Johnson Controls NS Series Catalog Page

NS Series Network Sensors
NS Series Network Sensors with Black Enclosures
Code No. LIT-1900350 Issued July 2016
NS Series Network Sensors
The NS Series Network Sensor offering includes NS Series Network Zone Sensors and NS Series Network Discharge Air Sensors. The NS Series Network Sensors are designed to function directly with Metasys® system Field Equipment Controllers (FECs), Input/Output Modules (IOMs), VAV Modular Assembly (VMA16) Controllers, and Facility Explorer FX-PC Series Programmable Controllers (FX-PCGs, FX-PCVs, and FX-PCXs).
The majority of NS Series Network Zone Sensors monitor room temperature; however, options are available to also monitor zone humidity, carbon dioxide (CO adjustments, and other variables. This data is transmitted to a controller on the Sensor Actuator (SA) Bus.
Some models of NS Series Network Zone Sensors include an onboard passive infrared (PIR) occupancy sensor that detects motion to determine if a space is occupied. This feature maximizes up to 30% energy savings in high-energy usage environments such as schools, dormitories, offices, hospitals, and hotels by adjusting the temperature of the space based on the occupancy status. In addition, the PIR occupancy sensor facilitates trending of floor space usage in these environments.
The NS Series Network Zone Sensors include models with a temperature setpoint dial and LCD that allows occupants to view the zone temperature, Relative Humidity (RH), and view and adjust the zone temperature setpoint. Some temperature and humidity models include a push button to toggle between temperature and RH on the display. These models also have the capability to set the desired default display to either temperature or RH.
A fan mode push button is included to set the desired fan speed (AUTO-OFF-low-medium-high). An occupancy override function allows the user to signal to the controller that the zone is occupied to override the scheduled mode. Some models have DIP switches to set a unique address for applications that require multiple sensors.
For communication wiring flexibility, the wires connecting the network zone sensor to a controller can be terminated using a modular jack or screw terminals.
Note: Mixing of phone jack and screw terminal devices on the same SA bus segment must be avoided.
Each network sensor includes an SA Bus access port to allow accessories to access the SA Bus. This plug allows accessories to service or commission the connected controller or gain access to any other controller on the same Field Controller (FC) Bus.
The NS Series Network Zone Sensor offering includes models that can be surface mounted, vertical wallbox mounted, or flush mounted to meet the requirements of the specific application. Some NS Series Sensor models are designed to assist with the California Energy Code (Title 24). Select models offer stylish black enclosures to suit specific architectural and interior design needs.
The NS Series Network Discharge Air Sensors monitor the duct temperature, typically at the discharge of the VA V box, and transmit this data to a local controller on the SA Bus using the 10 ft (305 cm) wiring lead included with the unit. The 10 ft (305 cm) wiring lead consists of four 22 AWG (0.6 mm) trade size color-coded wires encased in a plenum-rated jacket. Each of the wires is stripped and tinned for easy connection to the SA Bus screw terminal block.
The NS Series Network Discharge Air Sensors are available with either a 4- or 8-in. (102 or 203 mm) temperature probe. All models include DIP switches for applications requiring multiple discharge air sensors, each with a unique DIP switch address.
Refer to the NS Series Network Sensors Product Bulletin (LIT-12011574) for important product application and single point of contact information.
The performance specifications are nomina l and conf orm to accep table industr y standar ds. For ap plications a t condition s beyond th ese specification s, consult the local Johnson Controls o ffice. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2016 Johnson Controls, Inc.
), local temperature setpoint
2
Features
• BACnet® Master-Slave/Token-Passing (MS/TP) protocol communication — provides compatibility with Metasys system field controllers and Facility Explorer programmable controllers in a proven communication network
• backlit LCD available on some models — provides real-time status of the environment with backlighting activated during user interaction
• simple temperature setpoint adjustment available on some models — enables you to change the setpoint with the turn of a dial
• onboard PIR occupancy sensor available on some models — maximizes up to 30% energy savings in high-energy usage environments, and facilitates trending of floor space usage
• temporary occupancy available on some models — provides a timed override command, which temporarily initiates an alternate mode
• field selectable default display setting on some models — allows you to toggle between temperature and RH on the display, and set the desired default for continuous viewing
• Fahrenheit/Celsius (F/C) button available on some models — toggles the display temperature between degrees Celsius and degrees Fahrenheit
www.johnsoncontrols.com
1
NS Series Network Sensors (Continued)
Note: Since some NS Series Network Sensor features are not supported in previous releases of Metasys or Facility Explorer system software, it is recommended that the system software be kept up to date.
Repair Information
If the NS Series Network Zone Sensor or the NS Series Network Discharge Air Sensor fails to operate within its specifications, replace the unit. For a replacement sensor, contact the nearest Johnson Controls® representative.
Selection Charts
Network Zone Sensor Ordering Information—Temperature Only Models (Part 1 of 2)
Product Code Number
NS-ATA7001-0 80 x 80 SM Yes Yes Set Yes, No No No MJ No No NS-ATA7001-0A
NS-ATA7002-0 80 x 80 SM Yes Yes Set Yes, No No No ST No No NS-ATA7002-0A NS-ATA7002-3
NS-ATA7003-0 80 x 80 SM Yes Yes Set Yes, No No No ST Yes No NS-ATA7004-2 80 x 80 SM No Yes Set Yes, No No No ST, MJ Yes No NS-ATB7001-0 80 x 80 SM Yes Yes Set Yes, No Yes No MJ No No NS-ATB7002-0 80 x 80 SM Yes Yes Set Yes, No Yes No ST No No NS-ATB7003-0 80 x 80 SM Yes Yes Set Yes, No Yes No ST Yes No NS-ATC7001-0 80 x 80 SM Yes Yes Set Yes, No No Yes MJ No No NS-ATC7002-0 80 x 80 SM Yes Yes Set Yes, No No Yes S T No No NS-ATC7005-2 80 x 80 SM No Yes Set Yes, No No Yes ST, MJ No No NS-ATD7001-0 80 x 80 SM Yes Yes Set Yes, No Yes Yes MJ No No NS-ATD7002-0 80 x 80 SM Yes Yes Set Yes, No Yes Yes ST No No NS-ATF7001-0 80 x 80 SM Yes Yes W/C Yes, No Yes No MJ No No NS-ATF7002-0 80 x 80 SM Yes Yes W/C Yes, No Yes No ST No No NS-ATN7001-0 80 x 80 SM Yes No N/A No, No No No MJ No No NS-ATN7001-2 80 x 80 SM No No N/A No, No No No MJ No No NS-ATN7003-0 80 x 80 SM Yes No N/A No, No No No ST Yes No NS-ATN7003-2 80 x 80 SM No No N/A No, No No No ST Yes No NS-ATN7004-2 80 x 80 SM No No N/A No, No No No ST, MJ Yes No NS-ATP7001-0 80 x 80 SM Yes No W/C Yes, No No No MJ No No NS-ATP7001-2 80 x 80 SM No No W/C Yes, No No No MJ No No NS-ATP7002-0 80 x 80 SM Yes No W/C Yes, No No No ST No No NS-ATP7002-2 80 x 80 SM No No W/C Yes, No No No ST No No NS-ATP7003-0 80 x 80 SM Yes No W/C Yes, No No No ST Yes No NS-ATP7003-2 80 x 80 SM No No W/C Yes, No No No ST Yes No NS-ATV7001-0 80 x 80 SM Yes Yes Set Yes, No Yes No NS-ATV7002-0 80 x 80 SM Yes Yes Set Yes, No Yes No NS-BTB7001-0 120 x 80 WB, SM Yes Yes Set Yes, No Yes No MJ No No NS-BTB7001-2 120 x 80 WB, SM No Yes Set Yes, No Yes No MJ No No
NS-BTB7001-3 NS-BTB7002-0 120 x 80 WB, SM Yes Yes Set Yes, No Yes No ST No No NS-BTB7003-0 120 x 80 WB, SM Yes Yes Set Yes, No Yes No ST Yes No NS-BTB7003-2 120 x 80 WB, SM No Yes Set Yes, No Yes No ST Yes No NS-BTF7001-0 120 x 80 WB, SM Yes Yes W/C Yes, No Yes No MJ No No NS-BTF7002-0 120 x 80 WB, SM Yes Yes W/C Yes, No Yes No ST No No NS-BTL7003-0 120 x 80 WB, SM Yes No N/A Yes, No No No ST Yes No NS-BTN7001-0 120 x 80 WB, SM Yes No N/A No, No No No MJ No No NS-BTN7001-2 120 x 80 WB, SM No No N/A No, No No No MJ No No NS-BTN7003-0 120 x 80 WB, SM Yes No N/A No, No No No ST Yes No NS-BTN7003-2 120 x 80 WB, SM No No N/A No, No No No ST Yes No NS-BTP7001-0 120 x 80 WB, SM Yes No W/C Yes, No No No MJ No No NS-BTP7001-2 120 x 80 WB, SM No No W/C Yes, No No No MJ No No
The performance specifications are no minal and co nform t o acceptab le ind ustry standar ds. For appl ications at condition s beyond these specifica tions, consult the local Johnson Co ntrols office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2016 Johnson Controls, Inc.
Size (mm), Height x Width
2
80 x 80 SM Yes Yes Set Yes, No No No MJ No No
2
80 x 80 SM Yes Yes Set Yes, No No No ST No No
3
80 x 80 SM Yes Yes Set Yes, No No No ST No No
3
120 x 80 WB, SM Yes Yes Set Yes, No Yes No MJ No No
Vertical Wallbox­Mounted (WB) or Surface­Mounted (SM)
Johnson Controls Logo
LCD Display
Temperature Adjustment: Setpoint (Set) or Warmer/Cooler Dial (W/C)
Occupancy
1
Override PIR Occupancy Sensor
,
F/C Scale Toggle
Fan Control
4 4
Screw Terminals (ST) or Modular Jack (MJ)
MJ No Yes ST No Yes
Address Switches
www.johnsoncontrols.com
VAV Balancing Feature
2
NS Series Network Sensors (Continued)
Network Zone Sensor Ordering Information—Temperature Only Models (Part 2 of 2)
Product Code Number
NS-BTP7002-0 120 x 80 WB, SM Yes No W/C Yes, No No No ST No No NS-BTP7002-2 120 x 80 WB, SM No No W/C Yes, No No No ST No No NS-BTP7003-0 120 x 80 WB, SM Yes No W/C Yes, No No No ST Yes No NS-BTV7001-0 120 x 80 WB, SM Yes Yes Set Yes, No Yes No NS-BTV7002-0 120 x 80 WB, SM Yes Yes Set Yes, No Yes No NS-MTB7001-0 120 x 80 WB, SM Yes Yes Set Yes, Yes Yes No MJ No No NS-MTB7002-0 120 x 80 WB, SM Yes Yes Set Yes, Yes Yes No ST No No NS-MTB7004-2 120 x 80 WB, SM No Yes Set Yes, Yes Yes No ST, MJ Yes No NS-MTL7001-0 120 x 80 WB, SM Yes No N/A Yes, Yes No No MJ No No NS-MTL7002-0 120 x 80 WB, SM Yes No N/A Yes, Yes No No ST No No NS-MTN7004-2 120 x 80 WB, SM No No N/A No, Yes No No ST, MJ Yes No
1. An Occupancy Override button is available on NS-xxP and NS-xxL models. Other models di splay Occup ancy Over ride through the setpoint adjustme nt interf ace.
2. This model is currently only available in Asia. Contact your Johnson Controls representative for more information.
3. These models feature a black enclosure.
4. In the VAV balancing models, the fan control butt on is replaced by a light bulb button used in the VAV balancing process.
Network Zone Sensor Ordering Information—Temperature and Humidity Models without RH Display
Product Code Number
NS-AHA7001-0 80 x 80 SM Yes Yes, No 3% Set Yes, No No MJ No NS-AHA7002-0 80 x 80 SM Yes Yes, No 3% Set Yes, No No ST No NS-AHA7004-2 80 x 80 SM No Yes, No 3% Set Yes, No No ST, MJ Yes NS-AHB7001-0 80 x 80 SM Yes Yes, No 3% Set Yes, No Yes MJ No NS-AHB7002-0 80 x 80 SM Yes Yes, No 3% Set Yes, No Yes ST No NS-AHB7003-0 80 x 80 SM Yes Yes, No 3% Set Yes, No Yes ST Yes NS-AHN7001-0 80 x 80 SM Yes None 3% N/A No, No No MJ No NS-AHN7001-2 80 x 80 SM No None 3% N/A No, No No MJ No NS-AHN7003-0 80 x 80 SM Yes None 3% N/A No, No No ST Yes NS-AHN7004-2 80 x 80 SM No None 3% N/A No, No No ST, MJ Yes NS-AHP7001-0 80 x 80 SM Yes None 3% W/C Yes, No No MJ No NS-APA7001-0 80 x 80 SM Yes Yes, No 2% Set Yes, No No MJ No NS-APA7002-0 80 x 80 SM Yes Yes, No 2% Set Yes, No No ST No NS-APB7001-0 80 x 80 SM Yes Yes, No 2% Set Yes, No Yes MJ No NS-APB7002-0 80 x 80 SM Yes Yes, No 2% Set Yes, No Yes ST No NS-APB7003-0 80 x 80 SM Yes Yes, No 2% Set Yes, No Yes ST Yes NS-BHB7001-0 120 x 80 WB, SM Yes Yes, No 3% Set Yes, No Yes MJ No NS-BHB7002-0 120 x 80 WB, SM Yes Yes, No 3% Set Yes, No Yes ST No NS-BHB7003-0 120 x 80 WB, SM Yes Yes, No 3% Set Yes, No Yes ST Yes NS-BHN7001-0 120 x 80 WB, SM Yes None 3% N/A No, No No MJ No NS-BHN7001-2 120 x 80 WB, SM No None 3% N/A No, No No MJ No NS-BHN7003-0 120 x 80 WB, SM Yes None 3% N/A No, No No ST Yes NS-BHP7001-0 120 x 80 WB, SM Yes None 3% W/C Yes, No No MJ No NS-BHP7003-0 120 x 80 WB, SM Yes None 3% W/C Yes, No No ST Yes NS-BPB7001-0 120 x 80 WB, SM Yes Yes, No 2% Set Yes, No Yes MJ No NS-BPB7002-0 120 x 80 WB, SM Yes Yes, No 2% Set Yes, No Yes ST No NS-BPB7003-0 120 x 80 WB, SM Yes Yes, No 2% Set Yes, No Yes ST Yes NS-MHB7004-2 120 x 80 WB, SM No Yes, No 3% Set Yes, Yes Yes ST, MJ Yes NS-MHL7001-0 120 x 80 WB, SM Yes No, No 3% N/A Yes, Yes No MJ No NS-MHL7002-0 120 x 80 WB, SM Yes No, No 3% N/A Yes, Yes No ST No NS-MHN7004-2 120 x 80 WB, SM No None 3% N/A No, Yes No ST, MJ Yes
Size (mm), Height x Width
Size (mm), Height x Width
Vertical Wallbox­Mounted (WB) or Surface­Mounted (SM)
Vertical Wallbox­Mounted (WB) or Surface­Mounted (SM)
Johnson Controls Logo
Johnson Controls Logo
LCD Display
LCD Display, RH Display
Temperature Adjustment: Setpoint (Set) or Warmer/Cooler Dial (W/C)
Humidity Element Accuracy
Occupancy
1
Override PIR Occupancy Sensor
,
Temperature Adjustment: Setpoint (Set) or Warmer/ Cooler Dial (W/C)
F/C Scale Toggle
Occupancy Override
Fan Control
1
, PIR Occupancy Sensor
Screw Terminals (ST) or Modular Jack (MJ)
4
MJ No Yes
4
ST No Yes
F/C Scale Toggle
Screw Terminals (ST) or Modular Jack (MJ)
Address Switches
VAV Balancing Feature
Address Switches
The performance specifications are no minal and co nform t o acceptab le ind ustry standar ds. For appl ications at condition s beyond these specifica tions, consult the local Johnson Co ntrols office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2016 Johnson Controls, Inc.
www.johnsoncontrols.com
3
NS Series Network Sensors (Continued)
1. An Occupancy Override button is available on NS-xxP and NS-xxL models. Other models d isplay O ccup ancy Overrid e t hrough t he se tpoint adjustment interface.
Network Zone Sensor Ordering Information—Temperature and Humidity Models with Temperature or RH Display (Field Selectable Default Display)
Product Code Number
NS-AHR7101-0 80 x 80 SM Yes, Yes 3% Set Yes Yes MJ No NS-AHR7102-0 80 x 80 SM Yes, Yes 3% Set Yes Yes ST No NS-AHR7103-0 80 x 80 SM Yes, Yes 3% Set Yes Yes ST Yes NS-APR7101-0 80 x 80 SM Yes, Yes 2% Set Yes Yes MJ No NS-APR7102-0 80 x 80 SM Yes, Yes 2% Set Yes Yes ST No NS-BHR7101-0 120 x 80 WB, SM Yes, Yes 3% Set Yes Yes MJ No NS-BHR7103-0 120 x 80 WB, SM Yes, Yes 3% Set Yes Yes ST Yes
1. An Occupancy Override button is available on NS-xxP and NS-xxL models. Other models display Occup an cy Override t hrough the se tpoi nt adjustme nt interf ace.
Network Zone Sensor Ordering Information—Motion Detection Only Models (No Temperature or Humidity Sensing)
Product Code Number
NS-MNN7001-0 120 x 80 WB, SM Yes No Yes MJ No NS-MNN7003-0 120 x 80 WB, SM Yes No Yes ST Yes NS-MNN7004-2 120 x 80 WB, SM No No Yes ST, MJ Yes
Network Zone Sensor Ordering Information—CO2 Models
Product Code Number
NS-BCN7004-0 120 x 80 WB, SM No 0 to 2,000 ppm Yes ST, MJ DIP Switch
NS-BCN7004-2 120 x 80 WB, SM No 0 to 2,000 ppm No ST, MJ DIP Switch
Network Zone Sensor Ordering Information—Flush-Mount Temperature Only Models
Product Code Number
NS-FTN7003-0 4-1/2 in. x 2-3/4 in.
NS-FTN7003-2 4-1/2 in. x 2-3/4 in.
Network Discharge Air Sensor Ordering Information
Product Code Number
NS-DTN7043-0 3 in. x 3 in. x 2 in.
NS-DTN7043-2 3 in. x 3 in. x 2 in.
NS-DTN7083-0 3 in. x 3 in. x 2 in.
NS-DTN7083-2 3 in. x 3 in. x 2 in.
Size (mm), Height x Width
Vertical Wallbox­Mounted (WB) or Surface­Mounted (SM)
Size (mm), Height x Width
Size (mm), Height x Width
Faceplate Dimensions, Height x Width
(114mm x 70 mm)
(114mm x 70 mm)
Dimensions, Height x Width x Depth
(76 mm x 76 mm x 51 mm)
(76 mm x 76 mm x 51 mm)
(76 mm x 76 mm x 51 mm)
(76 mm x 76 mm x 51 mm)
LCD Display, RH Display
Humidity Element Accuracy
Temperature Adjustment: Setpoint (Set) or Warmer/ Cooler Dial (W/C)
Vertical Wallbox­Mounted (WB), or Surface-Mounted
Johnson Controls Logo
LCD Display
(SM)
Vertical Wallbox-
LCD Display CO2 Measurement Mounted (WB), or Surface-Mounted (SM)
Mounting LCD Display Temperature
Measurement Range
Flush-Mount No 32.0°F/0.0°C to
Flush-Mount No 32.0°F/0.0°C to
Johnson Controls
104.0°F/40.0°C
104.0°F/40.0°C
Temperature Probe Length
Logo
Yes 4 in. (102 mm) Yes Screw Terminal Block DIP Switch
No 4 in. (102 mm) Yes Screw Terminal Block DIP Switch
Yes 8 in. (203 mm) Yes Screw Terminal Block DIP Switch
No 8 in. (203 mm) Yes Screw Terminal Block DIP Switch
Range
10 ft (305 cm) Wiring Lead Included
Occupancy Override
1
F/C Scale Toggle
Screw Terminals (ST) or Modular
Address Switches
Jack (MJ)
PIR Occupancy Sensor
Screw Terminals (ST),
Address
Switches or Modular Jack (MJ)
Johnson Controls Logo
Screw Terminals (ST), or Modular
Sensor Addressing
Jack (MJ)
(212 to 219)
(212 to 219)
Johnson Controls
Terminations Sensor
Addressing
Logo
Yes Screw Terminal Block DIP Switch
No Screw Terminal Block DIP Switch
(200 to 203)
(200 to 203)
Terminations Sensor
Addressing
(204 to 211)
(204 to 211)
(204 to 211)
(204 to 211)
The performance specifications are no minal and co nform t o acceptab le ind ustry standar ds. For appl ications at condition s beyond these specifica tions, consult the local Johnson Co ntrols office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2016 Johnson Controls, Inc.
www.johnsoncontrols.com
4
NS Series Network Sensors (Continued)
Network Sensors with Fault Code Capability Ordering Information (Title 24 Models for Economizer Fault Detection Diagnostics [FDD])
Product Code Number
NS-ATB7F03-0 80 x 80 Yes Yes, Yes Yes Yes Set Yes No NS-ATB7F03-1 80 x 80 Yes Yes, Yes Yes Yes Set No No NS-BTB7F03-0 80 x 120 Yes Yes, Yes Yes Yes Set Yes No NS-BTB7F03-1 80 x 120 Yes Yes, Yes Yes Yes Set No No
NS Sensors with Fault Code Capability Error Codes
The fault indication comes through the Network Sensor Bus when a Network Sensor is used in the Zone. The LCD indicates the code number for all the required state of California Title 24 economizer fault conditions.
Display Text California Title 24 Economizer Fault
EF1 Air temperature sensor failure/fault Problem with one of the air temperature sensors. Check Outdoor Air, Return Air, or
EF5 Not economizing when it should The economizer is not using outdoor air when it should. EF6 Economizing when it should The economizer is allowing outdoor air inside when the condit ions are not suitable for
EF8 Damper not modulating The economizer damper is not able to modulate properly. Check damper, linkage to
EF9 Excess outdoor air The economizer is allowing excess outdoor air inside.
Size (mm), Height x Width
Condition
Vertical Wallbox­Mounted (WB)
LCD Display, F/C Scale Tog­gle
Possible Problem
Supply Air sensors.
economizer operation.
actuator, or the actuator.
Screw Terminals
Address Switches
Temperature Adjustment: Setpoint (Set) or Warmer/ Cooler Dial (W/C)
Johnson Controls Logo
VAV Balancing Feature
Technical Specifications
NS Series Network Zone Sensors—Temperature Only Models and Temperature and Humidity Models (Part 1 of 2)
Supply Voltage 9.8 to 16.5 VDC; 15 VDC nominal (from SA bus) Current Consumption Temperature only models with LCD display: 21 mA maximum (non-transmitting)
Temperature only models wi thout LCD display: 13 mA maximum (non-transmitting) Temperature and humidity models with LCD display: 25 mA maximum
(non-transmitting) Temperature and humidity models without LCD display: 17 mA maximum
(non-transmitting)
Terminations Modular jack or screw terminal block Sensor Addressing NS-AHx7003-0, NS-APB7003-0, NS-ATx7003-0, NS-BHx7003-0, NS-BPB7003-0,
Wire Size Modular jack models: 24 AWG or 26 AWG (0.5 or 0.4 mm diameter) recommended; three twisted pair
Communication Rate Auto-detect: 9.6k, 19.2k, 38.4k, or 76.8k bps Mounting Surface-mounted: 80 x 80 mm
Temperature Measurement Range 32.0°F/0.0°C to 104.0°F/40.0°C Humidity Measurement Range Full range: 0 to 100% RH
Temperature Sensor Type Local 1k ohm Platinum Resistance Temperature Detector (RTD);
Humidity Sensor Type Thin film capacitive sensor Temperature Resolution (Models with
LCD) Temperature Accuracy NS Series Network Zone Sensor: ±1.0F°/±0.6C°
Humidity Element Accuracy NS-APx700x-0 and NS-BPB700x-0 models: ±2% RH for 20 to 80% RH; ±4% RH for 10 to 20% and 80 to 90% RH
Time Constant 10 minutes nominal at 10 fpm airflow Default Temperature Setpoint
Adjustment Range
NS-BTB7003-0, NS-BTN7003-0, and NS-BTP7003-0 Models: DIP switch set from 200 to 203; factory set at 203 All other models: Fixed address of 199
(six conductors)
Screw terminal block models: 18 to 22 AWG (1.0 to 0.6 mm diameter); 22 AWG (0.6 mm diameter) recommended
Surface-mounted or vertical wallbox-mounted: 120 x 80 mm
Calibrated range: 10 to 90% RH
Class A per IEC 60751
±0.5F°/±0.5C°
Temperature element only: 0.35F° at 70°F (0.2C° at 21°C)
NS-AHx700x-x, NS-BHx700x-0, and NS-MHx700x-x models: ±3% RH for 20to 80% RH; ±6% RH for 10 to 20% and
80 to 90% RH
With LCD display: 50.0°F/10.0°C to 86.0°F/30.0°C in 0.5° increments Without LCD display: ±5.0F°/±3.0C°
The performance specifications are no minal and co nform t o acceptab le ind ustry standar ds. For appl ications at condition s beyond these specifica tions, consult the local Johnson Co ntrols office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2016 Johnson Controls, Inc.
www.johnsoncontrols.com
5
NS Series Network Sensors (Continued)
NS Series Network Zone Sensors—Temperature Only Models and Temperature and Humidity Models (Part 2 of 2)
PIR Occupancy Sensor Motion Detection (Models with PIR Occupancy Sensor)
Ambient Conditions Operating: 32 to 104°F (0 to 40°C); 10 to 90% RH, noncondensing; 85°F (29°C) maximum dew point
Compliance BACnet
Accessory (Order Separately) NS-WALLPLATE-0 : adapts an 80 x 80 mm NS Series Network Zone Sensor to a standard 80 x 120 mm wallbox Shipping Weight 0.20 lb (0.09 kg)
International United States UL Listed, File E107041, CCN PAZX, Under UL 916, Energy Management Equipment;
Canada UL Listed, File E107041, CCN PAZX7, Under CAN/CSA C22.2 No. 205, Signal Equi pment;
Europe CE Mark – Johnson Controls, Inc., declares that this product is in compliance with the essential requirements and
Australia and New Zealand
NS Series Network Zone Sensors—Motion Detection Only Models (No Temperature or Humidity Sensing)
Supply Voltage 9.8 to 16.5 VDC; 15 VDC nominal (from SA bus) Current Consumption 13 mA maximum (non-transmitting) Terminations Modular jack or screw terminal block Sensor Addressing
(NS-MNN7003-0 Model) Wire Size Modular jack model: 24 AWG or 26 AWG (0.5 or 0.4 mm diameter) recommended; three twiste d p air (sixconductors)
Communication Rate Auto-detect: 9.6k, 19.2k, 38.4k, or 76.8k bps Mounting Surface-mounted or vertical wallbox-mounted: 120 x 80 mm PIR Occupancy Sensor
Motion Detection Ambient Conditions Operating: 32 to 104°F (0 to 40°C); 10 to 90% RH, noncondensing; 85°F (29°C) maximum dew point
Compliance BACnet
Shipping Weight 0.24 lb (0.11 kg)
Supply Voltage Non-isolated: 20 to 30 VAC (18 to 30 VDC), Class 2 or Safet y Extra-Low Voltage (SELV)
Current Consumption Non-isolated: 22 mA average at 24 VAC; 28 mA average at 24 VDC
Power Consumption Non-isolated: less than 0.7 W average Terminations Non-isolated supply: screw terminal block
Sensor Addressing DIP switch set from 212 to 219; factory set at 212 Wire Size Modular jack: 24 AWG or 26 AWG (0.5 or 0.4 mm diameter) recommended; three twisted pair (six conductors)
Communication Rate Auto-detect: 9.6k, 19.2k, 38.4k, or 76.8k bps
Measurement Range 0 to 2,000 ppm
CO
2
International United States UL Listed, File E107041, CCN PAZX, Under UL 916, Energy Management Equipment;
Canada UL Listed, File E107041, CCN PAZX7, Under CAN/CSA C22.2 No. 205, Signal Equi pment;
Europe CE Mark – Johnson Controls, Inc., declares that this product is in compliance with the essential requirements and
Australia and New Zealand
Minimum 94 angular degrees up to a distance of 15 ft (4.6 m); basedon a clear line of sight
Storage with LCD display: -4 to 140°F (-20 to 60°C); 5 to 95% RH, noncondensing Storage without LCD display: -40 to 158°F (-40 to 70°C); 5 to 95% RH, noncondensing
BACnet Testing Laboratories™ (BTL) 135-2004 Listed BACnet Smart Sensor (B-SS) Note: Excludes the NS-ATV70 0x-0 and NS-BTV700x-0 models.
FCC Compliant to CFR 47, Part 15, Subpart B, Class A Note: Excludes the NS-ATA7001-0A and NS-ATA7002-0A models (Asia Only)
Industry Canada, ICES-003 Note: Excludes the NS-ATA7001-0A and NS-ATA7002-0A models (Asia Only)
other relevant provisions of the EMC Directive 2004/108/EC. RCM Mark, Australia/NZ Emissions Compliant
DIP switch set from 200 to 203; factory set at 203
Screw terminal block model: 18 to 22 AWG (1.0 to 0.6 mm diameter); 22 AWG (0.6 mm diameter) recommended
Minimum 94 angular degrees up to a distance of 15 ft (4.6 m); basedon a clear line of sight
Storage: -40 to 158°F (-40 to 70°C); 5 to 95% RH, noncondensing BACnet Testing Laboratories™ (BTL) 135-2004 Listed BACnet Smart Sensor (B-SS)
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Industry Canada, ICES-003
other relevant provisions of the EMC Directive 2004/108/EC. RCM Mark, Australia/NZ Emissions Compliant
NS Series Network Zone Sensor—CO2 Models (Part 1 of 2)
Isolated: 9.8 to 16.5 VDC; 15 VDC nominal (from SA bus)
Isolated: 5 mA maximum, non-transmitting (from SA bus)
SA bus: modular jack or screw terminal block
Screw terminal block: 18 to 22 AWG (1.0 to 0.6 mm diameter); 22 AWG (0.6 mm diameter) recommended
The performance specifications are no minal and co nform t o acceptab le ind ustry standar ds. For appl ications at condition s beyond these specifica tions, consult the local Johnson Co ntrols office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2016 Johnson Controls, Inc.
www.johnsoncontrols.com
6
NS Series Network Sensors (Continued)
NS Series Network Zone Sensor—CO2 Models (Part 2 of 2)
CO2 Sensing Accuracy Plus or minus the sum of 40 ppm and 2.0% of the CO2 reading at 77°F (25°C) and 978hPa or an altitude of 1,000 ft/
Sensing Resolution 1 ppm
CO
2
CO
Sensing Response Time 1 minute (0 to 90%)
2
CO
Sensing Warm-Up Time Less than 1 minute; less than 10 minutes for full accuracy
2
Sensing Long-Term Stability Less than ±100 ppm over 5 years
CO
2
Mounting Surface-mounted or vertical wallbox-mounted: 120 x 80 mm Ambient Conditions Operating: 32 to 104°F (0 to 40°C); 10 to 90% RH, noncondensing; 85°F (29°C) maximum dew point; 700 to 1,200
Compliance BACnet
International United States UL Listed, File E107041 CCN PAZX, Under UL 916, Energy Management Equipment;
Canada UL Listed, File E107041, CCN PAZX7, Under CAN/CSA C22.2 No. 205, Signal Equipment; Industry Canada,
Europe CE Mark – Johnson Controls, Inc., declares that this product is in compliance with the essential requirements and
Australia and New Zealand
Shipping Weight 0.35 lb (0.16 kg)
Supply Voltage 9.8 to 16.5 VDC; 15 VDC Nominal (from SA bus) Current Consumption 12 mA maximum (non-transmitting) per flush-mount network sensor Terminations Screw terminal block
Sensor Addressing DIP switch set from 200 to 203; factory set at 203 Wire Size 18 to 22 AWG (1.0 to 0.6 mm diameter); 22 AWG (0.6 mm diameter) recommended;
Communication Rate Auto-detect: 9.6k, 19.2k, 38.4k, or 76.8k bps Temperature Measurement Range 32.0°F/0.0°C to 104.0°F/40.0°C Temperature Sensor Type Local 1k ohm Platinum Resistance Temperature Detector (RTD);
Temperature Accuracy NS Series Network Zone Sensor: ±1.0F°/±0.6C°
Ambient Conditions Operating: 32 to 104°F (0 to 40°C); 10 to 90% RH, noncondensing; 85°F (29°C) Maximum Dew Point
Compliance BACnet
International United States UL Listed, File E107041, CCN PAZX, Under UL 916, Energy Management Equipment;
Canada UL Listed, File E107041, CCN PAZX7, Under CAN/CSA C22.2 No. 205, Signal Equipme nt; Industry Canada, ICES-
Europe CE Mark – Johnson Controls, Inc., declares that this product is in compliance with the essential requirements and
Australia and New Zealand
Shipping Weight 0.25 lb (0.11 kg)
Supply Voltage 9.8 to 16.5 VDC; 15 VDC nominal Current Consumption 12 mA maximum (non-transmitting) per discharge air sensor Terminations Four color-coded wiring leads, stripped and tinned; factory-installedat the discharge air sensor screw terminal block Sensor Addressing DIP switch set from 204 to 211; factory set at 204 Wire Size 18 to 22 AWG (1.0 to 0.6 mm diameter); 22 AWG (0.6 mm diameter) recommended;
Communication Rate Auto-detect: 9.6k, 19.2k, 38.4k, or 76.8k bps
300 m Note: All accuracy specifications reflect the testing of the device using high-grade certified gases. This device is
intended for an altitude range of 0 ft/0 m to 2,000 ft/600 m above se a l evel without compensation.
Temperature dependence of output: -0.35% of the CO Pressure dependence of output: +0.15% of the CO
reading per 1.8F°/1C° typical
2
reading per 1 hPa typical
2
hPa Storage: -40 to 158°F (-40 to 70°C); 0 to 95% RH, noncondensing BACnet Testing Laboratories™ (BTL) 135-2004 Listed BACnet Sma rt Sensor (B-SS)
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
ICES-003
other relevant provisions of the EMC Directive 2004/108/EC. RCM Mark, Australia/NZ Emissions Compliant
NS Series Network Zone Sensor—Flush-Mount Temperature Only Models
Note: Wire leads are field supplied and are not tinned.
10 ft (304.8 cm) wiring lead Included with the unit
Class A per IEC 60751
Temperature Element Only: 0.35F° at 70°F (0.2C° at 21°C)
Storage: -40 to 158°F (-40 to 70°C); 5 to 95% RH, noncondensing
BACnet Testing Laboratories™ (BTL) 135-2004 Listed BACnet Sma rt Sensor (B-SS)
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
003
other relevant provisions of the EMC Directive 2004/108/EC. RCM Mark, Australia/NZ Emissions Compliant
NS Series Network Discharge Air Sensors (Part 1 of 2)
10 ft (305 cm) wiring lead included with the unit
The performance specifications are no minal and co nform t o acceptab le ind ustry standar ds. For appl ications at condition s beyond these specifica tions, consult the local Johnson Co ntrols office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2016 Johnson Controls, Inc.
www.johnsoncontrols.com
7
NS Series Network Sensors (Continued)
NS Series Network Discharge Air Sensors (Part 2 of 2)
Mounting Duct-mounted: 4 or 8 in. (102 or 203 mm) temperature probe length Temperature Measurement Range 14°F/-10°C to 140°F/60°C Temperature Sensor Type Local 1k ohm Platinum Resistance Temperature Detector (RTD);
Temperature Accuracy NS Series Network Discharge Air Sensor: ±1.0F°/±0.6C°
Ambient Conditions Operating: 14 to 140°F (-10 to 60°C); 10 to 90% RH, noncondensing; 85°F (29°C) Maximum Dew Point
Compliance BACnet
Shipping Weight NS-DTN7043-x: 1.15 lb (0.52 kg)
Supply Voltage 9.8 to 16.5 VDC; 15 VDC nominal (from SA bus) Current Consumption 21 mA maximum, non-transmitting (from SA bus) Network Sensor Addressing DIP switch set from 200 to 203; factory set at 203 Terminations Screw terminal block Screw Terminal Wire Size 18 to 22 AWG (1.0 to 6.0 mm Diameter); 22 AWG (0.6 mm diameter) recommended Communication Rate Auto-detect: 9.6k, 19.2k, 38.4k, or 76.8k bps Temperature Measurement Range 32.0°F/0.0°C to 104.0°F/40.0°C Temperature Sensor Type Local Platinum Resistance Temperature Detector (RTD) Temperature Resolution ±0.5F°/±0.5C° Temperature
Accuracy
Time Constant 10 minutes nominal at 10 fpm airflow Default Temperature Setpoint
Adjustment Range Ambient
Conditions
Compliance United States UL Listed, File E107041, CCN PAZX,
Dimensions (Height x Width x Depth) NS-ATBF703-x: 3-5/32 x 3-5/32 x 1-3/8 in. (80 x 80 x 35 mm)
Shipping Weight 0.25 lb (0.11 kg)
International United States UL Listed, File E107041, CCN PA ZX , Under UL 916, Energy Management Equipment;
Canada UL Listed, File E107041, CCN PAZX7, Under CAN/CSA C22.2 No. 205, Signal Equipment; Industry Canada,
Europe CE Mark – Johnson Controls, Inc., declares that this product is in compliance with the essential requirements and
Australia and New Zealand
NS Series Network Sensor
Temperature Element Only
Operating 32 to 104°F (0 to 40°C); 10 to 90% RH, noncondensing;
Storage -4 to 140°F (-20 to 60°C); 5 to 95% RH, noncondensing
Canada UL Listed, File E107041, CCN PAZX7,
Europe CE Mark – JohnsonControls, Inc., declares that this product is in compliance with the essential requirements and
Australia and New Zealand
Class A per IEC 60751
Temperature element only: 0.35F° at 70°F (0.2C° at 21°C)
Storage: -40 to 158°F (-40 to 70°C); 5 to 95% RH, noncondensing
BACnet Testing Laboratories™ (BTL) 135-2004 Listed BACnet Smart Sensor (B-SS)
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
ICES-003
other relevant provisions of the EMC Directive 2004/108/EC. RCM Mark, Australia/NZ Emissions Compliant
NS-DTN7083-x: 1.17 lb (0.53 kg)
NS Series Network Sensors with Fault Code Capability
±1.0F°/±0.6C°
0.35F° at 70°F (0.2C° at 21°C)
50.0°F/10.0°C to 86.0°F/30.0°C in 0.5° increments
85°F (29°C) maximum dew point
Under UL 916, Energy Management Equipment FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Under CAN/CSA C22.2 No. 205, Signal Equipment Industry Canada, ICES-003
other relevant provisions of the EMC Directive 2004/108/EC. RCM Mark, Australia/NZ Emissions Compliant
NS-BTB7F03-x: 4-23/32 x 3-5/32 x 1-3/8 in. (120 x 80 x 35 mm)
The performance specifications are no minal and co nform t o acceptab le ind ustry standar ds. For appl ications at condition s beyond these specifica tions, consult the local Johnson Co ntrols office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2016 Johnson Controls, Inc.
www.johnsoncontrols.com
8
NS Series Network Sensors (Continued)
European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact:
JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY
JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA
JOHNSON CONTROLS C/O CONTROLS PRODUCT MANAGEMENT NO. 22 BLOCK D NEW DISTRICT WUXI JIANGSU PROVINCE 214142 CHINA
The performance specifications are no minal and co nform t o acceptab le ind ustry standar ds. For appl ications at condition s beyond these specifica tions, consult the local Johnson Co ntrols office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2016 Johnson Controls, Inc.
www.johnsoncontrols.com
9
Loading...