Johnson Controls NS Series, NS-ATB7F03 Series, NS-BTB7F03 Series, NS-ATB7F03-0, NS-ATB7F03-1 Installation Instructions Manual

...
NS Series Network Sensors with Fault Code Capability
24- 10094-76, Rev. C
Installation Instructions
NS-ATB7F03-x, NS-BTB7F03-x
Part No. 24-10094-76, Rev. C
Issued March 2016

Applications

The surface-mounted NS Series Network Sensor with Fault Code Capability is an electronic zone sensor designed to function directly with Johnson Controls® BACnet® MS/TP digital controllers in HVAC systems. Models in this series monitor the temperature setpoint and zone temperature and transmit this data to a field controller on the Sensor Actuator (SA) Bus.
This sensor is designed to assist with the California Energy Code (Title 24), providing a visual indication of operational faults with rooftop equipment. The NS Series sensor displays codes that may indicate the system is operating inefficiently. Fault codes include air temperature sensor failure or fault, not economizing properly, economizer return air, economizer not using outdoor air, outdoor air not suitable, and damper not modulating. See Table 2 for additional Fault Code information.
You may adjust the setpoint while the sensor displays the fault. You must reset the fault at the equipment controller. The sensor cannot reset the fault.
All models feature a temperature setpoint dial and
LCD designed to make adjusting the temperature
setpoint and viewing the zone temperature easier.
A °F/°C push button is available on certain models to provide temperature scale options for display. An occupancy override function is featured on all models, which allows the user to signal the controller that the space is occupied, to request an override of time-of-day scheduling. Rotating the setpoint dial signals occupancy. See Temperature Setpoint
Adjustment/Occupancy Override/Fault Temporary Override for more information.
All models include an SA Bus access port for connecting accessories to access the SA Bus. This feature allows a technician to commission or service the controller via the network sensor.
IMPORTANT: The surface-mounted NS Series Network Sensor with Fault Code Capability is intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the network sensor could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the network sensor.
IMPORTANT : Le surface-mounted NS Series Network Sensor with Fault Code Capability est destiné à transmettre des données entrantes à un équipement dans des conditions normales de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du network sensor risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du network sensor.
NS Series Network Sensors with Fault Code Capability Installation Instructions 1

North American Emissions Compliance

!

United States

This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area may cause harmful interference, in which case the users will be required to correct the interference at their own expense.

Canada

The following ambient operating conditions apply:
Temperature: 32 to 104°F (0 to 40°C)
Humidity: 10 to 90% Relative Humidity (RH), noncondensing; 85°F (29°C) maximum dew point
To mount the network sensor to the wall:
1. Use a 1/16 in. (1.5 mm) Allen wrench or Johnson Controls T-4000-119 Allen-Head Adjustment Tool to loosen the security screw on the top of the unit.
2. Insert a coin into the slot next to the security screw location, then carefully pry the top edge of the sensor assembly away from its mounting base and remove.
IMPORTANT: Do not remove the Printed Circuit Board (PCB). Removing the PCB voids the product warranty.
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.

Installation

Special Tools Needed

A 1/16 in. (1.5 mm) Allen wrench or a Johnson Controls T-4000-119 Allen-Head Adjustment Tool is required during installation.

Mounting

Location Considerations

Locate the network sensor:
on a partitioning wall, approximately 5 ft (1.5 m) above the floor in a location of average temperature
away from direct sunlight, radiant heat, outside walls, outside doors, air discharge grills, or stairwells; and from behind doors
away from steam or water pipes, warm air stacks, unconditioned areas (not heated or cooled), or sources of electrical interference
Note: The network sensor is shock and vibration resistant; however, be careful not to drop the unit or mount it where it could be exposed to excessive vibration.
3. Pull out approximately 6 in. (152 mm) of cable from the wall, and insert the cable through the hole in the mounting base.
4. Align the mounting base on the wall, and use the base as a template to mark the location of the two mounting holes on the surface.
Note: Confirm that the mounting base is positioned with the proper edge up. The mounting base is positioned properly when the security screw is located on the top edge of the base.
5. Secure the mounting base to the wall using the appropriate mounting hardware (field furnished).
6. Wire the network sensor. For more details on wiring the MS/TP Communications Bus, refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034).
Wire the screw terminal block as illustrated in Figure 2.
CAUTION: Risk of Electric Shock.
Disconnect the power supply before making electrical connections to avoid electric shock.
MISE EN GARDE : Risque de décharge électrique.
Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de décharge électrique.
NS Series Network Sensors with Fault Code Capability Installation Instructions2
Loading...
+ 4 hidden pages