These are electric cooling/gas heating units designed for outdoor installation. Only gas piping, electric power and duct connections are
required at the point of installation.
The gas-fired heaters have spark ignition.
The refrigerant system is fully charged with R-410A Refrigerant, and is
tested and factory sealed.
SECTION II: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to
alert against unsafe practices and hazards involving only property damage.
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or maintenance
can cause injury or property damage. Failure to carefully read and
follow all instructions in this manual can result in furnace malfunction, death, personal injury and/or property damage. Only a
qualified contractor, installer or service agency should install this
product.
!
CAUTION
This product must be installed in strict compliance with the installation instructions and any applicable local, state, and national codes
including, but not limited to building, electrical, and mechanical
codes.
Johnson Controls Unitary Products1183746-UIM-D-1015
1183746-UIM-D-1015
!
WARNING
Before performing service or maintenance operations on unit, turn off
main power switch to unit. Electrical shock could cause personal
injury. Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual.
For assistance or additional information consult a qualified installer,
service agency or the gas supplier.
!
CAUTION
This system uses R-410A Refrigerant which operates at higher pressures than R-22. No other refrigerant may be used in this system.
Gage sets, hoses, refrigerant containers and recovery systems must
be designed to handle R-410A. If you are unsure, consult the equipment manufacturer. Failure to use R-410A compatible servicing
equipment may result in property damage or injury.
!
WARNING
If the information in this manual is not followed exactly, a fire or
explosion may result causing property damage, personal injury or
loss of life.
Do not store or use gasoline or other flammable vapors and liquids in
the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
1. Do not try to light any appliance.
2. Do not touch any electrical switch; do not use any phone in
your building.
3. Immediately call your gas supplier from a neighbor’s phone.
Follow the gas supplier’s instructions.
4. If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer,
service agency or the gas supplier.
Due to system pressure, moving parts, and electrical components,
installation and servicing of air conditioning equipment can be hazardous. Only qualified, trained service personnel should install, repair, or
service this equipment. Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters.
Observe all precautions in the literature, labels, and tags accompanying
the equipment whenever working on air conditioning equipment. Be
sure to follow all other applicable safety precautions and codes including ANSI Z223.1 or CSA-B149.1- latest edition.
Wear safety glasses and work gloves. Use quenching cloth and have a
fire extinguisher available during brazing operations.
SECTION III: MODEL NUMBER NOMENCLATURE
PCG4A24502X1A
123456789
1. Model Family
PCG - packaged A/C with gas heat,
PHG - packaged heat pump with gas heat,
PCE - packaged A/C with electric heat,
PHE - packaged heat pump with electric heat
4. Nominal Air Conditioning Cooling Capacity BTUx1000
24 = 24,000 BTU, etc.
Examples:
PCG4B421002X1A is a packaged A/C with gas heat, 14 SEER, 3-1/2 ton, large cabinet, single-stage heat, 100,000 BTU gas heat, 230 volt, single
phase, low-NOx model (first generation, first release)
SECTION IV: INSTALLATION
INSTALLATION SAFETY INFORMATION
Read these instructions before continuing this appliance installation.
This is an outdoor combination heating and cooling unit. The installer
must assure that these instructions are made available to the consumer
with instructions to retain them for future reference.
1. Refer to the unit rating plate for the approved type of gas for this
product.
2. Install this unit only in a location and position as specified on Page
4 of these instructions.
3. Never test for gas leaks with an open flame. Use commercially
available soap solution made specifically for the detection of leaks
when checking all connections, as specified on Page 10 of these
instructions.
5. Gas Heating Input BTU/Hr x 1000
050 = 50,000 BTU/Hr. input, blank = electric heat
6. Voltage-Phase-Frequency
2 = 208/230-1-60, 3=208/230-3-60, 4 = 460-3-60
7. NOx Approval
X = low-NOx, blank = not low-Nox
8. Generation Level
1 = first generation
9. Revision Level
A = original release, B = second release
4. Always install unit to operate within the unit's intended temperaturerise range with the duct system and within the allowable external
static pressure range, as specified on the unit name/rating plate,
specified in Table 6 of these instructions.
5. This equipment is not to be used for temporary heating of buildings
or structures under construction.
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warning exactly could result in serious
injury, death or property damage.
Never test for gas leaks with an open flame. use a commercially
available soap solution made specifically for the detection of leaks to
check all connections. A fire or explosion may result causing property
damage, personal injury or loss of life.
2Johnson Controls Unitary Products
1183746-UIM-D-1015
LIMITATIONS
These units must be installed in accordance with the following:
In U.S.A.:
1. National Electrical Code, ANSI/NFPA No. 70 - Latest Edition
2. National Fuel Gas Code, ANSI Z223.1 - Latest Edition
3. Gas-Fired Central Furnace Standard, ANSI Z21.47a. - Latest Edition
4. Local building codes, and
5. Local gas utility requirements
In Canada:
1. Canadian Electrical Code, CSA C22.1
2. Installation Codes, CSA - B149.1.
3. Local plumbing and waste water codes, and
4. Other applicable local codes.
Refer to unit application data found in this document.
After installation, gas fired units must be adjusted to obtain a temperature
rise within the range specified on the unit rating plate.
If components are to be added to a unit to meet local codes, they are to
be installed at the dealer’s and/or customer’s expense.
Size of unit for proposed installation should be based on heat loss/heat
gain calculation made according to the methods of Air Conditioning
Contractors of America (ACCA).
This furnace is not to be used for temporary heating of buildings or
structures under construction.
FAN MOTOR
OUTDOOR FAN
COIL GUARD PANEL
OUTDOOR COIL
(Behind Panel)
BLOWER MOTOR
TXV
INDOOR COIL
INDOOR BLOWER
COMPRESSOR
REMOVABLE
BASE RAILS
FIGURE 1: Component Location
Table 1: Unit Limitations
Use the following guidelines to select a suitable location for these units:
1. Unit is designed for
2. Condenser coils must have an unlimited supply of air. Where a
choice of location is possible, position the unit on either north or
east side of building.
3. Suitable for mounting on roof curb.
Do not attach supply and return duct work to the bottom of the unit
base pan as the drain pan could be compromised.
4. For ground level installation, a level pad or slab should be used.
The thickness and size of the pad or slab used should meet local
codes and unit weight. Do not tie the slab to the building foundation.
5. Roof structures must be able to support the weight of the unit and
its options/accessories. Unit must be installed on a solid, level roof
curb or appropriate angle iron frame.
6. Maintain level tolerance to 1/8” across the entire width and length of
unit.
Excessive exposure of this unit to contaminated combustion air may
result in equipment damage or personal injury. Typical contaminates
include: permanent wave solution, chlorinated waxes and cleaners,
chlorine based swimming pool chemicals, water softening chemicals,
carbon tetrachloride, Halogen type refrigerants, cleaning solvents
(e.g. perchloroethylene), printing inks, paint removers, varnishes,
hydrochloric acid, cements and glues, anti-static fabric softeners for
clothes dryers, masonry acid washing materials.
outdoor installation only.
!
WARNING
!
WARNING
CLEARANCES
All units require particular clearances for proper operation and service.
Installer must make provisions for adequate combustion and ventilation
air in accordance with section 5.3 of Air for Combustion and Ventilation
of the National Fuel Gas Code, ANSI Z223.1 – Latest Edition (in
U.S.A.), or Sections 7.2, 7.3, or 7.4 of Gas Installation Codes, CSAB149.1 (in Canada) - Latest Edition, and/or applicable provisions of the
local building codes. Refer to Table 4 for clearances required for combustible construction, servicing, and proper unit operation.
!
WARNING
Do not permit overhanging structures or shrubs to obstruct condenser air discharge outlet, combustion air inlet or vent outlets.
RIGGING AND HANDLING
Exercise care when moving the unit. Do not remove any packaging until
the unit is near the place of installation. Rig the unit by attaching chain
or cable slings to the lifting holes provided in the base rails. Spreader
bars, whose length exceeds the largest dimension across the unit,
MUST be used across the top of the unit.
!
CAUTION
Before lifting, make sure the unit weight is distributed equally on the
rigging cables so it will lift evenly.
Units may be moved or lifted with a forklift. Slotted openings in the base
rails are provided for this purpose.
!
CAUTION
If a unit is to be installed on a roof curb other than a Unitary Products
roof curb, gasket or sealant must be applied to all surfaces that come
in contact with the unit underside.
!
CAUTION
All panels must be secured in place when the unit is lifted.
The condenser coils should be protected from rigging cable damage
with plywood or other suitable material.
"D"
CENTER OF
COMPRESSOR
"A"
FRONT
OF UNIT
X
FIGURE 2: Center of Gravity Location
"B"
GRAVITY
"C"
Y
A0295-001
Table 2: Weights and Dimensions
ModelWeight (lbs.)Center of Gravity4 Point Load Location (lbs.)
1. A 1" clearance must be provided between any combustible material and the supply air duct work.
2. The products of combustion must not be allowed to accumulate within a confined space and recirculate.
3. Units must be installed outdoors. Over hanging structure or shrubs should not obstruct condenser air discharge outlet.
4. Units may be installed on combustible floors made from class A, B or C roof covering materials.
4
1
A0296-001
Johnson Controls Unitary Products5
1183746-UIM-D-1015
D
C
A
B
A
ModelABCDEF
24, 30, 36, 421021.554.547.532
48, 601413.553.547.542
FIGURE 4: Bottom Duct Dimensions (inches)
16
RETURN
AIR DUCT
SUPPLY
AIR DUCT
E
F
A0298-001
Duct work should be designed and sized according to the methods of
the Air Conditioning Contractors of America (ACCA), as set forth in their
Manual D.
A closed return duct system shall be used. This shall not preclude use
of economizers or ventilation air intake. Flexible joints are recommended to be used in the supply and return duct work to minimize the
transmission of vibration and noise.
NOTICE
Be sure to note supply and return openings.
Refer to Figures 5 and 6 for information concerning rear and bottom
supply and return air duct openings.
FILTERS
Proper filter size is very important. Filter size, type and pressure drop
should always be considered during duct system design.
Single phase units are shipped without a filter or filter racks. It is the
responsibility of the installer to secure a filter in the return air ductwork
or install a Filter/Frame Kit.
A filter rack and high velocity filters are standard on three phase units.
Filters must always be used and must be kept clean. When filters
become dirt laden, insufficient air will be delivered by the blower,
decreasing your units efficiency and increasing operating costs and
wear-and-tear on the unit and controls.
Filters should be checked monthly; this is especially important since this
unit is used for both heating and cooling.
CONDENSATE DRAIN
A condensate trap must be installed in the condensate drain. The
plumbing must conform to local codes.
DO NOT use Teflon tape or Pipe thread compound.
SUPPLY
15.6
6
A0299-001
ModelAB
24, 30, 36, 429.622
48, 6013.614
FIGURE 5: Rear Duct Dimensions (inches)
AIR DUCT
A
B
RETURN
AIR DUCT
A
4.3
DUCTWORK
These units are adaptable to downflow use as well as rear supply and
return air duct openings. To convert to downflow, use the following
steps:
1. Remove the duct covers found in the bottom return and supply air
duct openings.
2. Install the duct covers (removed in step one) to the rear supply and
return air duct openings.
3. Seal duct covers with silicone caulk.
!
CAUTION
Hand tighten only.
SERVICE ACCESS
Access to all serviceable components is provided at the following locations:
• Coil guards
• Unit top panel
• Corner posts
• Blower access panel
• Control access panel
• Indoor coil access panel
• Compressor access panel
• Heat exchanger access panel
Refer to Figure 4 for location of these access locations and minimum
clearances in Table 4.
!
CAUTION
This system uses R-410A Refrigerant which operates at higher pressures than R-22. No other refrigerant may be used in this system.
Gage sets, hoses, refrigerant containers and recovery systems must
be designed to handle R-410A. If you are unsure, consult the equipment manufacturer. Failure to use R-410A compatible servicing
equipment may result in property damage or injury.
!
WARNING
Wear safety glasses and gloves when handling refrigerants. Failure
to follow this warning can cause serious personal injury.
Refer to Figure 14 for the R-410A Quick Reference Guide.
6Johnson Controls Unitary Products
1183746-UIM-D-1015
THERMOSTAT
The room thermostat should be located on an inside wall approximately
60" above the floor where it will not be subject to drafts, sun exposure or
heat from electrical fixtures or appliances. Sealant should be used
behind thermostat to prevent air infiltration. Follow manufacturer's
instructions enclosed with the thermostat for general installation procedure. Color coded insulated wires (minimum #18 AWG) should be used
to connect thermostat to unit. See Figure 6. Do not use power stealing
thermostats.
POWER AND CONTROL WIRING
Field wiring to the unit must conform to provisions of the current N.E.C.
ANSI/NFPA No. 70 or C.E.C. and/or local ordinances. The unit must be
electrically grounded in accordance with local codes or, in their
absence, with the N.E.C./C.E.C. Voltage tolerances which must be
maintained at the compressor terminals during starting and running
conditions are indicated on the unit Rating Plate and Table 1.
The wiring entering the cabinet must be provided with mechanical strain
relief.
A fused disconnect switch should be field provided for the unit. If any of
the wire supplied with the unit must be replaced, replacement wire must
be of the type shown on the wiring diagram.
Electrical service must be sized properly to carry the load. Each unit
must be wired with a separate branch circuit fed directly from the main
distribution panel and properly fused.
Refer to Figures 6 and 7 for typical field wiring and to the appropriate
unit wiring diagram for control circuit and power wiring information.
Minimum wire size of 18 AWG wire should be used for all field
installed control wiring.
THERMOSTAT
R
G
Y
W
C
NOTE:
Heat Anticipator should be set at 0.35 AMPS for all models
RED
GREEN
YELLOW
WHITE
BLUE
CONTROL
BOARD
A0294-001
FIGURE 6: Typical Field Control Wiring Diagram For Gas Heat - AC
Models
CONTACTOR
FIELD SUPPLIED
DISCONNECT
SINGLE
PHASE
GND
LUG
REFER TO ELECTRICAL
DATA TABLES TO SIZE
THE DISCONNECT
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker size installed at factory or field installed.
3
(Amps)
Size
Johnson Controls Unitary Products7
1183746-UIM-D-1015
Table 6: Physical Data
COMPONENT
NOMINAL TONNAGE2.02.53.03.54.05.0
AHRI Cooling Performance
Gross Capacity @ AHRI A point (MBH)23.730.137.243.547.755.0
AHRI net capacity (MBH)22.829.034.641.045.552.5
EER11.011.011.011.011.011.0
SEER14.014.014.014.014.014.0
Nominal CFM80010001200140016002000
System power (KW)2.12.63.23.84.24.8
Refrigerant typeR410AR410AR410AR410AR410AR410A
Refrigerant charge (lb-oz)5-49-28-39-414-414-2
Face area (Sq. Ft.)15.117.017.017.023.826.0
Rows233333
Fins per inch161616161616
Tube diameter 3/8 3/8 3/8 3/8 3/8 3/8
Circuitry TypeInterlacedInterlacedInterlacedInterlacedInterlacedInterlaced
Evaporator Coil Data
Face area (Sq. Ft.)3.43.43.44.44.44.4
Rows233333
Fins per inch161616161616
Tube diameter 3/8 3/8 3/8 3/8 3/8 3/8
Circuitry TypeInterlacedInterlacedInterlacedInterlacedInterlacedInterlaced
Refrigerant controlTXVTXVTXVTXVTXVTXV
Condenser Fan Data
Fan diameter (Inch)242424242626
TypePropPropPropPropPropProp
Drive typeDirectDirectDirectDirectDirectDirect
No. speeds111111
Motor HP each 1/4 1/4 1/4 1/4 1/3 1/3
RPM850850850850850850
Nominal total CFM240024002400240032003200
Direct Drive Evaporator Fan Data
Fan Size (Inch)11 x 811 x 811 x 1011 x 1011 x 1011 x 10
TypeCentrifugalCentrifugalCentrifugalCentrifugalCentrifugalCentrifugal
Motor HP each 1/31/2 1/31/21/23/4 3/43/41
RPM1200 Max1200 Max1200 Max1200 Max1200 Max1200 Max
Frame size484848484848
Field-supplied external filters must be sized so as not to exceed 300 fpm air velocity through disposable
filters. For internal filter use, a filter rack kit is available. Consult the instructions supplied with that kit for
replacement filter sizes. Filter sizes: A=20x20, B=20x30.
51-1/451-1/451-1/451-1/4
35-3/435-3/445-3/445-3/4
MODELS
8Johnson Controls Unitary Products
Loading...
+ 18 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.