Johnson Controls NS-BCN7004-0, NS Series, NS-BCN7004-2 Installation Instructions Manual

NS Series CO2 Network Sensors
24- 10424- 6, Rev. E
Installation Instructions
NS-BCN7004-0, NS-BCN7004-2

Applications

The NS Series CO2 Network Sensors are electronic zone sensors designed to function directly with Johnson Controls® BACnet® MS/TP digital controllers in Heating, Ventilating, and Air Conditioning (HVAC) systems.
These sensors monitor room carbon dioxide (CO2). This data is transmitted to a field controller on the Sensor Actuator (SA) Bus.
Applications include Demand Control Ventilation (DCV) with fresh air and Indoor Air Quality (IAQ), as part of a system to meet ANSI/ASHRAE Standard
62.1-2010 Ventilation for Acceptable Indoor Air Quality. For DCV applications, fresh air is brought into a zone based on the concentration levels of CO2.
The NS Series CO2 Network Sensors include DIP switches to set a unique address in averaging applications. The wires connecting the network sensor to the controller can be terminated using either a modular jack or screw terminal block, offering wiring flexibility.
The NS Series CO2 Network Sensors include an SA Bus access port for connecting accessories to access the SA Bus. This feature allows a technician to commission or service the controller via the network sensor.
Part No. 24-10424-6, Rev. E
Issued March 2016
IMPORTANT: The NS Series CO
Sensors are intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the network sensor could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the network sensor.
IMPORTANT : Le NS Series CO est destiné à transmettre des données entrantes à
un équipement dans des conditions normales de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du network sensor risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du network sensor.
Network
2
Network Sensors
2
NS Series CO2 Network Sensors Installation Instructions 1

North American Emissions Compliance

United States

This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area may cause harmful interference, in which case the users will be required to correct the interference at their own expense.

Canada

This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.

Installation

Special Tools Needed

A 1/16 in. (1.5 mm) Allen wrench or a Johnson Controls T-4000-119 Allen-Head Adjustment Tool is required during installation.

Mounting

Note: The NS Series CO2 Network Sensors are
intended to be mounted on a vertically roughed-in wallbox only; do not attempt to mount the network sensor on a horizontally roughed-in wallbox.

Location Considerations

Locate the network sensor:
on a partitioning wall, approximately 5 ft (1.5 m) above the floor in a location of average temperature
away from direct sunlight, radiant heat, outside walls, outside doors, air discharge grills, or stairwells; and from behind doors
away from steam or water pipes, warm air stacks, unconditioned areas (not heated or cooled), or sources of electrical interference
Note: The network sensor is shock and vibration resistant; however, be careful not to drop the unit or mount it where it could be exposed to excessive vibration.
The following ambient operating conditions apply:
Temperature: 32 to 104°F (0 to 40°C)
Humidity: 10 to 90% Relative Humidity (RH), noncondensing; 85°F (29°C) maximum dew point
To mount the network sensor to a wallbox:
1. Use a 1/16 in. (1.5 mm) Allen wrench or Johnson Controls T-4000- 119 Allen-Head Adjustment Tool to loosen the security screw on the top of the unit.
2. Insert a coin into the slot next to the security screw location, pressing the tab that keeps the unit closed. Then carefully pry the top edge of the sensor assembly away from its mounting base and remove.
IMPORTANT: Do not insert tools into the housing. Be careful not to damage any components when pushing on the tab.
IMPORTANT: Do not remove the Printed Circuit Board (PCB). Removing the PCB voids the product warranty.
Pull out approximately 6 in. (152 mm) of cable fro m the wallbox, and insert the cable through the hole in the mounting base.
3. Align the mounting base on the wallbox.
Note: Confirm that the mounting base is positioned with the proper edge up. The mounting base is positioned properly when the security screw is located on the top edge of the base.
4. Secure the mounting base to the wallbox using the appropriate mounting hardware (field furnished).
5. Wire the network sensor as follows: SA Bus Wiring: For the modular jack, simply snap
the wiring plug into the jack. See Figure 1 for modular jack pin number assignments. A modular jack requires a straight-through, one-to-one connection (not a crossover). For the screw terminal block, wire the unit as illustrated in Figure 2.
Note: Connect to the SA Bus using either the screw terminal block or the modular jack. Do not use both.
NS Series CO2 Network Sensors Installation Instructions2
Loading...
+ 4 hidden pages