OLS-2100 Occupancy Light Switch
OLS-2100 Series Occupancy Light Switch
Code No. LIT-1922205
Issued February 23, 2013
Description
The OLS-2100 Occupancy Light Switch, a
passive infrared sensor, is designed to turn
lights on when it detects human movement
within its field of view. The sensor is an indoor
lighting control and should not be used
outdoors, or as a security device, or to control
fans, heaters, or air conditioners.
Features
• three settings: time delay, daylight sensor
lockout, and sensitivity control, to allow for
changes that best match the room’s use
and the occupants’ needs
• standard, single-toggle light switch size
allows quick, easy replacement of existing
wall switches, reducing installation time
• infrared occupancy sensor can control
lighting usage based on occupancy
• a single model provides compatibility with
supply voltages in commercial buildings
• low-profile design and decorative wall plate
complement building and office decor
• 180° field of view and coverage to 900
square feet covers most offices,
conference rooms, and storage areas
Selection Chart
Code
Number
OLS-2100-1 Incandescent 120 VAC, 60 Hz
1. The OLS-2100 is not designed to operate at 50 Hz.
Lighting Type Voltage Load Range
Fluorescent 277 VAC, 60 Hz
Description
• the adjustment cover has an anti-tamper
feature that prevents unauthorized
changes to selected settings
Applications
• lighting control in enclosed offices,
conference rooms, computer rooms, and
small common areas in a building
• replaces standard, single-pole, indoor light
switches that control incandescent or
fluorescent fixtures that use magnetic or
electronic ballasts
• use alone or to complement integrated
lighting systems
Repair Information
If the OLS-2100 Occupancy Light Switch fails
to operate within its specifications, replace the
unit. For a replacement switch, contact the
nearest Johnson Controls® representative.
Technical Specifications
OLS-2100 Occupancy Light Switch
Maximum
1
0 to 800 Watts
1
0 to 1200 Watts
Sensor Type Passive infrar e d
Power Requirement 120/277 VAC, 60 Hz
Load Range (Standard or electron ic ballast)
Current Consumption Less than 0.5 mA
Warmup Time 60 seconds maximum
Wiring 3-wire installation (Requires a continuous grounding
Ambient Conditions 32 to 95° F (0 to 35°C), 5 to 95% RH noncon densing ;
Field of View 180° (900 sq ft [81 sq m])
LED Indicator Flashes when motion is detected
Daylight Lockout
Control
Time Delay Control 30 seconds to 30 minutes (Factory set to 30 minutes.)
Sensitivity Control Adjustable from 20 to 100% of maximum sensitivity.
Shipping Weight 0. 5 l b (0.23 kg)
Agency Listing UL Listed (120 VAC and 277 VAC models),
120 VAC, 60 Hz; 25 to 800 watts incandescent,
40 to 800 watts fluorescent
277 VAC, 60 Hz; 40 to 1,200 watts fluorescent
system.)
85°F (29°C) maximum dew point
Lights stay off if adequate light level is det ected
(Factory set to 100%.)
cUL Listed (120 VAC)
The performance specifications are nomina l and conf orm to accep table industr y standar ds. For ap plications a t condition s beyond th ese specification s, consult the local Johnson Controls o ffice.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2013 Johnson Controls, Inc.