NS Series Network Sensors with Fault Code Capability
24- 10094-76, Rev. C
Installation Instructions
NS-ATB7F03-x, NS-BTB7F03-x
Part No. 24-10094-76, Rev. C
Issued March 2016

Applications

The surface-mounted NS Series Network Sensor with Fault Code Capability is an electronic zone sensor designed to function directly with Johnson Controls® BACnet® MS/TP digital controllers in HVAC systems. Models in this series monitor the temperature setpoint and zone temperature and transmit this data to a field controller on the Sensor Actuator (SA) Bus.
This sensor is designed to assist with the California Energy Code (Title 24), providing a visual indication of operational faults with rooftop equipment. The NS Series sensor displays codes that may indicate the system is operating inefficiently. Fault codes include air temperature sensor failure or fault, not economizing properly, economizer return air, economizer not using outdoor air, outdoor air not suitable, and damper not modulating. See Table 2 for additional Fault Code information.
You may adjust the setpoint while the sensor displays the fault. You must reset the fault at the equipment controller. The sensor cannot reset the fault.
All models feature a temperature setpoint dial and
LCD designed to make adjusting the temperature
setpoint and viewing the zone temperature easier.
A °F/°C push button is available on certain models to provide temperature scale options for display. An occupancy override function is featured on all models, which allows the user to signal the controller that the space is occupied, to request an override of time-of-day scheduling. Rotating the setpoint dial signals occupancy. See Temperature Setpoint
Adjustment/Occupancy Override/Fault Temporary Override for more information.
All models include an SA Bus access port for connecting accessories to access the SA Bus. This feature allows a technician to commission or service the controller via the network sensor.
IMPORTANT: The surface-mounted NS Series Network Sensor with Fault Code Capability is intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the network sensor could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the network sensor.
IMPORTANT : Le surface-mounted NS Series Network Sensor with Fault Code Capability est destiné à transmettre des données entrantes à un équipement dans des conditions normales de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du network sensor risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du network sensor.
NS Series Network Sensors with Fault Code Capability Installation Instructions 1
Page 2

North American Emissions Compliance

!

United States

This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area may cause harmful interference, in which case the users will be required to correct the interference at their own expense.

Canada

The following ambient operating conditions apply:
Temperature: 32 to 104°F (0 to 40°C)
Humidity: 10 to 90% Relative Humidity (RH), noncondensing; 85°F (29°C) maximum dew point
To mount the network sensor to the wall:
1. Use a 1/16 in. (1.5 mm) Allen wrench or Johnson Controls T-4000-119 Allen-Head Adjustment Tool to loosen the security screw on the top of the unit.
2. Insert a coin into the slot next to the security screw location, then carefully pry the top edge of the sensor assembly away from its mounting base and remove.
IMPORTANT: Do not remove the Printed Circuit Board (PCB). Removing the PCB voids the product warranty.
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.

Installation

Special Tools Needed

A 1/16 in. (1.5 mm) Allen wrench or a Johnson Controls T-4000-119 Allen-Head Adjustment Tool is required during installation.

Mounting

Location Considerations

Locate the network sensor:
on a partitioning wall, approximately 5 ft (1.5 m) above the floor in a location of average temperature
away from direct sunlight, radiant heat, outside walls, outside doors, air discharge grills, or stairwells; and from behind doors
away from steam or water pipes, warm air stacks, unconditioned areas (not heated or cooled), or sources of electrical interference
Note: The network sensor is shock and vibration resistant; however, be careful not to drop the unit or mount it where it could be exposed to excessive vibration.
3. Pull out approximately 6 in. (152 mm) of cable from the wall, and insert the cable through the hole in the mounting base.
4. Align the mounting base on the wall, and use the base as a template to mark the location of the two mounting holes on the surface.
Note: Confirm that the mounting base is positioned with the proper edge up. The mounting base is positioned properly when the security screw is located on the top edge of the base.
5. Secure the mounting base to the wall using the appropriate mounting hardware (field furnished).
6. Wire the network sensor. For more details on wiring the MS/TP Communications Bus, refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034).
Wire the screw terminal block as illustrated in Figure 2.
CAUTION: Risk of Electric Shock.
Disconnect the power supply before making electrical connections to avoid electric shock.
MISE EN GARDE : Risque de décharge électrique.
Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de décharge électrique.
NS Series Network Sensors with Fault Code Capability Installation Instructions2
Page 3
IMPORTANT: Failure to adhere to these wiring
Figure 1: Pin Number Assignments
Pin Numb er Assignment for
Straight - Through Cable
Printed C i r c ui t Board
SA P
ower (Network
Sensor)
2
3
45
6
1
FIG:mdlr_jck
S
A
+
S
A
-
SA B
us
C
ommo
n
(Tool
A
cces
s)
S
A
Power
(T
oo
l
A
cc
ess
)
Main
Network
Port
S
A
Bus Co
m
m
o
n
(
Ne
t
work
Sensor)
Figure 2: Wiring to the Screw Terminal Block
FIG:scrw_t rmnl_blck
Figure 3: LCD for NS Sensors with
Fault Code Capability
Occupied/Unoccupied Mode
Celsius Temp erature
FIG:lcd_w_fn
%
details causes the network sensor to function incorrectly. You will not be able to connect to the system using the wireless commissioning converter or the handheld V AV balancing tool, and you will not be able to expand the system with future offerings.
Note: Ensure the terminal block pins align with the holes in the terminal block.
8. Use a 1/16 in. (1.5 mm) Allen wrench or Johnson Controls T-4000-119 Allen-Head Adjustment Tool to tighten the security screw and fasten the network sensor assembly to the mounting base.
Note: Do not overtighten the security screw to avoid damaging the unit.
9. Use the local LCD on the controller to commission and configure the network sensor.

Setup and Adjustments

°C °F
Fahrenheit Temperature
7. Align the tabs on the bottom edge of the mounting base with the slots on the bottom edge of the network sensor assembly, and rotate the assembly onto its mounting base.
NS Series Network Sensors with Fault Code Capability Installation Instructions 3
Loss of Network Connection Symbol

Temperature Setpoint Adjustment/Occupancy Override/Fault Temporary Override

The large dial on the face of the network sensor functions in two ways: to increase or decrease the setpoint temperature, and to change the controller mode from unoccupied and occupied. When the dial is rotated slightly, the backlight on the LCD lights up. If the dial is rotated slightly again, and the controller is in the unoccupied mode, the controller changes from the after-normal-working-hours setback mode to the normal-working-hours comfort mode. To adjust the setpoint, continue rotating the dial until the current setpoint is displayed and flashing. Turn the dial clockwise to increase the setpoint and counterclockwise to decrease the setpoint. S top tu rning the dial once the desired setpoint is reached. The new setpoint stops flashing and becomes fixed after a few seconds.
Page 4
If a fault code appears, the setpoint operation
Figure 4: Dual-Switch
DIP Switch Block
1
O N
2
ON
FIG:dp_swtch_blck
continues to function. Rotate the dial slightly and the backlight on the LCD lights up. The fault code disappears and the setpoint reappears. You can adjust the setpoint. The fault reappears after approximately 35 seconds of adjusting the setpoint.

°F/°C Temperature Mode Selection

Certain models include a °F/°C push button on the face of the network sensor to provide temperature scale options for display. Pressing the push button toggles the temperature mode between Fahrenheit and Celsius on the LCD.
Figure 4 and Table 1 for more details.

Network Sensor Addressing

Most network sensors have a default device address of 199 on the SA Bus. For averaging models, the sensor address must be set on the dual-switch DIP switch block on the network sensor Printed Wire Board (PWB).
Averaging models are shipped with both switches set to ON, resulting in a device address of 203. Device addresses can be DIP switch set from 200 to 203; see
Table 1: Network Sensor Addressing
DIP Switch
Switch 2 Switch 1
Address
200 OFF OFF 201 OFF ON 202 ON OFF 203 ON ON
NS Series Network Sensors with Fault Code Capability Installation Instructions4
Page 5

NS Sensors with Fault Code Capability Error Codes

The fault indication comes through the Network Sensor Bus when a Network Sensor is used in the Zone. The LCD indicates the code number for all the required state of California Title 24 economizer fault conditions. Table 2 describes the faults.
Table 2: Network Sensors with Fault Code Capability Error Codes
Display Text California Title 24 Economizer
Possible Problem
Fault Condition
EF1 Air temperature sensor failure/fault Problem with one of the air temperature sensors. Check
Outdoor Air, Return Air, or Supply Air sensors.
EF5 Not economizing when it should The economizer is not using outdoor air when it should. EF6 Economizing when it should The economizer is allowing outdoor air inside when the
conditions are not suitabl e for economizer operation.
EF8 Damper not modulating The economizer damper is not able to modulate properly.
Check damper, linkage to actuator, or the actuator.
EF9 Excess outdoor air The economizer is allowing excess outdoor air inside.

Ordering Information

Table 3: Network Sensors with Fault Code Capability Ordering Information (Title 24 Models for
Economizer Fault Detection Diagnostics [FDD])
Product Code Number
Size (mm), Height x Width
Vertical Wallbox­Mounted (WB)
LCD Display, F/C Scale Toggle
Screw Terminals
Address Switches
Temperature Adjustment: Setpoint (Set) or Warmer/ Cooler Dial (W/C)
Johnson Controls Logo
NS-A TB7F03-0 80 x 80 Yes Yes, Yes Yes Yes Set Yes No NS-A TB7F03-1 80 x 80 Yes Yes, Yes Yes Yes Set No No NS-BTB7F03-0 80 x 120 Yes Yes, Yes Yes Yes Set Yes No NS-BTB7F03-1 80 x 120 Yes Yes, Yes Yes Yes Set No No
VAV Balancing Feature

Repair Information

If the Fault Code Network Sensor fails to operate within its specifications, replace the unit. For a replacement network sensor, contact the nearest Johnson Controls representative.
NS Series Network Sensors with Fault Code Capability Installation Instructions 5
Page 6
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202

Technical Specifications

NS Series Network Sensors with Fault Code Capability

Supply Voltage 9.8 to 16.5 VDC; 15 VDC Nominal (From SA Bus) Current Consumption 21 mA maximum, non-transmitting (from SA Bus) Network Sensor Addressing DIP Switch set from 200 to 203; Factory set at 203 Terminations Screw Terminal Block Screw Terminal Wire Size 18 to 22 AWG (1.0 to 6.0 mm Diameter); 22 AWG (0.6 mm Diameter) recommended Communication Rate Auto-Detect: 9.6k, 19.2k, 38.4k, or 76.8k bps Temperature Measurement
Range Temperature Sensor Type Local Platinum Resistance Temperature Detector (RTD) Temperature Resolution ±0.5F°/±0.5C° Temperature
Accuracy
Time Constant 10 Minutes Nominal at 10 fpm Airflow Default Temperature Setpoint
Adjustment Range Ambient
Conditions
Compliance United States UL Listed, File E107041, CCN PAZX,
Dimensions (Height x Width x Depth)
Shipping Weight 0.25 lb (0.11 kg)
NS Series Network Sensor
Temperature Element Only
Operating 32 to 104°F (0 to 40°C); 10 to 90% RH, Noncondensing;
Storage -4 to 140°F (-20 to 60°C); 5 to 95% RH, Noncondensing
Canada UL Listed, File E107041, CCN PAZX7,
Europe CE Mark – Johnson Controls, Inc., declares that this product is in compliance with the
Australia and New Zealand
32.0°F/0.0°C to 104.0°F/40.0°C
±1.0F°/±0.6C°
0.35F° at 70°F (0.19C° at 21°C)
50.0°F/10.0°C to 86.0°F/30.0°C in 0.5° Increments
85°F (29°C) Maximum Dew Point
Under UL 916, Energy Management Equipment FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Under CAN/CSA C22.2 No. 205, Signal Equipment Industry Canada, ICES-003
essential requirements and other relevant provisions of the EMC Directive. RCM Mark, Australia/NZ Emissions Compliant
NS-ATBF703-x: 3-5/32 x 3-5/32 x 1-3/8 in. (80 x 80 x 35 mm) NS-BTB7F03-x: 4-23/32 x 3-5/32 x 1-3/8 in. (120 x 80 x 35 mm)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local office. Johnson Controls, Inc. shall not be liable for damage resulting from misapplication or misuse of its products.
European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact:
JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY
NS Series Network Sensors with Fault Code Capability Installation Instructions6
Published in U.S.A. www.johnsoncontrols.com
JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA
JOHNSON CONTROLS C/O CONTROLS PRODUCT MANAGEMENT NO. 22 BLOCK D NEW DISTRICT WUXI JIANGSU PROVINCE 214142 CHINA
Loading...