Refer to the QuickLIT website for the most up-to-date version of this document.
Applications
The surface-mounted NS Series Network Sensor
without LCD is an electronic zone sensor designed to
function directly with Johnson Controls® BACnet®
Master-Slave/Token-Passing (MS/TP) digital
controllers in HVAC systems. Models in this series
monitor the zone temperature and humidity, and
transmit this data to a field controller on the Sensor
Actuator (SA) Bus.
A warmer/cooler dial is included on certain models for
minor temperature adjustments from the setpoint. An
occupancy override button is also featured on some
models, which allows the user to signal the controller
that the space is occupied, to request an override of
time-of-day scheduling. Rotation of the warmer/cooler
dial signals occupancy as well. Select models include
DIP switches to set a unique address in averaging
applications. Models are available with or without a
Johnson Controls logo on the face of the unit.
Depending on the model chosen, the wires connecting
the network sensor to the controller can be termin at ed
using either a modular jack or screw terminal block,
offering wiring flexibility.
Note: Models featuring a modular jack are not
intended for installations where daisy chaining to the
MS/TP Bus is required.
All models include an SA Bus access port for
connecting accessories to access the SA Bus. This
feature allows a technician to commission or service
the controller via the network sensor.
Note: Since some NS Series Network Sensor
features are not supported in previous releases of
Metasys® or Facility Explorer system software, it is
recommended that the system software be kept up to
date.
IMPORTANT: The surface-mounted NS Series
Network Sensor is intended to provide an input to
equipment under normal operating conditions.
Where failure or malfunction of the network sensor
could lead to personal injury or property damage to
the controlled equipment or other property,
additional precautions must be designed into the
control system. Incorporate and maintain other
devices, such as supervisory or alarm systems or
safety or limit controls, intended to warn of or protect
against failure or malfunction of the network sensor.
IMPORTANT: Le surface-mounted NS Series
Network Sensor est destiné à transmettre des
données entrantes à un équipement dans des
conditions normales de fonctionnement. Lorsqu'une
défaillance ou un dysfonctionnement du network
sensor risque de provoquer des blessures ou
d'endommager l'équipement contrôlé ou un autre
équipement, la conception du système de con tr ôle
doit intégrer des dispositifs de protection
supplémentaires. Veiller dans ce cas à intégrer de
façon permanente d'autres dispositifs, tels que des
systèmes de supervision ou d'alarme, ou des
dispositifs de sécurité ou de limitation, ayant une
fonction d'avertissement ou de protection en cas de
défaillance ou de dysfonctionnement du network
sensor.
North American Emissions Compliance
United States
This equipment has been tested and found to
comply with the limits for a Class A digital device
pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection
against harmful interference when this equipment is
operated in a commercial environment. This
equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in
accordance with the instruction manual, may cause
harmful interference to radio communications.
Operation of this equipment in a residential area
may cause harmful interference, in which case the
users will be required to correct the interference at
their own expense.
Part No. 24-10094-17, Rev. R
Issued May 2018
Surface-Mounted NS Series Network Sensors without LCD Installation
Instructions
1
Page 2
Canada
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment
Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur
du Canada.
Installation
Special Tools Needed
A 1/16 in. (1.5 mm) Allen wrench or a Johnson Controls T -4000- 119 Allen-Head Adjustment Tool is required during
installation.
Mounting
Location Considerations
Locate the network sensor:
•on a partitioning wall, approximately 5 ft (1.5 m) above the floor in a location of average temperature
•away from direct sunlight, radiant heat, outside walls, outside doors, air discharge grills, or stairwells; and from
behind doors
•away from steam or water pipes, warm air stacks, unconditioned areas (not heated or cooled), or sources of
electrical interference
Note: The network sensor is shock and vibration resistant; however, be careful not to drop the unit or mount it
where it could be exposed to excessive vibration.
The following ambient operating conditions apply:
•Temperature: 32 to 104°F (0 to 40°C)
•Humidity: 10 to 90% Relative Humidity (RH), noncondensing; 85°F (29°C) maximum dew point
To mount the network sensor to the wall:
1. Use a 1/16 in. (1.5 mm) Allen wrench or Johnson Controls T-4000-119 Allen-Head Adjustment Tool to loosen
the security screw on the top of the unit.
2. Insert a coin into the slot next to the security screw location, then carefully pry the top edge of the sensor
assembly away from its mounting base and remove.
IMPORTANT: Do not remove the Printed Circuit Board (PCB). Removing the PCB voids the product warranty.
3. Pull out approximately 6 in. (152 mm) of cab le fro m the wall, and insert the cable through the hole in the
mounting base.
4. Align the mounting base on the wall, and use the base as a template to mark the location of the two mounting
holes on the surface.
Note: Confirm that the mounting base is positioned with the proper edge up. The mounting base is positioned
properly when the security screw is located on the top edge of the base.
5. Secure the mounting base to the wall using the appropriate mounting hardware (field furnished).
6. Wire the network sensor. For more details on wiring the MS/TP Communications Bus, refer to the MS/TP
Communications Bus Technical Bulletin (LIT-12011034) or the FX-PC Series Controllers MS/TP
Communications Bus Technical Bulletin
(LIT-12011670).
Surface-Mounted NS Series Network Sensors without LCD Installation Instructions
2
Page 3
For models featuring a modular jack, simply snap the wiring plug into the jack. See Figure 1 for modular jack
!
pin number assignments. Modular jack models require a straight-thr ough, one-to-one connection (not a
crossover). For models featuring a screw terminal block, wire the unit as illustrated in Figure 2.
CAUTION: Risk of Electric Shock.
Disconnect the power supply before making electrical connections to avoid electric shock.
MISE EN GARDE : Risque de décharge électrique.
Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de
décharge électrique.
IMPORTANT: Failure to adhere to these wiring details causes the ne twork sensor to function incorrectly. You
will not be able to connect to the system using the wireless commissioning converter or the handheld Variable
Air Volume (VAV) balancing tool, and you will not be able to expand the system with future offerings.
Surface-Mounted NS Series Network Sensors without LCD Installation Instructions
3
Page 4
Figure 1: Modular Jack Pin Number Assignments
Pin Numb er Assignment for
Straight - Through Cable
Printed C i r c ui t Board
SA P
ower (Network
Sensor)
2
3
45
6
1
FIG:mdlr_jck
S
A
+
S
A
-
SA B
us
C
ommo
n
(Tool
A
cces
s)
S
A
Power
(T
oo
l
A
cc
ess
)
Main
Network
Port
S
A
Bus Co
m
m
o
n
(
Ne
t
work
Sensor)
Figure 2: Wiring to the Screw Te rminal Block
FIG:scrw_trmnl_blck
7. Align the tabs on the bottom edge of the mounting base with the slots on the bottom edge of the network
sensor assembly, and rotate the assembly onto its mounting base.
Note: On models featuring a screw terminal block, be certain that the terminal block pins align with the holes in
the terminal block.
Surface-Mounted NS Series Network Sensors without LCD Installation Instructions
4
Page 5
8. Use a 1/16 in. (1.5 mm) Allen wrench or Johnson Controls T-4000-119 Allen-Head Adjustment Tool to tighten
Figure 3: Dual-Switch
DIP Switch Block
1
O
N
2
ON
FIG:dp_sw tch_blck
the security screw and fasten the network sensor assembly to the mounting base.
Note: Do not overtighten the security screw to avoid damaging the unit.
9. Use the Metasys Controller Configuration Tool (CCT) or Facility Explorer Programmable Controller Tool (FXPCT) software to commission the network sensor. Refer to the Controller Tool Help (LIT-12011147) for more
details.
Setup and Adjustments
Warmer/Cooler Adjustment
Certain models include a warmer/cooler dial designed to make minor temperature adjustments from the setpoint.
Turning the warmer/cooler dial adjusts the temperature setpoint up to ±5.0F°/±3.0C°.
Occupancy Override
Some models include an occupancy override push button on the left side of the network sensor, inline with the
green Light-Emitting Diode (LED). If the green LED is illuminated, the network sensor is in the occupancy override
mode. If the green LED is not illuminated, pressing the occupancy override push button activates the
normal-working-hours comfor t mo de .
Some NS-series sensor models also include a PIR Occupancy Sensor, or can initiate occupancy by rotating the
setpoint dial. The LED is not illuminated when the PIR sense occupancy or the setpoint dial is rotated.
Network Sensor Addressing
Most network sensors have a default device address of 199 on the SA Bus. For averaging models, the sensor
address must be set on the dual-switch DIP switch block on the network sensor Printed Wire Board (PWB).
Averaging models are shipped with both switches set to ON, resulting in a device address of 203. Device
addresses can be DIP switch set from 200 to 203; see Figure 3 and Table 1 for more details.
Surface-Mounted NS Series Network Sensors without LCD Installation Instructions
5
Page 6
Table 1: Network Sensor Addressing
DIP Switch AddressSwitch 2Switch 1
200OFFOFF
201OFFON
202ONOFF
203ONON
Repair Information
If the NS Series Network Sensor fails to operate within its specifications, replace the unit. For a replacement
network sensor, contact the nearest Johnson Controls representative.
Technical Specifications
Surface-Mounted NS Series Network Sensors without LCD (Part 1 of 2)
Supply Voltage9.8 to 16.5 VDC; 15 VDC nominal (from SA Bus)
Current
Consumption
TerminationsModular jack or screw terminal block
Network
Sensor
Addressing
Wire SizeModular Jack
Communication RateAuto-detect: 9.6k, 19.2k, 38.4k, or 76.8k bps
Temperature Measurement
Range
Humidity
Measurement
Range
Temperature Sensor TypeLocal 1k Ohm platinum resistance temperature detector (RTD); Class A per IEC 60751
Humidity Sensor TypeThin film capacitive sensor
Temperature
Accuracy
Humidity Element Accuracy±3% RH for 20 to 80% RH;
Time Constant10 minutes nominal at 10 fpm airflow
Default Temperature Setpoint
Adjustment Range
Temperature
Only Models
Temperature
and Humidity
Models
NS-A Tx7003-0,
NS-AHx7003-0
Models
All Other
Models
Models
Screw
Terminal
Block Models
Full Range0 to 100% RH
Calibrated
Range
NS Series
Network Zone
Sensor
Temperature
Element Only
13 mA maximum (non-transmitting)
17 mA maximum (non-transmitting)
DIP switch set from 200 to 203; factory set at 203
Fixed address of 199
24 or 26 AWG (0.5 or 0.4 mm diameter); three twisted pair (six conductors)
18 to 22 AWG (1.0 to 0.6 mm diameter); 22 AWG (0.6 mm diameter) recommended
32.0°F/0.0°C to 104.0°F/40.0°C
10 to 90% RH
±1.0F°/±0.6C°
0.35F° at 70°F (0.2C° at 21°C)
±6% RH for 10 to 20% and 80 to 90% RH
±5.0F°/±3.0C°
Surface-Mounted NS Series Network Sensors without LCD Installation Instructions
6
Page 7
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls.