Johnson Controls NS Series, NS-MTJ700 Series, NS-MTB7001-0, NS-MHB7004-2, NS-MTB7002-0 Installation Instructions Manual

...
Page 1
Vertical Wallbox-Mounted or Surface-Mounted Occupancy
24- 10094-41, Rev. F
Sensing NS Series Network Sensors with LCD
Installation Instructions
NS-MHB7004-2, NS-MTB7001-0, NS-MTB7002-0,
Part No. 24-10094-41, Rev. F
Issued January 2017
NS-MTB7004-2, NS-MTJ700x-x
Refer to the QuickLIT website for the most up-to-date version of this document.

Applications

The vertical wallbox-mounted or surface-mounted occupancy sensing NS Series Network Sensor with LCD is an electronic zone sensor designed to function directly with Johnson Controls® BACnet® Master-Slave/Token­Passing (MS/TP) digital controllers in HVAC systems. Models in this series monitor the temperature setpoint and zone temperature, and transmit this data to a field controller on the Sensor Actuator (SA) Bus.
All models include an onboard passive infrared (PIR) occupancy sen sor that detects motion to de termine if a space is occupied. This feature maximizes up to 30% energy savings in high-energy usage environmen ts such as schools, residence halls, offices, hospitals, and hotels by adjusting the temperature of the space based on the occupancy status. In addition, the PIR occupancy sensor facilitates trending of floor space usage in these environments.
An LCD and, depending on the model, either a temperature setpoint dial or setpoint adjustment buttons are featured on all models to make adjusting the temperature setpoint and viewing the zone temperature easier.
A °F/°C pushbutton is available on all models to provide temperature scale options for display. An occupancy override function is featured on all models, which allows you to signal th e controller that the sp ace is occupied or to request an override of time-of-day scheduling. Rotating the setpoint dial or pressing either setpoint adjustment button signals occupancy. See Temperature Setpoint Adjustment/Occupancy Override
Depending on the model chosen, you can terminate the wires that connect the network sensor to the controller using either a modular jack or screw terminal block, which offers wiring flexibility.
for more information.
Note: The model featuring a modular jack is not i ntended fo r installations where daisy chaining to the MS/TP Bus is required.
All models include an SA Bus access port for connecting accessories to access the SA Bus. This feature allows a technician to commission or service the controller through the network senso r.
Note: Since some NS Series Network Sensor features are not supported in previous releases of Metasys® or Facility Explorer system software, we recommend that you keep the system software up to date.
IMPORTANT: The occupancy sensing NS Series Network Sensor is intended to provide an input to equipmen t under normal operating conditions. Where failure or malfunction of the network sensor could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the network sensor.
IMPORTANT: Le occupancy sensing NS Series Network Sensor est destiné à transmettre des données entrantes à un équipement dans des conditions normales de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du network sensor risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de limit ation, ayant une fonction d'avertisseme nt ou de protection en cas de défaillance ou de dysfonctionnement du network sensor.
Vertical Wallbox-Mounted or Surface-Mounted Occupancy Sensing NS
Series Network Sensors with LCD Installation Instructions
1
Page 2

North American Emissions Compliance

United States

This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not inst alled a nd used in accordan ce with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area may cause harmful interference, in which case users will be required to correct the interference at their own expense.

Canada

This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.

Installation

Special Tools Needed

A 1/16 in. (1.5 mm) Allen wrench or a Johnson Controls T-4000-119 Allen-Head Adjustment Tool is required during installation.

Mounting

Note: For wallbox-mounted installations, the occupancy sensing NS Series Network Sensor is intended to be
mounted on a vertically roughed-in wallbox only; do not attempt to mount the network sensor on a horizontally roughed-in wallbox.

Location Considerations

Locate the network sensor:
on a partitioning wall, approximately 5 ft (1.5 m) above the floor in a location of average temperature
away from direct sunlight, radiant heat, outside walls, outside doors, air discharge grills, or stairwells; and from behind doors
away from steam or water pipes, warm air stacks, unconditioned areas (not heated or cooled), or sources of electrical interference
in a clear path between the PIR occupancy sensor and the space being monitored
Note: The network sensor is shock and vibration resistant; however, be careful not to drop the unit or mount it where it could be exposed to excessive vibration.
The following ambient operating conditions apply:
Temperature: 32 to 104°F (0 to 40°C)
Humidity: 10 to 90% Relative Humidity (RH), noncondensing; 85°F (29°C) maximum dew point
To mount the network sensor:
1. Use a 1/16 in. (1.5 mm) Allen wrench or Johnson Controls T-4000-119 Allen-Head Adjustment Tool to loosen the security screw on the top of the unit.
2. Insert a coin into the slot next to the security screw location, then carefully pry the top edge of the sensor assembly away from its mounting base and remove.
IMPORTANT: Do not remove the Printed Circuit Board (PCB). Removing the PCB voids the product warranty.
Vertical Wallbox-Mounted or Surface-Mounted Occupancy Sensing NS Series Network Sen sors with LCD
Installation Instructions
2
Page 3
3. For vertical wallbox-mounted installations, proceed to Step 4. For surface-mounted installations, proceed to Step 7.
4. Pull out approximately 6 in. (152 mm) of cab le fro m the wallbo x an d ins er t the cab le th ro ug h the ho le in the mounting base.
5. Align the mounting base on the wallbox.
Note: Confirm that the mounting base is positioned with the proper edge up. The mounting base is positioned properly when the security screw is located on the top edge of the base.
6. Secure the mounting base to the wallbox using the two No. 6 pan- head mounting screws in cluded with the unit. Proceed to Step 9.
7. Align the mounting base on the wall and use the base as a template to mark the location of the two mounting holes on the surface.
Note: Confirm that the mounting base is positioned with the proper edge up. The mounting base is positioned properly when the security screw is located on the top edge of the base.
8. Secure the mounting base to the wall using the appropriate mounting hardware (field furnished). Proceed to Step 9.
9. Wire the network sensor. For more details on wiring the MS/TP Communications Bus, refer to the MS/TP
Communications Bus Technical Bulletin (LIT-12011034) or the FX-PC Series Controllers MS/TP Communications Bus Technical Bulletin (LIT-12011670).
For the model featuring a modular jack, simply snap the wiring plug into the jack. See Figure 1 for modular jack pin number assignments. The modular jack model requires a straight- through, one-to-one connection (not a crossover). For the model featuring a screw terminal block, wire the unit as illustrated in Figure 2.
Risk of Electric Shock.
Disconnect the power supply before making electrical connections to avoid electric shock.
Risque de décharge électrique.
Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de décharge électrique.
IMPORTANT: Failure to adhere to these wiring details causes the ne twork sensor to function incorrectly. You will not be able to connect to the system using the wireless commissioning converter or the handheld VAV balancing tool, and you will not be able to expand the system with future offerings.
Vertical Wallbox-Mounted or Surface-Mounted Occupancy Sensing NS Series Network Sen sors with LCD
Installation Instructions
3
Page 4
Figure 1: Modular Jack Pin Number Assignments
Pin Numb er Assign m ent for
Straight - Through Cab le
Printed C i r c ui t Board
SA Powe
r (Network
Sensor)
2
3
45
6
1
FIG:mdlr_jck
S
A
+
S
A
-
SA B
us
Com
mo
n
(Tool
A
cces
s)
S
A
P
ower
(T
oo
l
A
cc
ess
)
Main
Network
Port
S
A
Bus Co
m
m
o
n
(
Ne
t
work
Sensor)
Figure 2: Wiring to the Screw Terminal Block
FIG:scrw_t rmnl_blck
10. Align the tabs on the bottom edge of the mounting base with the slots on the bottom edge of the network sensor assembly and rotate the assembly onto its mounting base.
Note: On the model featuring a screw terminal block, be cer t ain that the te rminal block pins align with the holes in the terminal block.
11. Use a 1/16 in. (1.5 mm) Allen wrench or Johnson Controls T-4000-119 Allen-Head Adjustment Tool to tighten the security screw and fasten the network sensor assembly to the mounting base.
Note: Do not overtighten the security screw to avoid damaging the unit.
12. Before use, clean the lens of the PIR occupancy sensor with a soft, dry cloth.
Note: Do not use water or other solvents to clean the lens.
Vertical Wallbox-Mounted or Surface-Mounted Occupancy Sensing NS Series Network Sen sors with LCD
Installation Instructions
4
Page 5
13. Use the Metasys Controller Configuration Tool (CCT) or Facility Explorer Programmable Controller Tool
Figure 3: LCD on Temperature Only Models
Celsius Temperature
FIG:lcd_wo _fn
(FX-PCT) software to commission the network sensor. Refer to the Controller Tool Help (LIT-12011147) for more details.

Setup and Adjustments

°C °F
Loss of Network Connecti on Symbol

Temperature Setpoint Adjustment/Occupancy Override

Depending on the model, you can use either the large temperature setpoint adjustment dial or the temperature setpoint adjustment buttons on the face of the network sensor to change the controller mode from unoccupied to occupied, or to adjust the temperature setpoint.
To change the occupancy mode using the dial, rotate the dial slightly, so the backlight on the LCD lights up. If you rotate the dial slightly again and the controller is in the unoccupied mode, the controller changes from the after-normal-working-hours setback mode to the normal-working-hours comfort mode. Alternatively, you can use the pushbuttons to change the controller mode from unoccupied to occupied.
To adjust the setpoint using the dial, continue rotating the dial until the current setpoint is displayed and flashing. Turn the dial clockwise to increa se the setpoint a nd counterclockwise to de crease the setpoint. Stop turning the dial once the preferred setpoint is reached. The new se tpoint stops flashin g and be comes fixed a f ter a few second s. To use the pushbuttons instead, press the up arrow button to increase the setpoint or the down arrow to decrease it.

°F/°C Temperature Mode Selection

All models include a °F/°C pushbutton on the face of the network sensor to provide temperature scale options for display. Pressing the pushbutton toggles the temperature mode between Fahrenheit and Celsius on the LCD.
Fahrenheit Temperature
Occupied/Unoccupi ed Mode

Network Sensor Addressing

All occupancy sensing NS Series Network Sensors with LCD have a default device address of 199 on the SA Bus.

Repair Information

If the occupancy sensing NS Series Network Sensor fails to operate within its specifications, replace the unit. For a replacement network sensor, contact the nearest Johnson Controls representative.
Vertical Wallbox-Mounted or Surface-Mounted Occupancy Sensing NS Series Network Sen sors with LCD
Installation Instructions
5
Page 6

Technical Specifications

Vertical Wallbox-Mounted or Surface-Mounted Occupancy Sensing NS Series Network Sensors with LCD (Part 1 of 2)
Supply Voltage 9.8 to 16.5 VDC; 15 VDC nominal (from SA Bus) Current Consumption 21 mA maximum (non-transmitting) Terminations Modular jack or screw terminal block Network Sensor Addressing Fixed address of 199 Wire Size Modular Jack
Models Screw Terminal
Block Models
Communication Rate Auto-detect: 9.6k, 19.2k, 38.4k, or 76.8k bps Temperature Measurement
Range Temperature Sensor Type Local 1k Ohm platinum resistance temperature detector (RTD); Class A per IEC 60751 Temperature Resolution ±0.5F°/±0.5C° Temperature
Accuracy
Humidity Accuracy
Time Constant 10 minutes nominal at 10 fpm airflow Default Temperature Setpoint
Adjustment Range PIR Occupancy Sensor
Motion Detection Ambient
Conditions
NS Series Network Zone Sensor
T emperature Element Only
NS-MHB7004-x Models
Operating 32 to 104°F (0 to 40°C); 10 to 90% RH, noncondensing;
Storage -4 to 140°F (-20 to 60°C); 5 to 95% RH, noncondensing
24 or 26 AWG (0.5 or 0.4 mm diameter); three twisted pair (six conductors)
18 to 22 AWG (1.0 to 0.6 mm diameter); 22 AWG (0.6 mm diameter) recommended
32.0°F/0.0°C to 104.0°F/40.0°C
±1.0F°/±0.6C°
0.35F° at 70°F (0.2C° at 21°C)
±3% RH for 20% to 80% RH at 77°F (25°C); ±6% RH for 10% to 20% RH and 80% to 90% RH at 77°F (25°C)
50.0°F/10.0°C to 86.0°F/30.0°C in 0.5° increments
Minimum 94 Angular Degrees up to a distance of 15 ft (4.6 m); based on a clear line of sight
85°F (29°C) Maximum Dew Point
Vertical Wallbox-Mounted or Surface-Mounted Occupancy Sensing NS Series Network Sen sors with LCD
Installation Instructions
6
Page 7
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls.
All other marks herein are the marks of their respective owners. © 2017 Johnson Controls.
Building Technologies & Solutions
507 E. Michigan Street, Milwaukee, WI 53202
Vertical Wallbox-Mounted or Surface-Mounted Occupancy Sensing NS Series Network Sensors with LCD (Part 2 of 2)
Compliance BACnet
International United States UL Listed, File E107041, CCN PAZX,
Canada UL Listed, File E107041, CCN PAZX7,
Europe CE Mark – Johnson Controls declares that this product is in compliance
Australia and New Zealand
Dimensions (Height x Width x Depth)
Shipping Weight 0.24 lb (0.11 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damage resulting from misapplication or misuse of its products.
European Single Point of Contact: NA/SA Single Point of Contact: AP AC Single Point of Contact:
JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY
BACnet Testing Laboratories™ (BTL) 135-2004 Listed BACnet Smart Sensor (B-SS)
Under UL 916, Energy Management Equipment FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Under CAN/CSA C22.2 No. 205, Signal Equipment Industry Canada, ICES-003
with the essential requirements and other releva nt provisions of the EMC Directive. Regulatory Compliance Mark (RCM), Australia/NZ Emissions Compliant
4-23/32 x 3-5/32 x 1-3/8 in. (120 x 80 x 35 mm)
JOHNSON CONTROLS 507 E MICHIGAN ST MIL WAUKEE WI 53202 USA
JOHNSON CONTROLS C/O CONTROLS PRODUCT MANAGEMENT NO. 22 BLOCK D NEW DISTRICT WUXI JIANGSU PROVINCE 214142 CHINA
Vertical Wallbox-Mounted or Surface-Mounted Occupancy Sensing NS Series Network Sensors with LCD
Installation Instructions
Published in U.S.A. www.johnsoncontrols.com
7
Loading...