Johnson Controls NS-AHN700 Series, NS-ATN700 Series, NS-ATP700 Series, NS-AHP7001-0 Installation Instructions Manual

Page 1
Surface-Mounted NS Series Network Sensors without LCD
*241009417R*
(barcode for factory use only)
24-10094-17, Rev. R
Installation Instructions
NS-AHP7001-0, NS-AHN700x-x, NS-ATN700x-x, NS-ATP700x-x
Refer to the QuickLIT website for the most up-to-date version of this document.
Applications
The surface-mounted NS Series Network Sensor without LCD is an electronic zone sensor designed to function directly with Johnson Controls® BACnet® Master-Slave/Token-Passing (MS/TP) digital controllers in HVAC systems. Models in this series monitor the zone temperature and humidity, and transmit this data to a field controller on the Sensor Actuator (SA) Bus.
A warmer/cooler dial is included on certain models for minor temperature adjustments from the setpoint. An occupancy override button is also featured on some models, which allows the user to signal the controller that the space is occupied, to request an override of time-of-day scheduling. Rotation of the warmer/cooler dial signals occupancy as well. Select models include DIP switches to set a unique address in averaging applications. Models are available with or without a Johnson Controls logo on the face of the unit.
Depending on the model chosen, the wires connecting the network sensor to the controller can be termin at ed using either a modular jack or screw terminal block, offering wiring flexibility.
Note: Models featuring a modular jack are not intended for installations where daisy chaining to the MS/TP Bus is required.
All models include an SA Bus access port for connecting accessories to access the SA Bus. This feature allows a technician to commission or service the controller via the network sensor.
Note: Since some NS Series Network Sensor features are not supported in previous releases of Metasys® or Facility Explorer system software, it is recommended that the system software be kept up to date.
IMPORTANT: The surface-mounted NS Series Network Sensor is intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the network sensor could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the network sensor.
IMPORTANT: Le surface-mounted NS Series Network Sensor est destiné à transmettre des données entrantes à un équipement dans des conditions normales de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du network sensor risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de con tr ôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du network sensor.
North American Emissions Compliance
United States
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area may cause harmful interference, in which case the users will be required to correct the interference at their own expense.
Part No. 24-10094-17, Rev. R
Issued May 2018
Surface-Mounted NS Series Network Sensors without LCD Installation
Instructions
1
Page 2
Canada
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
Installation
Special Tools Needed
A 1/16 in. (1.5 mm) Allen wrench or a Johnson Controls T -4000- 119 Allen-Head Adjustment Tool is required during installation.
Mounting
Location Considerations
Locate the network sensor:
on a partitioning wall, approximately 5 ft (1.5 m) above the floor in a location of average temperature
away from direct sunlight, radiant heat, outside walls, outside doors, air discharge grills, or stairwells; and from behind doors
away from steam or water pipes, warm air stacks, unconditioned areas (not heated or cooled), or sources of electrical interference
Note: The network sensor is shock and vibration resistant; however, be careful not to drop the unit or mount it where it could be exposed to excessive vibration.
The following ambient operating conditions apply:
Temperature: 32 to 104°F (0 to 40°C)
Humidity: 10 to 90% Relative Humidity (RH), noncondensing; 85°F (29°C) maximum dew point
To mount the network sensor to the wall:
1. Use a 1/16 in. (1.5 mm) Allen wrench or Johnson Controls T-4000-119 Allen-Head Adjustment Tool to loosen the security screw on the top of the unit.
2. Insert a coin into the slot next to the security screw location, then carefully pry the top edge of the sensor assembly away from its mounting base and remove.
IMPORTANT: Do not remove the Printed Circuit Board (PCB). Removing the PCB voids the product warranty.
3. Pull out approximately 6 in. (152 mm) of cab le fro m the wall, and insert the cable through the hole in the mounting base.
4. Align the mounting base on the wall, and use the base as a template to mark the location of the two mounting holes on the surface.
Note: Confirm that the mounting base is positioned with the proper edge up. The mounting base is positioned properly when the security screw is located on the top edge of the base.
5. Secure the mounting base to the wall using the appropriate mounting hardware (field furnished).
6. Wire the network sensor. For more details on wiring the MS/TP Communications Bus, refer to the MS/TP
Communications Bus Technical Bulletin (LIT-12011034) or the FX-PC Series Controllers MS/TP Communications Bus Technical Bulletin (LIT-12011670).
Surface-Mounted NS Series Network Sensors without LCD Installation Instructions
2
Page 3
For models featuring a modular jack, simply snap the wiring plug into the jack. See Figure 1 for modular jack
!
pin number assignments. Modular jack models require a straight-thr ough, one-to-one connection (not a crossover). For models featuring a screw terminal block, wire the unit as illustrated in Figure 2.
CAUTION: Risk of Electric Shock.
Disconnect the power supply before making electrical connections to avoid electric shock.
MISE EN GARDE : Risque de décharge électrique.
Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de décharge électrique.
IMPORTANT: Failure to adhere to these wiring details causes the ne twork sensor to function incorrectly. You will not be able to connect to the system using the wireless commissioning converter or the handheld Variable Air Volume (VAV) balancing tool, and you will not be able to expand the system with future offerings.
Surface-Mounted NS Series Network Sensors without LCD Installation Instructions
3
Page 4
Figure 1: Modular Jack Pin Number Assignments
Pin Numb er Assignment for
Straight - Through Cable
Printed C i r c ui t Board
SA P
ower (Network
Sensor)
2
3
45
6
1
FIG:mdlr_jck
S
A
+
S
A
-
SA B
us
C
ommo
n
(Tool
A
cces
s)
S
A
Power
(T
oo
l
A
cc
ess
)
Main
Network
Port
S
A
Bus Co
m
m
o
n
(
Ne
t
work
Sensor)
Figure 2: Wiring to the Screw Te rminal Block
FIG:scrw_trmnl_blck
7. Align the tabs on the bottom edge of the mounting base with the slots on the bottom edge of the network sensor assembly, and rotate the assembly onto its mounting base.
Note: On models featuring a screw terminal block, be certain that the terminal block pins align with the holes in the terminal block.
Surface-Mounted NS Series Network Sensors without LCD Installation Instructions
4
Page 5
8. Use a 1/16 in. (1.5 mm) Allen wrench or Johnson Controls T-4000-119 Allen-Head Adjustment Tool to tighten
Figure 3: Dual-Switch
DIP Switch Block
1
O N
2
ON
FIG:dp_sw tch_blck
the security screw and fasten the network sensor assembly to the mounting base.
Note: Do not overtighten the security screw to avoid damaging the unit.
9. Use the Metasys Controller Configuration Tool (CCT) or Facility Explorer Programmable Controller Tool (FX­PCT) software to commission the network sensor. Refer to the Controller Tool Help (LIT-12011147) for more details.
Setup and Adjustments
Warmer/Cooler Adjustment
Certain models include a warmer/cooler dial designed to make minor temperature adjustments from the setpoint. Turning the warmer/cooler dial adjusts the temperature setpoint up to ±5.0F°/±3.0C°.
Occupancy Override
Some models include an occupancy override push button on the left side of the network sensor, inline with the green Light-Emitting Diode (LED). If the green LED is illuminated, the network sensor is in the occupancy override mode. If the green LED is not illuminated, pressing the occupancy override push button activates the normal-working-hours comfor t mo de .
Some NS-series sensor models also include a PIR Occupancy Sensor, or can initiate occupancy by rotating the setpoint dial. The LED is not illuminated when the PIR sense occupancy or the setpoint dial is rotated.
Network Sensor Addressing
Most network sensors have a default device address of 199 on the SA Bus. For averaging models, the sensor address must be set on the dual-switch DIP switch block on the network sensor Printed Wire Board (PWB).
Averaging models are shipped with both switches set to ON, resulting in a device address of 203. Device addresses can be DIP switch set from 200 to 203; see Figure 3 and Table 1 for more details.
Surface-Mounted NS Series Network Sensors without LCD Installation Instructions
5
Page 6
Table 1: Network Sensor Addressing
DIP Switch Address Switch 2 Switch 1
200 OFF OFF 201 OFF ON 202 ON OFF 203 ON ON
Repair Information
If the NS Series Network Sensor fails to operate within its specifications, replace the unit. For a replacement network sensor, contact the nearest Johnson Controls representative.
Technical Specifications
Surface-Mounted NS Series Network Sensors without LCD (Part 1 of 2)
Supply Voltage 9.8 to 16.5 VDC; 15 VDC nominal (from SA Bus) Current
Consumption
Terminations Modular jack or screw terminal block Network
Sensor Addressing
Wire Size Modular Jack
Communication Rate Auto-detect: 9.6k, 19.2k, 38.4k, or 76.8k bps Temperature Measurement
Range Humidity
Measurement Range
Temperature Sensor Type Local 1k Ohm platinum resistance temperature detector (RTD); Class A per IEC 60751 Humidity Sensor Type Thin film capacitive sensor Temperature
Accuracy
Humidity Element Accuracy ±3% RH for 20 to 80% RH;
Time Constant 10 minutes nominal at 10 fpm airflow Default Temperature Setpoint
Adjustment Range
Temperature Only Models
Temperature and Humidity Models
NS-A Tx7003-0, NS-AHx7003-0 Models
All Other Models
Models Screw
Terminal Block Models
Full Range 0 to 100% RH Calibrated
Range
NS Series Network Zone Sensor
Temperature Element Only
13 mA maximum (non-transmitting)
17 mA maximum (non-transmitting)
DIP switch set from 200 to 203; factory set at 203
Fixed address of 199
24 or 26 AWG (0.5 or 0.4 mm diameter); three twisted pair (six conductors)
18 to 22 AWG (1.0 to 0.6 mm diameter); 22 AWG (0.6 mm diameter) recommended
32.0°F/0.0°C to 104.0°F/40.0°C
10 to 90% RH
±1.0F°/±0.6C°
0.35F° at 70°F (0.2C° at 21°C)
±6% RH for 10 to 20% and 80 to 90% RH
±5.0F°/±3.0C°
Surface-Mounted NS Series Network Sensors without LCD Installation Instructions
6
Page 7
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls.
All other marks herein are the marks of their respective owners. © 2018 Johnson Controls.
Building Technologies & Solutions
507 E. Michigan Street, Milwaukee, WI 53202
Surface-Mounted NS Series Network Sensors without LCD (Part 2 of 2)
Ambient Conditions
Compliance BACnet
Dimensions (Height x Width x Depth)
Shipping Weight 0.20 lb (0.09 kg)
Operating 32 to 104°F (0 to 40°C); 10 to 90% RH, noncondensing;
85°F (29°C) maximum dewpoint
Storage -40 to 158°F (-40 to 70°C); 5 to 95% RH, noncondensing
International United States UL Listed, File E107041, CCN PAZX,
Canada UL Listed, File E107041, CCN PAZX7,
Europe CE Mark – Johnson Controls, Inc. declares that this product is in compliance with the
Australia and New Zealand
BACnet Testing Laboratories™ (BTL) 135-2004 Listed BACnet Smart Sensor (B-SS)
Under UL 916, Energy Management Equipment FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Under CAN/CSA C22.2 No. 205, Signal Equipment Industry Canada, ICES-003
essential requirements and other relevant provisions of the EMC Directive. RCM Mark, Australia/NZ Emissions Compliant
3-5/32 x 3-5/32 x 1-3/8 in. (80 x 80 x 35 mm)
European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact:
JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY
Surface-Mounted NS Series Network Sensors without LCD Installation Instructions
Published in U.S.A. www.johnsoncontrols.com
JOHNSON CONTROLS 507 E MICHIGAN ST MIL WAUKEE WI 53202 USA
7
JOHNSON CONTROLS C/O CONTROLS PRODUCT MANAGEMENT NO. 22 BLOCK D NEW DISTRICT WUXI JIANGSU PROVINCE 214142 CHINA
Loading...