Johnson Controls P352PN-2, P352PN-4, P352PN-3 Product Manual

System 350 Product Guide 930
Basic Controls Section
Product/Technical Bulletin P352P
Issue Date 0300
Pressure Controls for PSI Applications
The P352PN Series controls are electronic proportional plus integral or proportional-only pressure controls that generate a 0 to 10 VDC and a 0 to 20 mA analog output signal based on sensed pressure. Three models are available with setpoint ranges of 0-100 psi, 90-250 psi, and 240-600 psi.
The P352PN Series controls have a wide adjustable throttling range (proportional band), as well as three selectable integration constants.
The P352PN Series controls are housed in a NEMA 1 high-impact thermoplastic enclosure. The modular design provides easy, plug-together connections for quick installation and integration with specified power, stage, and display modules.
Features and Benefits
Modular Design
Plug-together Connectors
and 35 mm DIN Rail Mounting
Three Models Cover Wide
Setpoint Ranges: 0-100 psi, 90-250 psi, and 240-600 psi
Adjustable Minimum Signal
Output
Wide Adjustable Throttling
Ranges: 5 to 50 psi and 10 to 100 psi
Reverse or Direct Acting
Modes
Figure 1: P352PN Electronic Proportional Plus
Integral Pressure Control for PSI Applications
Provides the flexibility to add a D352 Pressure Display Module, S352 Stage Modules, and a Y350R Power Module
Eliminates wiring between modules and reduces installation costs
Reduces inventory while providing control for most positive-pressure refrigeration and HVAC applications, in three overlapping pressure ranges
Allows the user to adjust the minimum output between 0 and 60% of the output signal range
Enables user to match the range of pressure control to specific application requirements
Works in a variety of pressure applications
Three Selectable
Integration Constants
© 2000 Johnson Controls, Inc.
Part No. 24-7664-1911, Rev. — www.johnsoncontrols.com Code No. LIT-930044
Allows the user to adjust system recovery rate to setpoint pressure at slow, medium, or fast to meet application requirements
1
pplication
A
A P352PN Series pressure control may be set as a proportional-only control or as a proportional plus integral control, to generate two standard analog output signals (0 to 10 VDC and 4 to 20 mA).
The P352PN controls can be used as stand-alone devices or in conjunction with plug-together power, stage, and display modules.
A typical System 350 pressure control application includes the following:
P352PN Pressure Control
Y350R Power Module (or 24 VAC transformer)
S352AA-2 Stage Module
D352AA-2 Digital Pressure Display Module
P399 Pressure Transducer
Typical P352PN pressure control applications include:
Condenser fan speed control
Damper positioning
Flow valve positioning
peration Overview
O
IMPORTANT: The P352PN controls are intended to
control equipment under normal operating conditions. Where failure or malfunction of the P352PN control could lead to an abnormal operating condition that could cause personal injury or damage to the equipment or other property, other devices (limit or safety controls) or systems (alarm or supervisory systems) intended to warn of, or protect against, failure or malfunction of the P352PN control must be incorporated into and maintained as part of the control system.
The P352PN control operates on 24 VAC and provides two analog output signals: 0 to 10 VDC and 0 to 20 mA. A 10-segment front panel LED bar graph indicates percentage of output. Adjustable features include:
Setpoint
Minimum output
Throttling range (proportional band)
Integration constant
Reverse acting or direct acting mode of operation
Setpoint Potentiometer
Minimum Output Potentiometer
Throttling Range
Potentiometer
Integration DIP Switch
43
21
O
N
0 to 10 VDC Output 0 to 20 mA Output
Common for Analog
Outputs
Module Connector
J1 Jumper
Positions
LED Indicator
24 VAC Transformer
(If a Y350R Power Module
Red wire to VDC
Reverse Acting
Direct Acting
is not used)
120/240 VAC
Black wire to C
White wire to SN
THROT RANGE
OUTPUT
I
V
MIN
PSI
SN
VDC
24V
C
(Percent of Output)
24 VAC
Connect Cable
Shield to C
Figure 2: Interior View and Typical Wiring of P352PN Control
P399
Transducer
WHA-P 399
Wiring Harness
2
Basic Controls—P352PN Electronic Proportional Plus Integral Pressure Controls for PSI Applications
Proportional-Only Controls
Proportional Plus Integral Controls
Proportional-only controls work by continuously adjusting the magnitude of the control’s output signal in proportion to the difference (input-error) between the control’s setpoint value and the actual value sensed in the controlled system. As load on a system increases, the input-error to the control increases. The control reacts by increasing the magnitude of the output signal, driving the controlled device to respond to the increased load. (See Figure 3.)
The advantages of proportional-only controls are that they are easy to set up and adjust, and they provide good stability and rapid response to changing load conditions.
A disadvantage of proportional-only controls is they can not maintain a system process at the exact control setpoint. A proportional offset (or droop) is always present when there is a steady load on the controlled system. (See Figure 3.)
The result is that a proportional-only control maintains a system process at a control-point instead of the desired setpoint. Control-point is setpoint plus the proportional offset. The greater the load on the system, the greater the proportional offset and the further the control-point is from the system setpoint. A proportional-only control can not adjust the output signal to drive a system process from the control-point to the desired setpoint. (See Figure 3.)
Systems with proportional-only controls and large loads or highly variable load conditions may operate at control-points that vary significantly from the desired setpoint.
The P352PN proportional plus integral (PI) pressure control incorporates integral (or reset) control action along with proportional-only control action. The advantage to this is that the PI design effectively eliminates proportional offset, and the PI control can adjust the output signal to not only match a steady load on the system, but also drive the system process towards setpoint. On a properly sized system with steady load conditions, a PI control can maintain the system process very close to the system setpoint. (See Figure 3.)
The speed at which the PI control drives the system process to setpoint (recovery rate) is determined by the system’s capacity, the size of the load, and the integration constant set on the PI control.
The integration constant establishes the rate at which the control re-adjusts to the load as it drives the process towards setpoint. The faster the integration constant, the faster the control re-adjusts the magnitude of the output signal, and the faster the recovery rate of a properly sized and setup system.
On traditional PI controls, the rate of re-adjustment can become too large if the process load exceeds the capacity of the equipment. When the controlled equipment is at full capacity and the setpoint still cannot be reached, traditional PI controls continue to readjust the magnitude of the output signal. The result is called
The P352PN Series proportional plus integral controls avoid dynamic ceiling on the integrator, which allows the process to recover from an out-of-range condition without experiencing a long period of overshoot.
integral windup
integral windup
.
with a patented circuit that puts a
Basic Controls—P352PN Electronic Proportional Plus Integral Pressure Controls for PSI Applications
It should be noted that PI controls might not be suitable for all applications. Improperly applied PI controls may be unstable and overshoot setpoint.
Also, PI controls require two separate adjustments that are dependent on each other. The system must be properly sized to handle the maximum process load, and close observation is necessary when the PI controls are initially set up and checked out. But on the proper applications PI controls provide superior accuracy and continuous setpoint control.
3
Temperature
Proportional Only Control
Proportional
Offset
Proportional
Offset = 0
Load Change
Setpoi nt
Temperature
Load Change
Setpoi nt
Error
Time
Proportional Plus Integral Control
Error
Time
Figure 3: Operation of Proportional Only vs. Proportional Plus Integral Control
Minimum Output Adjustment and LED Bar Graph Output Indicator
The minimum output adjustment sets the minimum signal output (in VDC or mA) that the P352PN control provides to the controlled device. The minimum output can be set between 0 and 60% of the output range (up to 6 VDC or 12 mA).
Example: For a controlled device that responds to a 4 to 20 mA output signal, the minimum output must be 4 mA or 20% of the 0 to 20 mA range. (See Figure 4.)
Adjust the MIN OUTPUT potentiometer located in the center of the circuit board. The LED bar graph will advance one LED segment for each 10% increase in output range. The first segment lights at 10%, the second segment at 20% and so on, until the tenth segment lights at 100%.
Output
20
Range
(in mAs)
Minimum
Output
Setting (20%)
Minimum Output Set to 20% (4 mA) and Throttling Range Set to 50 psi for P352PN-2 or 100 psi for P352PN-3 and P352PN-4.
10
4
0
Setpoi nt
Pressure
25 50
Throttling Range (psi)
50
100
(Range for
P352PN-2)
(Range for
P352PN-3 or
P352PN-4)
System Load
Throttling
Control Point Follows the Load
System Load
Integration adjusts the proportional output to bring the process to setpoint regardless of load.
Range
Throttling Range (Proportional Band)
On controls set for proportional only, the throttling range or proportional band setting establishes how far the system pressure must deviate from the P352PN control setpoint to generate a 100% output signal from the control.
Thus, on a proportional only control with a throttling range setting of 25 psi, the output signal (VDC or mA) is 0% when the system pressure equals the setpoint pressure. The output signal increases to 100% (10 VDC or 20 mA) when the system pressure rises 25 psi above the setpoint in DA mode, or drops 25 psi below the setpoint in RA mode.
When setting up controls for proportional plus integral operation, start with the integration constant OFF (in the proportional only mode), and set the throttling range (or proportional band) to a wide setting (60% or more of the total range) to assure a stable control loop. Then set the integration constant as slow as possible. (Refer to
Adjust the throttling range by turning the THROT RANGE potentiometer located under the control cover on the center of the circuit board.
The throttling range can be adjusted from 5-50 psi on the P352PN-2 model and 10-100 psi on the P352PN-3 and P352PN-4 models. (See Figures 4 and 5.)
Integration Constant DIP Switch Settings.
)
Figure 4: Minimum Output and Throttling Ranges for
the P352PN Controls
4
Basic Controls—P352PN Electronic Proportional Plus Integral Pressure Controls for PSI Applications
Loading...
+ 8 hidden pages