Johnson Controls N-1001 Catalog Page

N-1001
N-1001 Economizer Logic Network
Economizer Logic Network
Description
The N-1001 Economizer Logic Network provides a sequence of logic functions for use with all types of mixed air handling units. The N-1001 provides fan interlock and minimum percent outside air damper position adjustment, as well as economizer switchover and other auxiliary switching strategies.
Refer to N-1001 Economizer Logic Network Product Bulletin (LIT-7171500) for important product information.
Features
• Choice of these economizer switchovers:
- differential temperature
- outside air dry bulb
- enthalpy
• compatible with all pneumatic controllers and transmitters
• includes hypodermic needle test points on all inputs and outputs
• mounts upright with the integral bracket and two No. 8 sheet metal screws
Code No. LIT-1921275 Issued January 15, 2008
Selection Charts
N-1001 Economizer Logic Network
Code Number Description
N-1001-1 Economizer Logic Network
Accessories for N-1001
Repair Information
If the N-1001 Economizer Logic Network fails to operate within its specifications, replace the unit. For a replacement logic network, contact the nearest Johnson Controls® representative.
Code Number Description
A-4000-1037 Inline Supply Air filter JC 5361 Hypodermic Needle Test
JC 5383A Calibration Kit (Optional)
Probe
Technical Specifications
N-1001 Economizer Logic Network
Supply Pressure 20 psig (140 kPa) Nominal,
25 psig (175 kPa) Maximum 18 psig (126 kPa) Minimum Air supply must be clean, dry , and oil free
Air Connections S Barbed fitting for 5/32 or 1/4 in. O.D. Polytubing;
DIFF COM DB All Other Fittings Barbed fitting for 1/4 in. O.D. Polytubing
Adjustments Switchover
Dry Bulb Economizer Switchover Variation
Integral Test Points For all fittings except S, DIFF, COM, and DB Ambient Temperature Limits 40 to 120°F (4 to 49°C) Air Consumption Maximum 250 SCIM (68 mL/s), excluding any field installed restricted sources of supply Flow Capacities
(DPR, CLG, TLL, and AUX) Mounting Surface mounted using integral bracket Materials Frame and Cover Zinc plated steel
Adjustment
Minimum Position Adjustment
50F° T-5210 Span 1/4F° Variation 100F° T-5210 Span 1/2F° Variation 200F° T-5210 Span 1F° Variation
Manifold Black Noryl Thermoplastic Other Fittings Brass Internal
Repeaters Internal Tubing Silicone
Use only 1/4 in. O.D. Polytubing
O.A./R.A. Differential: Switchover adjustment factory set at approximately 0.1 psig (0.7 kPa) adjustable from 0.1 to 6 psig (0.7 to 42 kPa)
Dry Bulb: adjustable from 2 to 12 psig (14 to 84 kPa) Minimum position O.A. adjustment factory set at approximately
9 psig (63 kPa); adjustable from 2 to 12 psig (14 to 84 kPa)
45 SCIM (12 mL/s)
Polysulfone body
The performance specifications are nomina l and conf orm to accep table industr y standar ds. For ap plications a t condition s beyond th ese specification s, consult the local Johnson Controls o ffice. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2011 Johnson Controls, Inc.