC condensing units.
The C450CPW-100 module has a single onboard analog output that can be
configured as a hybrid analog output to optimize and extend the controlled speed
range of variable speed EC motors. The onboard analog output can also be set up
for High Input Signal Selection, which enables precise and efficient EC motor
speed control on multi-circuit condensing units.
Hybrid analog output control enables the C450CPW-100 control module’s hybrid
analog output to transition between a pulse output and a standard VDC output,
depending on the sensor value relative to the proportional band. At low output
levels, the pulse output signal provides an average motor speed that is less than the
EC motor’s fixed minimum speed (Figure 5).
Note: Only Analog Output 1 (OUT A1) on the C450CPW-100 control module can
be configured as a hybrid analog output and use the High Input Signal
Selection feature. These features are not available for any of the other
outputs in control systems that use a C450CPW-100 control module.
System 450™ Series Modular Control Systems with Standard Control Modules Technical Bulletin14
System 450 Compatible Sensors and Transducers
System 450 standard control modules are designed to operate with a variety of
compatible sensors and transducers. The System 450 compatible sensors and
transducers cover a wide range of temperature, pressure, and humidity conditions.
Note: System 450 compatible sensors consist of temperature sensors, humidity
sensors, and pressure transducers. The term sensor refers to all System 450
compatible input devices including transducers, unless noted otherwise.
System 450 compatible sensors also come in a variety of styles and configurations,
allowing you to select the sensor or transducer that best fits your control system
requirements. See Table 11 through Table 20 in Repair and Ordering Information
on page 62 for more information on System 450 compatible sensors.
You can connect up to three sensors to a System 450 control module at the
low-voltage terminal block. See Wiring System 450 Components on page 37 for
more information on System 450 sensor wiring terminals on control modules.
Refer to the System 450 module installation instructions and the sensor installation
instructions referenced in Related Documentation on page 5 for information on
installing, wiring, operating, troubleshooting, and replacing System 450
compatible sensors.
For each sensor in your control system, you must select the sensor’s corresponding
Sensor Type when you set up the sensors in the System 450 UI. A sensor’s
corresponding Sensor Type determines the controlled condition, unit of
measurement, minimum differential, setup values, and ranges for each output that
is set up to reference the sensor.
See Table 2 on page 16 for information about Sensor Types, the corresponding
output setup values and ranges, sensor models, and transducer models used in
standard System 450 control systems.
System 450 automatically designates the sensor connected to the Sn1 terminal and
a common (C) terminal as the Sn-1 sensor in the UI. The sensor connected to the
Sn2 and a C terminal is designated Sn-2, and the sensor connected to Sn3 and a C
terminal is designated Sn-3. You set up each sensor in the corresponding sensor
setup screens in the UI.
Note: For a System 450 control system to operate properly, you must wire the
correct sensor or transducer model to the correct sensor input terminals on
the control module and select the correct Sensor Type in the corresponding
Select Sensor Type screen in the System 450 UI. You must also set the
active/passive sensor jumpers or switches on the control module correctly
for each sensor or transducer connected to your control system.
See on page 40 and Setting Up the Sensors and Transducers
on page 45 for more
information and procedures on setting up sensors and Sensor Types in the System
450 UI. See Active and Passive Sensors on page 17 for information on setting the
active/passive switches and jumpers.
System 450™ Series Modular Control Systems with Standard Control Modules Technical Bulletin15
System 450 Sensors and Transducers for Standard Control Modules
Table 2 shows the Sensor Types, output setup values, value ranges, and product
types for the temperature sensors, humidity sensors, and pressure transducers that
are compatible with the C450CxN-x standard control module models.
Table 2: System 450 Sensor Types, Setup Values, and Sensor/Transducer
Product Codes
Sensor
Typ e
FF (Temperature/degrees)-46 to 255-40 to 25011A99B-xxx
CC (Temperature/degrees)-43 to 124-40 to 1210.50.5A99B-xxx
rH% (Humidity/%RH)1 to 100 10 to 95 12HE-67Sx-xxxxx
P 0.5INWC (Pressure/in. W.C.)0 to 0.5 0.025 to 0.50.005 0.025DPT2650-0R5D-AB
P 2.5INWC (Pressure/in. W.C.)0 to 2.5 0.1 to 2.50.02 0.1DPT2650-2R5D-AB
P 5INWC (Pressure/in. W.C.)0 to 5.0 0.25 to 5.00.05 0.25DPT2650-005D-AB
P 8bAR (Pressure/bar)-1 to 8-1 to 80.050.1 P499Rxx-401C
P 10INWC (Pressure/in. W.C.)0 to 100.5 to 10 0.050.2DPT2650-10D-AB
P 15bAR (Pressure/bar)-1 to 15-1 to 150.1 0.2P499Rxx-402C
P 30bAR (Pressure/bar)0 to 300 to 300.10.4P499Rxx-404C
P 50bAR (Pressure/bar)0 to 500 to 500.20.4 P499Rxx-405C
P 100PSI (Pressure/psi)0 to 1000 to 1000.51 P499Rxx-101C
P 110
P 200PSI (Pressure/psi)0 to 200 0 to 20011P499Rxx-102C
P 500PSI (Pressure/psi)0 to 500 90 to 5001 5 P499Rxx-105C
P 750PSI (Pressure/psi)0 to 750 150 to 7502 6 P499Rxx-107C
HIFF (Temperature/degrees)-50 to 340
HICC (Temperature/degrees)-45.5 to
Unit of Measurement
Value
(Condition/Units)
3
Hg/PSI (Pressure/Hg-psi)-10 to 100
Effective
Sensing
Range
(20 inHg to
100 psi)
170
Range of
Usable
1
Values
-10 to 1000.51 P499Rxx-100C
-40 to 340
-40 to 170
Resolution
Increment
Val ue
4
11TE-631x, TE-6000-x
4
0.50.5TE-631x, TE-6000-x
Minimum
Proportional
or Control
Band
Sensor Product
Type Number
HE-67Nx-xxxxx
HE-68Nx-0N00WS
TE-68NT-0N00S
TE-68NT-0N00S
2
1.Because of the way that the System 450 Differential Sensor (Sn-d) is set up and calculated with two identical sensors
(Sn-1 and Sn-2), the Range of Usable Values is twice as large as a single sensor. See Table 5 on page 26 for the
Range of Usable Values when an output references Sn-d.
2.See Repair and Ordering Information on page 62 (Table 12 through Table 20) for additional ordering information for
System 450 compatible sensors and transducers.
3.See Active and Passive Sensors on page 17 for information on setting up System 450 outputs that reference the P 110
Sensor Type.
4.Many of the temperature sensors that can be set up as HI°F or HI°C Sensor Types are not designed for use across the
entire Range of Usable Values for HI°F and HI°C Sensor Types. Refer to the Technical Specifications for the sensor
you intend to use to determine the condition range that the sensor is specified to be mounted and operate in.
System 450™ Series Modular Control Systems with Standard Control Modules Technical Bulletin16
Active and Passive Sensors
Figure 6: Example Showing the Active/Passive Slide Switch Settings
on a Control Module with Analog Outputs
Figure 7: Example Showing the Active/Passive Jumper Positions
on a Control Module with Relay Outputs
Each sensor/transducer hardwired to a System 450 control system is either an
active or passive sensor. Passive System 450 sensors are two-wire temperature
sensors that connect to one of the sensor input terminals and a common terminal
(C) only. Active sensors are three-wire humidity sensors and pressure transducers
that connect to one of the sensor input terminals, a common terminal, and a voltage
supply terminal (24V or 5V). The sensors and transducers have the following
requirements:
•Temperature sensors do not require a power source.
•Humidity sensors and differential air pressure transducers require 24 VAC
supply power and must be connected to the 24V terminal on the input terminal
block.
•P499 pressure transducers require a 5 VDC power source and must be
connected to the 5V terminal on the input terminal block.
On control modules with analog outputs, set the active/passive switches to ON for
passive temperature sensors and off for active humidity sensors.
On control modules with relay outputs, position the active/passive jumpers across
both pin terminals for passive temperature sensors and on one terminal for active
humidity and pressure sensors.
See System 450 Standard Control System Examples on page 27 for System 450
control system examples showing active/passive sensor jumper or switch settings.
System 450™ Series Modular Control Systems with Standard Control Modules Technical Bulletin17
System 450 Functional Sensors
System 450 control modules also enable several functional sensors based on the
input from one or more of the hard-wired sensors in your control system. Selecting
a functional sensor for an output on a System 450 standard control system enables
the differential or high signal selection control feature on the output.
Beginning with firmware Version 2.00, System 450 standard control modules
provide for three additional functional sensors:
•When Sn-1 and Sn-2 are set up as the same Sensor T ype, the High Input Signal
Selection functional sensor (HI-2) and Differential Control functional sensor
(Sn-d) are enabled and available in the Sensor Selection screens for each
output in the control system.
•When Sn-1, Sn-2, and Sn-3 are the same Sensor Type, the High Input Signal
Selection functional sensor (HI-3) is also enabled and available.
See High Input Signal Selection on page 24 and Differ ential Contr ol on page 25 for
more information about these functional sensors and system control features.
Relay Outputs
Relay outputs provide low and line-voltage on/off control for devices and
equipment in your controlled systems. Each relay output is a Single-Pole,
Double-Throw (SPDT) set of dry contacts. See Figure 15 on page 38.
Note: System 450 output relays are SPDT dry contact relays only and do not
provide any power source for your controlled equipment.
Selecting an ON value that is less than the OFF value (ON < OFF) turns the relay
on when the sensed condition value decreases, which is the typical heating mode in
temperature applications and referred to as reverse acting on/off control.
Selecting an ON value that is greater than the OFF value (ON > OFF) turns the
relay on when the sensed condition value increases, which is the typical cooling
mode in temperature applications and referred to as direct acting on/off control.
You can set up multiple relay outputs to create a variety of equipment staging
control systems. See Wiring System 450 Components
on page 37 for information
on wiring output relays. See Technical Specifications on page 67 for the relay
output electrical ratings.
A green LED on the relay control and relay expansion module housings (Figure 2)
indicates the relay output status.
When a relay output is On:
•the corresponding green LED on the module housing is lit
•the LNO (Line Normally Open) relay contact is closed
•the LNC (Line Normally Closed) relay contact is open
•the corresponding Output Status screen in the UI displays On
When a relay output is Off:
•the corresponding green LED on the module housing is not lit
System 450™ Series Modular Control Systems with Standard Control Modules Technical Bulletin18
•the LNO relay contact is open
Relay State
Relay On
Relay Off
Sensed Condition
OFF
Condition
Value
Direct Acting Relay
OFF < ON
ON
Condition
Value
Relay State
Relay On
Relay Off
Sensed Condition
ON
Condition
Value
OFF
Condition
Value
Reverse Acting Relay
ON < OFF
•the LNC relay contact is closed
•the corresponding Output Status screen in the UI displays OFF
System 450 control and expansion modules are available with one or two relay
outputs. See T able 11 on page 62 and Technical Specifications on page 67 for more
information about the System 450 Series module models used to build standard
control systems.
A relay output’s control action is determined by the values that you select in the
ON and OFF relay output setup screens:
•Relay ON values (ON) are the values at which the relay turns On.
•Relay Off values (OFF) are the values at which the relay turns Off.
Table 3 illustrates direct and reverse relay actions. When you select On/Off
condition values where OFF is less than On, the output relay is a direct acting
relay . When you select condition values where On is less than Of f, the output relay
is a reverse acting relay.
Table 3: System 450 Output Relay Control Actions and the Relationship
Between ON and OFF Values
Control ActionSet the Relay Output ON/OFF Value
Relationships for the Desired Control
Action
OFF < ON
ON < OFF
In temperature applications, direct acting relays are often used to control cooling
equipment, while reverse acting relays are often used to control heating equipment.
System 450™ Series Modular Control Systems with Standard Control Modules Technical Bulletin19
In pressure applications, directing acting relays are often used for condenser fan
cycling control or pump-down control, while reverse acting relay may be used for
high pressure cut-out.
In humidity applications, direct acting relays often control dehumidification
equipment, and reverse acting relay often control humidification equipment.
Analog Outputs
Analog outputs provide proportional analog signals for devices and equipment in
your controlled systems. Each analog output can generate either a 4 to 20 mA or
0 to 10 VDC signal. The output signal type is self-selecting; after you connect the
analog output to the controlled equipment, the output detects the analog input on
the controlled equipment and generates the appropriate analog signal for the
connected input.
You can set up an analog output to generate a direct acting or reverse acting
proportional output signal. You can also set up the output signal strength to
increase or decrease in either the direct acting or reverse acting mode. See Direct and Reverse Control Actions for Analog Outputs on page 20 for more information.
System 450 also provides six integration constants that allow you to set up a
proportional plus integral control signal, which can provide more precise setpoint
control. See Proportional Plus Integral Contr ol and Integration Constants on page
23 for information on determining the integration constant for an analog output.
For procedures on setting up analog outputs on standard control modules, see
Setting up an Analog Output on page 50.
System 450 control and expansion modules are available with one or two analog
outputs. See T able 11 on page 62 and Technical Specifications on page 67 for more
information about the System 450 Series module models that are used to build
standard control systems.
Direct and Reverse Control Actions for Analog Outputs
An analog output can be set up to provide one of four different control actions,
which allow you to match the output signal to the requirements of your control
system and the controlled equipment. The proportional output signal can provide
direct acting or reverse acting control. In addition, the output signal can be set up
to generate either the minimum or the maximum output signal strength at Setpoint.
A control ramp icon is displayed on the status screens for all analog outputs in your
control system. See Figure 2 on page 10. The displayed control ramp icon
represents the control action of the analog output signal. See Table 4 on page 22
for more information on analog output control actions and control ramp icons.
An analog output’s control action and the corresponding control ramp are
automatically determined by the values that you select in four analog output setup
screens:
•Setpoint value (SP) is the target value that the control system drives toward,
and along with the End Point, defines the output’s proportional band.
System 450™ Series Modular Control Systems with Standard Control Modules Technical Bulletin20
•End Point value (EP) is the maximum deviation from the target value
(Setpoint). The control system applies maximum output at the EP to drive the
process back toward the SP. The SP and EP define the analog output’s
proportional band.
•Output at Setpoint value (OSP) is the signal strength level of the analog
output when the input sensor is at Setpoint (SP). The OSP is expressed as a
percentage (0 to 100%) of the full scale output.
•Output at Endpoint value (OEP) is the signal strength level of the analog
output when the input sensor is at the End Point (EP). The OEP is expressed as
a percentage (0 to 100%) of the full scale output.
Note: System 450 analog outputs that reference the differential control sensor
(Sn-d) use a Differential Setpoint (dSP) and Differential End Point (dEP) to
define the output’s proportional band. See Differential Control on page 25
for more information.
System 450™ Series Modular Control Systems with Standard Control Modules Technical Bulletin21
Table 4 shows the four control ramp icons and describes their corresponding
P
r
o
p
o
r
t
i
o
n
B
a
n
d
OEP=100%
OSP=0%
F
F
P
r
o
p
o
r
t
i
o
n
a
l
B
a
n
d
OEP=100%
OSP=0%
OSP=10 0%
OEP=0%
EP=60°F
OSP=10 0%
OEP=0%
P
r
o
p
o
r
t
i
o
n
a
l
B
a
n
d
control actions and the setup value relationships required to configure the four
control actions. See Figure 23 and Figure 24 on page 52 for examples.
Table 4: System 450 Control Ramps, Analog Output Control Actions, and
System Setup Value Relationships
Control Ramp
Displayed
Control ActionSet the Analog Output Value Relationships
for the Desired Control Action and
Corresponding Control Ramp
SP < EP
Output Minimum at SP
SP=50°
l
a
EP=60°
OSP < OEP
SP > EP
Output Minimum at SP
EP=50°FSP=60°F
OSP < OEP
SP > EP
OSP > OEP
Output Maximum at SP
EP=50°FSP=60°F
l
a
n
o
i
t
r
d
o
n
p
a
o
r
B
P
SP < EP
Output Maximum at SP
System 450™ Series Modular Control Systems with Standard Control Modules Technical Bulletin22
OSP > OEP
SP=50°F
Proportional Plus Integral Control and Integration Constants
Figure 8: Proportional Only Control Versus Proportional Plus Integral Control
to bring the system condition to
Control point and output
follows the system load.
Humidity,
Pressure, or
Temperature
Offset Error
Zero
Offset
Error
In addition to standard proportional control, System 450 provides Proportional
plus Integral (PI) control capability. The addition of integral control enables a
properly set up analog output to drive a controlled condition closer to Setpoint
(Figure 8).
Standard proportional-only controls continuously adjust the output in proportion
to the difference (offset error) between the Setpoint value and the sensor value. As
the load on the system increases, the offset error increases. A proportional-only
control responds to the increased offset error by changing the output signal, which
drives the controlled equipment to compensate for the load change (Figure 8).
Proportional-only control loops are relatively easy to set up and adjust.
T ypically, under constant system load, proportional-only control loops do not drive
a system to the selected Setpoint. Instead, the controlled system is maintained at a
control point within the proportional band (throttling range) between setpoint and
end point. The larger the load on the system, the further the control point drifts
from setpoint. Still, for many applications, proportional-only control is the best
choice for analog output control.
Proportional Only Control
End Point
Humidity,
Pressure, or
Temperature
Integral control adjusts the o utput
Setpoint regardless of system load.
Offset Error
End Point
Proportional plus Integral (PI) control incorporates a time-integral control action
with proportional control action and, if properly set up, a PI control loop can
effectively eliminate offset error and enable a controlled system to drive to setpoint
even under large constant loads (Figure 8). On a properly sized system with
predictable loads, PI control can maintain the controlled system very close to
setpoint.
PONLY-PRO+I
A system’s output capacity, the size of the load on the system, and the integration
constant selected determine the speed (recovery rate) at which the PI control drives
the system to setpoint.
System 450™ Series Modular Control Systems with Standard Control Modules Technical Bulletin23
The integration constant establishes the rate at which the control readjusts the
analog output signal. The faster the integration constant, the faster the control
readjusts the output signal and the faster the recovery rate of a properly sized and
setup control loop.
Note: PI control is not suitable for all controlled systems. Improperly applied PI
control loops are unstable and can overshoot setpoint, resulting in control
loop oscillation. Also, with PI control, the proportional band (throttling
range) and the integration constant are interdependent and you must
properly set up these values in relation to each other. You must also
properly size the system equipment to handle the maximum load. Close
observation over several cycles and under different load conditions is
required to properly set up a PI control loop. On a properly sized system, a
PI control loop can drive the system condition much closer to setpoint than
proportional-only control.
In addition to a proportional-only setting, System 450 provides six time-integral
settings in the Integration Constant Setup screen for matching the analog
signal’s response rate to the controlled system’s recovery rate. The seven
integration constant settings are shown in Table 8 on page 60.
See Determining the Integration Constant for an Analog Output on page 56 for
more information and the procedures for determining an integration constant and
testing a PI control loop in your controlled system.
High Input Signal Selection
Standard System 450 control modules, including the C450CPW -100 hybrid analog
control module, include the High Input Signal Selection control feature.
The High Input Signal Selection feature enables a System 450 control system to
monitor a condition (temperature, pressure, or humidity) with two or three sensors
(of the same type) and control relay and analog outputs based on the highest
condition value sensed by the two or three referenced sensors.
When Sn-1 and Sn-2 are set up with the same Sensor Type, the functional High
Input Signal Selection sensor (HI-2) is available for selection when you set up the
outputs in the control system. When Sn-1, Sn-2, and Sn-3 are set up with the same
Sensor Type, the functional sensor (HI-3) is also available for selection.
Note: High Input Signal Selection is available on standard System 450 control
modules beginning with firmware Version 2.00 and on the hybrid analog
control module (C450CPW-100). On the hybrid analog control module,
High Input Signal Selection is only available for the hybrid analog output
(OUTA1).
Note: Setting up Sn-1 and Sn-2 as the same Sensor Types also enables the
functional Differential Control sensor (Sn-d). See Differential Control
page 25 for more information.
on
High Input Signal Selection control application examples include:
•fan-staging control on multi-circuit condensing units
System 450™ Series Modular Control Systems with Standard Control Modules Technical Bulletin24
•fan motor speed control on multi-circuit condensing units
The Hybrid Analog and High Input Signal Selection Control System Example on
page 32 provides module assembly, wiring, and UI setup information for a
System 450 hybrid analog output control system that uses the High Input Signal
Selection feature.
Differential Control
Standard System 450 control modules include the Differential Control feature.
The Differential Control feature enables a System 450 control system to monitor
and maintain a temperature, pressure, or humidity dif ferential between two sensors
of the same type and control relay and/or analog outputs based on the sensed
differential value relative to user-selected differential values.
Note: Differential Control is available on standard System 450 control modules
beginning with firmware Version 2.00. Differential Control is not available
on the hybrid analog control module (C450CPW-100).
Differential Control application examples include:
•solar heating systems
•pump pressure-drop monitoring and control
•fluid filter pressure-drop monitoring
•air filter pressure-drop monitoring
Setting up an output (relay or analog) for Differential Control requires connecting
two identical sensors to input terminals Sn1 and Sn2 and selecting the same Sensor
Type in the System 450 UI for Sensor 1 (Sn-1) and Sensor 2 (Sn-2). The
System 450 control system recognizes the same Sensor Types and makes the
functional Differential Control sensor (Sn-d) available for selection when you set
up each of the control system outputs.
Note: Setting up Sn-1 and Sn-2 as the same Sensor Types also enables the
functional High Input Signal Selection sensor (HI-2). See High Input Signal Selection on page 24 for more information.
When a Differential Control sensor (Sn-d) is set up, the differential sensor value is
a calculated value; (Sn-d) = (Sn-1) minus (Sn-2). The Differential Control sensor
(Sn-d) value is always equal to Sn-1 minus Sn-2. Therefore, depending on the
intended control action of the output, the differential value may be either a positive
or negative value.
The sensed differential value (Sn-d) between Sn-1 and Sn-2 is displayed in the
System Status screens as either a temperature differential value (dIFT), pressure
differential value (dIFP), or humidity differential value (dIFH). The unit of
measurement associated with the displayed differential value is determined by the
Sn-1 and Sn-2 Sensor Type. See Table 2 on page 16 for Sensor Types and their
units of measurement.
System 450™ Series Modular Control Systems with Standard Control Modules Technical Bulletin25
When a relay output is set up for Differential Control, System 450 compares the
sensed differential value, Sn-d (Sn-d = Sn-1 minus Sn-2), to the user-selected
differential values (dON and dOFF) to control the relay’s On/Off state.
When an analog output is set up for Differential Control, System 450 compares the
sensed differential value, Sn-d (Sn-d = Sn-1 minus Sn-2), to the user-selected
differential values (dSP and dEP) to control the analog output signal strength.
The Solar Heating Contr ol System Example Using Differential Control on page 28
provides module assembly, wiring, and UI setup information for a standard
System 450 control system that uses the Differential Control feature.
Note: Because of the way that the System 450 Differential Sensor (Sn-d) is set up
and calculated using two sensors with identical Sensor T ypes, the Range of
Usable Values for each Sensor Type is twice as large as a single sensor.
(Each Sensor Type has an equal number of positive and negative values on
outputs that reference Sn-d.) See Table 5 for a Sensor Type’s Range of
Usable Values when an output references Sn-d.
Table 5: Range of Usable Values for Sensor Types in Differential Control
Applications
Sensor TypeSn-d Range of Usable
Values
F-290 to 290P 30-30.0 to 30.0
C-161.0 to 161.0P 50-50.0 to 50.0
rH-95 to 95P 100-100.0 to 100.0
P 0.5-0.500 to 0.500P 110-110.0 to 110.0
P 2.5-2.50 to 2.50P 200-200 to 200
P 5-5.00 to 5.00P 500-500 to 500
P 8-9.00 to 9.00P 750-750 to 750
P 10-10.00 to 10.00HIF-380 to 380
P 15-16.0 to 16.0 HIC-210.0 to 210.0
Sensor TypeSn-d Range of Usable
Values
Sensor Failure Mode
System 450 allows you to select the mode of operation for your control system
outputs in the event of a sensor (or sensor wiring) failure of the sensor or sensors
that the outputs reference. When you set up an output in the System 450 UI, you
must select a sensor failure mode of operation in the Sensor Failure Mode (SNF)
screen. Your selection determines how an output responds if a referenced sensor or
sensor wiring fails.
System 450 outputs can be set up to directly reference a single compatible sensor
hardwired to the control system (Sn-1, Sn-2, or Sn-3). Outputs in control systems
with System 450 standard control modules can also be set up to reference several
functional sensors (Sn-d, HI-2, or HI-3). The functional sensors reference input
from one or more of the hard-wired sensors; thus one or more of the hard-wired
sensors can influence the outputs that reference functional sensors.
System 450™ Series Modular Control Systems with Standard Control Modules Technical Bulletin26
Loading...
+ 58 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.