Vertical Wallbox-Mounted or Surface-Mounted Occupancy
24- 10094-41, Rev. F
Sensing NS Series Network Sensors with LCD
Installation Instructions
NS-MHB7004-2, NS-MTB7001-0, NS-MTB7002-0,
Part No. 24-10094-41, Rev. F
Issued January 2017
NS-MTB7004-2, NS-MTJ700x-x
Refer to the QuickLIT website for the most up-to-date version of this document.
Applications
The vertical wallbox-mounted or surface-mounted occupancy sensing NS Series Network Sensor with LCD is an
electronic zone sensor designed to function directly with Johnson Controls® BACnet® Master-Slave/TokenPassing (MS/TP) digital controllers in HVAC systems. Models in this series monitor the temperature setpoint and
zone temperature, and transmit this data to a field controller on the Sensor Actuator (SA) Bus.
All models include an onboard passive infrared (PIR) occupancy sen sor that detects motion to de termine if a space
is occupied. This feature maximizes up to 30% energy savings in high-energy usage environmen ts such as
schools, residence halls, offices, hospitals, and hotels by adjusting the temperature of the space based on the
occupancy status. In addition, the PIR occupancy sensor facilitates trending of floor space usage in these
environments.
An LCD and, depending on the model, either a temperature setpoint dial or setpoint adjustment buttons are
featured on all models to make adjusting the temperature setpoint and viewing the zone temperature easier.
A °F/°C pushbutton is available on all models to provide temperature scale options for display. An occupancy
override function is featured on all models, which allows you to signal th e controller that the sp ace is occupied or to
request an override of time-of-day scheduling. Rotating the setpoint dial or pressing either setpoint adjustment
button signals occupancy. See Temperature Setpoint Adjustment/Occupancy Override
Depending on the model chosen, you can terminate the wires that connect the network sensor to the controller
using either a modular jack or screw terminal block, which offers wiring flexibility.
for more information.
Note: The model featuring a modular jack is not i ntended fo r installations where daisy chaining to the MS/TP Bus
is required.
All models include an SA Bus access port for connecting accessories to access the SA Bus. This feature allows a
technician to commission or service the controller through the network senso r.
Note: Since some NS Series Network Sensor features are not supported in previous releases of Metasys® or
Facility Explorer system software, we recommend that you keep the system software up to date.
IMPORTANT: The occupancy sensing NS Series Network Sensor is intended to provide an input to equipmen t
under normal operating conditions. Where failure or malfunction of the network sensor could lead to personal
injury or property damage to the controlled equipment or other property, additional precautions must be
designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems
or safety or limit controls, intended to warn of or protect against failure or malfunction of the network sensor.
IMPORTANT: Le occupancy sensing NS Series Network Sensor est destiné à transmettre des données
entrantes à un équipement dans des conditions normales de fonctionnement. Lorsqu'une défaillance ou un
dysfonctionnement du network sensor risque de provoquer des blessures ou d'endommager l'équipement
contrôlé ou un autre équipement, la conception du système de contrôle doit intégrer des dispositifs de protection
supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes
de supervision ou d'alarme, ou des dispositifs de sécurité ou de limit ation, ayant une fonction d'avertisseme nt ou
de protection en cas de défaillance ou de dysfonctionnement du network sensor.
Vertical Wallbox-Mounted or Surface-Mounted Occupancy Sensing NS
Series Network Sensors with LCD Installation Instructions
1
Page 2
North American Emissions Compliance
United States
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to
Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference when this equipment is operated in a commercial environment. This equipment generates, uses,
and can radiate radio frequency energy and, if not inst alled a nd used in accordan ce with the instruction manual,
may cause harmful interference to radio communications. Operation of this equipment in a residential area may
cause harmful interference, in which case users will be required to correct the interference at their own expense.
Canada
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment
Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur
du Canada.
Installation
Special Tools Needed
A 1/16 in. (1.5 mm) Allen wrench or a Johnson Controls T-4000-119 Allen-Head Adjustment Tool is required during
installation.
Mounting
Note: For wallbox-mounted installations, the occupancy sensing NS Series Network Sensor is intended to be
mounted on a vertically roughed-in wallbox only; do not attempt to mount the network sensor on a horizontally
roughed-in wallbox.
Location Considerations
Locate the network sensor:
•on a partitioning wall, approximately 5 ft (1.5 m) above the floor in a location of average temperature
•away from direct sunlight, radiant heat, outside walls, outside doors, air discharge grills, or stairwells; and from
behind doors
•away from steam or water pipes, warm air stacks, unconditioned areas (not heated or cooled), or sources of
electrical interference
•in a clear path between the PIR occupancy sensor and the space being monitored
Note: The network sensor is shock and vibration resistant; however, be careful not to drop the unit or mount it
where it could be exposed to excessive vibration.
The following ambient operating conditions apply:
•Temperature: 32 to 104°F (0 to 40°C)
•Humidity: 10 to 90% Relative Humidity (RH), noncondensing; 85°F (29°C) maximum dew point
To mount the network sensor:
1. Use a 1/16 in. (1.5 mm) Allen wrench or Johnson Controls T-4000-119 Allen-Head Adjustment Tool to loosen
the security screw on the top of the unit.
2. Insert a coin into the slot next to the security screw location, then carefully pry the top edge of the sensor
assembly away from its mounting base and remove.
IMPORTANT: Do not remove the Printed Circuit Board (PCB). Removing the PCB voids the product warranty.
Vertical Wallbox-Mounted or Surface-Mounted Occupancy Sensing NS Series Network Sen sors with LCD
Installation Instructions
2
Page 3
3. For vertical wallbox-mounted installations, proceed to Step 4. For surface-mounted installations, proceed to
Step 7.
4. Pull out approximately 6 in. (152 mm) of cab le fro m the wallbo x an d ins er t the cab le th ro ug h the ho le in the
mounting base.
5. Align the mounting base on the wallbox.
Note: Confirm that the mounting base is positioned with the proper edge up. The mounting base is positioned
properly when the security screw is located on the top edge of the base.
6. Secure the mounting base to the wallbox using the two No. 6 pan- head mounting screws in cluded with the unit.
Proceed to Step 9.
7. Align the mounting base on the wall and use the base as a template to mark the location of the two mounting
holes on the surface.
Note: Confirm that the mounting base is positioned with the proper edge up. The mounting base is positioned
properly when the security screw is located on the top edge of the base.
8. Secure the mounting base to the wall using the appropriate mounting hardware (field furnished). Proceed to
Step 9.
9. Wire the network sensor. For more details on wiring the MS/TP Communications Bus, refer to the MS/TP
Communications Bus Technical Bulletin (LIT-12011034) or the FX-PC Series Controllers MS/TP
Communications Bus Technical Bulletin (LIT-12011670).
For the model featuring a modular jack, simply snap the wiring plug into the jack. See Figure 1 for modular jack
pin number assignments. The modular jack model requires a straight- through, one-to-one connection (not a
crossover). For the model featuring a screw terminal block, wire the unit as illustrated in Figure 2.
Risk of Electric Shock.
Disconnect the power supply before making electrical connections to avoid electric shock.
Risque de décharge électrique.
Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de décharge
électrique.
IMPORTANT: Failure to adhere to these wiring details causes the ne twork sensor to function incorrectly. You
will not be able to connect to the system using the wireless commissioning converter or the handheld VAV
balancing tool, and you will not be able to expand the system with future offerings.
Vertical Wallbox-Mounted or Surface-Mounted Occupancy Sensing NS Series Network Sen sors with LCD
Installation Instructions
3
Page 4
Figure 1: Modular Jack Pin Number Assignments
Pin Numb er Assign m ent for
Straight - Through Cab le
Printed C i r c ui t Board
SA Powe
r (Network
Sensor)
2
3
45
6
1
FIG:mdlr_jck
S
A
+
S
A
-
SA B
us
Com
mo
n
(Tool
A
cces
s)
S
A
P
ower
(T
oo
l
A
cc
ess
)
Main
Network
Port
S
A
Bus Co
m
m
o
n
(
Ne
t
work
Sensor)
Figure 2: Wiring to the Screw Terminal Block
FIG:scrw_t rmnl_blck
10. Align the tabs on the bottom edge of the mounting base with the slots on the bottom edge of the network
sensor assembly and rotate the assembly onto its mounting base.
Note: On the model featuring a screw terminal block, be cer t ain that the te rminal block pins align with the holes in
the terminal block.
11. Use a 1/16 in. (1.5 mm) Allen wrench or Johnson Controls T-4000-119 Allen-Head Adjustment Tool to tighten
the security screw and fasten the network sensor assembly to the mounting base.
Note: Do not overtighten the security screw to avoid damaging the unit.
12. Before use, clean the lens of the PIR occupancy sensor with a soft, dry cloth.
Note: Do not use water or other solvents to clean the lens.
Vertical Wallbox-Mounted or Surface-Mounted Occupancy Sensing NS Series Network Sen sors with LCD
Installation Instructions
4
Page 5
13. Use the Metasys Controller Configuration Tool (CCT) or Facility Explorer Programmable Controller Tool
Figure 3: LCD on Temperature Only Models
Celsius Temperature
FIG:lcd_wo _fn
(FX-PCT) software to commission the network sensor. Refer to the Controller Tool Help (LIT-12011147) for
more details.
Setup and Adjustments
°C
°F
Loss of Network Connecti on Symbol
Temperature Setpoint Adjustment/Occupancy Override
Depending on the model, you can use either the large temperature setpoint adjustment dial or the temperature
setpoint adjustment buttons on the face of the network sensor to change the controller mode from unoccupied to
occupied, or to adjust the temperature setpoint.
To change the occupancy mode using the dial, rotate the dial slightly, so the backlight on the LCD lights up. If you
rotate the dial slightly again and the controller is in the unoccupied mode, the controller changes from the
after-normal-working-hours setback mode to the normal-working-hours comfort mode. Alternatively, you can use
the pushbuttons to change the controller mode from unoccupied to occupied.
To adjust the setpoint using the dial, continue rotating the dial until the current setpoint is displayed and flashing.
Turn the dial clockwise to increa se the setpoint a nd counterclockwise to de crease the setpoint. Stop turning the dial
once the preferred setpoint is reached. The new se tpoint stops flashin g and be comes fixed a f ter a few second s. To
use the pushbuttons instead, press the up arrow button to increase the setpoint or the down arrow to decrease it.
°F/°C Temperature Mode Selection
All models include a °F/°C pushbutton on the face of the network sensor to provide temperature scale options for
display. Pressing the pushbutton toggles the temperature mode between Fahrenheit and Celsius on the LCD.
Fahrenheit Temperature
Occupied/Unoccupi ed Mode
Network Sensor Addressing
All occupancy sensing NS Series Network Sensors with LCD have a default device address of 199 on the SA Bus.
Repair Information
If the occupancy sensing NS Series Network Sensor fails to operate within its specifications, replace the unit. For a
replacement network sensor, contact the nearest Johnson Controls representative.
Vertical Wallbox-Mounted or Surface-Mounted Occupancy Sensing NS Series Network Sen sors with LCD
Installation Instructions
5
Page 6
Technical Specifications
Vertical Wallbox-Mounted or Surface-Mounted Occupancy Sensing NS Series Network Sensors
with LCD (Part 1 of 2)
Supply Voltage9.8 to 16.5 VDC; 15 VDC nominal (from SA Bus)
Current Consumption21 mA maximum (non-transmitting)
TerminationsModular jack or screw terminal block
Network Sensor AddressingFixed address of 199
Wire SizeModular Jack
Models
Screw Terminal
Block Models
Communication RateAuto-detect: 9.6k, 19.2k, 38.4k, or 76.8k bps
Temperature Measurement
Range
Temperature Sensor TypeLocal 1k Ohm platinum resistance temperature detector (RTD); Class A per IEC 60751
Temperature Resolution±0.5F°/±0.5C°
Temperature
Accuracy
Humidity
Accuracy
Time Constant10 minutes nominal at 10 fpm airflow
Default Temperature Setpoint
Adjustment Range
PIR Occupancy Sensor
Motion Detection
Ambient
Conditions
NS Series
Network Zone
Sensor
T emperature
Element Only
NS-MHB7004-x
Models
Operating32 to 104°F (0 to 40°C); 10 to 90% RH, noncondensing;
Storage-4 to 140°F (-20 to 60°C); 5 to 95% RH, noncondensing
24 or 26 AWG (0.5 or 0.4 mm diameter); three twisted pair (six conductors)
18 to 22 AWG (1.0 to 0.6 mm diameter); 22 AWG (0.6 mm diameter) recommended
32.0°F/0.0°C to 104.0°F/40.0°C
±1.0F°/±0.6C°
0.35F° at 70°F (0.2C° at 21°C)
±3% RH for 20% to 80% RH at 77°F (25°C);
±6% RH for 10% to 20% RH and 80% to 90% RH at 77°F (25°C)
50.0°F/10.0°C to 86.0°F/30.0°C in 0.5° increments
Minimum 94 Angular Degrees up to a distance of 15 ft (4.6 m);
based on a clear line of sight
85°F (29°C) Maximum Dew Point
Vertical Wallbox-Mounted or Surface-Mounted Occupancy Sensing NS Series Network Sen sors with LCD
Installation Instructions
6
Page 7
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls.
Vertical Wallbox-Mounted or Surface-Mounted Occupancy Sensing NS Series Network Sensors
with LCD (Part 2 of 2)
ComplianceBACnet
International
United StatesUL Listed, File E107041, CCN PAZX,
CanadaUL Listed, File E107041, CCN PAZX7,
EuropeCE Mark – Johnson Controls declares that this product is in compliance
Australia and
New Zealand
Dimensions
(Height x Width x Depth)
Shipping Weight0.24 lb (0.11 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damage resulting from misapplication or
misuse of its products.
European Single Point of Contact:NA/SA Single Point of Contact:AP AC Single Point of Contact:
Under UL 916, Energy Management Equipment
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Under CAN/CSA C22.2 No. 205, Signal Equipment
Industry Canada, ICES-003
with the essential requirements and other releva nt provisions of the EMC Directive.
Regulatory Compliance Mark (RCM), Australia/NZ Emissions Compliant
4-23/32 x 3-5/32 x 1-3/8 in.
(120 x 80 x 35 mm)
JOHNSON CONTROLS
507 E MICHIGAN ST
MIL WAUKEE WI 53202
USA
JOHNSON CONTROLS
C/O CONTROLS PRODUCT MANAGEMENT
NO. 22 BLOCK D NEW DISTRICT
WUXI JIANGSU PROVINCE 214142
CHINA
Vertical Wallbox-Mounted or Surface-Mounted Occupancy Sensing NS Series Network Sensors with LCD
Installation Instructions
Published in U.S.A.www.johnsoncontrols.com
7