These high efficiency, compact units employ induced combustion, reliable hot surface ignition and high heat transfer aluminized tubular heat
exchangers. The units are factory shipped for installation in downflow
applications and may be converted for upflow applications.
Blower Performance CFM - Any Position (Without Filter) . . . . . 28
These furnaces are designed for residential installation in a basement,
closet, alcove, attic, recreation room or garage applications. All units
are factory assembled, wired and tested to assure safe dependable and
economical installation and operation.
These units are Category IV listed and may not be common vented with
another gas appliance as allowed by the National Fuel Gas Code.
420705-UIM-C-0310
Page 2
420705-UIM-C-0310
SECTION I: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not
avoided may resul t in minor or moderate injury.
alert against unsafe practices and hazards involving only property damage.
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Failure to carefully
read and follow all instructions in this manual can result in furnace malfunction, death, personal injury and/or property damage. Only a qualified cont ractor, installer or service agency should
install this product.
SPECIFIC SAFETY RULES AND PRECAUTIONS
1.Only Natural gas or Propane (LP) gas are approved for use with
this furnace.
2.Install this furnace only in a location and position as specified in
these instructions.
3.A gas-fired furnace for installation in a residential garage must be
installed as specified in these instructions.
4.Provide adequate combustion and ventilation air to the furnace
space as specified in these instructions.
5.Combustion products must be discharged outdoors. Connect this
furnace to an approved vent system only, as specified in SECTION VII, "COMBUSTION AIR and VENT SYSTEM" of these
instructions.
6.Test for gas leaks as specified in these instructions.
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in serious
injury, death or property damage.
Never test for gas leaks with an open flame. Use a commercially
available soap solution made specifically for detection of leaks to
check all connections. A fire or explosion may result causing property damage, personal injury or loss of life.
7.Always install the furnace to operate within the furnace’s intended
temperature rise range. Only connect the furnace to a duct system
which has an external static pressure within the allowable range,
as specified on the furnace rating plate.
8.When a furnace is installed so that supply ducts carry air circulated
by the furnace to areas outside the space containing the furnace,
the return air may also be handled by duct(s) sealed to the furnace
casing and terminating outside the space containing the furnace.
The return air duct system is not required by the furnace manufacturer provided the combustion air and vent system have been
installed and maintained as a Two Pipe Sealed Combustion Air
System and provided a return air duct system and return air plenum are not required by state, local, or regional codes.
9.It is permitted to use the furnace for heating of buildings or structures under construction where the application and use must comply with all manufacturer’s installation instructions including:
• Proper vent installation;
• Furnace operating under thermostatic control;
.
It is also used to
• Return air duct sealed to the furnace;
• Air filters in place;
• Set furnace input rate and temperature rise per rating plate
marking;
• Means for providing outdoor air required for combustion;
• Return air temperature maintained between 55ºF (13ºC) and
80ºF (27ºC);
•The air filter must be replaced upon substantial completion of
the construction process;
• Clean furnace, duct work and components upon substantial
completion of the construction process, and verify furnaceoperating conditions including ignition, input rate, temperature
rise and venting, according to the manufacturer’s instructions.
10. When installed in a Manufactured (Mobile) Home, combustion air
shall not be supplied from occupied spaces.
11. The size of the unit should be based on an acceptable heat loss
calculation for the structure. ACCA, Manual J or other approved
methods may be used.
12. When moving or handling this furnace prior to installation, always
leave the doors on the furnace to provide support and to prevent
damage or warping of the cabinet. When lifting the furnace by the
cabinet, support the ends of the furnace rather than lifting by the
cabinet flanges at the return air openings (bottom or sides) or supply air opening.
13. When lifting the furnace, it is acceptable to use the primary heat
exchanger tubes as a lifting point provided that the tubes are lifted
at the front of the heat exchangers where attached to the vestibule
panel. Do not use the top return bend of the heat exchangers as
lifting points as the tubes may shift out of position or their location
brackets/baffles.
14. Manufactured (Mobile) Home Installation: This appliance must
be installed in a two-pipe (direct vent) configuration. The combustion air pipe must terminate in the same atmospheric zone, external to the building.
15. Modular Home Installations: A (two pipe) direct vent configuration. This configuration has a combustion air pipe and the vent
pipe that terminate in the same atmospheric zone, external to the
building, Refer to Figures 26 or 27 for combustion air and vent terminations.
16. Modular Home Definition: Factory-built home constructed to the
state, local, or regional code where the house will be located. The
home is transported in one or more modules and joined at the
home site.
17. Mobile Home Definition: Factory-built home constructed, transported and installed under the federal building code administered
by the U.S. Department of Housing and Urban Development (HUD
Code), rather than to building codes at their destination. The home
is built, transported, installed on a non-removable chassis.
SAFETY REQUIREMENTS
This product must be installed in strict compliance with the installation instructions and any applicable local, state, and national codes
including, but not limited to building, electrical, and mechanical
codes.
• A manufactured (mobile) home installation must conform with
Manufactured Home Construction and Safety Standard, Title 24
CFR, Part 3280, or when such standard is not applicable, the
standard for Manufactured Home Installations (Manufactured
Home Sites, Communities, and Set-ups) ANSI/NCS A225.1, and
/or the Canadian Standard for CAN/CSA Z240 MH, Series M92
Mobile Homes. Furnaces have been certified to the latest edition
of standard ANSI Z21-47 • CSA 2.3.
• Refer to the unit rating plate for the furnace model number, and
then see the dimensions page of this instruction for return air plenum dimensions in Figure 12. The plenum must be installed
according to the instructions.
• Provide clearances from combustible materials as listed under
Clearances to Combustibles in Table 1.
2Johnson Controls Unitary Products
Page 3
420705-UIM-C-0310
• Provide clearances for servicing ensuring that service access is
allowed for both the burners and blower.
• These models ARE
HUD Approved Modular Home
Home.
• This furnace is not approved for installation in trailers or recreational vehicles.
• Furnaces for installation on combustible flooring shall not be
installed directly on carpeting, tile or other combustible material
other than wood flooring.
• Check the rating plate and power supply to be sure that the electrical characteristics match. All models use nominal 115 VAC, 1
Phase, 60-Hertz power supply. DO NOT CONNECT THIS APPLIANCE TO A 50 HZ POWER SUPPLY OR A VOLTAGE ABOVE
130 VOLTS.
• Furnace shall be installed so the electrical components are protected from water.
• Installing and servicing heating equipment can be hazardous due
to the electrical components and the gas fired components. Only
trained and qualified personnel should install, repair, or service
gas heating equipment. Untrained service personnel can perform
basic maintenance functions such as cleaning and replacing the
air filters. When working on heating equipment, observe precautions in the manuals and on the labels attached to the unit and
other safety precautions that may apply.
• These instructions cover minimum requirements and conform to
existing national standards and safety codes. In some instances
these instructions exceed certain local codes and ordinances,
especially those who have not kept up with changing residential
and non-HUD modular home construction practices. These
instructions are required as a minimum for a safe installation.
CSA listed or approved for installation into a
or a Manufactured (Mobile)
COMBUSTION AIR QUALITY
(LIST OF CONTAMINANTS)
The furnace area must not be used as a broom closet or for any
other storage purposes, as a fire hazard may be created. Never
store items such as the following on, near or in contact with the furnace.
1. Spray or aerosol cans, rags, brooms, dust mops, vacuum
cleaners or other cleaning tools.
2. Soap powders, bleaches, waxes or other cleaning compounds; plastic items or containers; gasoline, kerosene, cigarette lighter fluid, dry cleaning fluids or other volatile fluid.
3. Paint thinners and other painting compounds.
4. Paper bags, boxes or other paper products
Never operate the furnace with the blower door removed. To
do so could result in serious personal injury and/or equipment
damage.
The furnace requires OUTDOOR AIR for combustion when the furnace
is located in any of the following environments.
• Restricted Environments
• Commercial buildings
• Buildings with indoor pools
• Furnaces installed in laundry rooms
• Furnaces installed in hobby or craft rooms
• Furnaces installed near chemical storage areas
• Chemical exposure
The furnace requires OUTDOOR AIR for combustion when the furnace
is located in an area where the furnace is being exposed to the following substances and / or chemicals.
• Permanent wave solutions
• Chlorinated waxes and cleaners
• Chlorine based swimming pool chemicals
• Water softening chemicals
• De-icing salts or chemicals
• Carbon tetrachloride
• Halogen type refrigerants
• Cleaning solvents (such as perchloroethylene)
• Printing inks, paint removers, varnishes, etc.
• Hydrochloric acid
• Cements and glues
• Antistatic fabric softeners for clothes dryers
• Masonry acid washing materials
When outdoor air is used for combustion, the combustion air intake duct
system termination must be located external to the building and in an
area where there will be no exposure to the substances listed above.
CODES AND STANDARDS
Follow all national, local codes and standards in addition to this installation manual. The installation must comply with regulations of the serving gas supplier, local building, heating, plumbing, and other codes. In
absence of local codes, the installation must comply with the national
codes listed below and all authorities having jurisdiction.
In the United States and Canada, follow all codes and standards for the
following, using the latest edition available:
STEP 1 -Safety
• US: National Fuel Gas Code (NFGC) NFPA 54/ANSI Z223.1 and
the Installation Standards, Warm Air Heating and Air Conditioning
Systems ANSI/NFPA 90B
• CANADA: CAN/CGA-B149.1 National Standard of Canada. Natural Gas and Propane Installation Codes (NSCNGPIC)
STEP 2 -General Installation
• US: Current edition of the NFGC and NFPA 90B. For copies, contact the
National Fire Protection Association Inc.
Batterymarch Park
Quincy, MA 02269
or for only the NFGC, contact the
American Gas Association,
400 N. Capital, N.W.
Washington DC 20001
or www.NFPA.org
• CANADA: NSCNGPIC. For a copy contact:
Standard Sales, CSA International
178 Rexdale Boulevard
Etobicoke, (Toronto) Ontario Canada M9W 1RS
STEP 3 -Combustion and Ventilation Air
• US: Section 5.3 of the NFGC, air for Combustion and Ventilation
• CANADA: Part 7 of NSCNGPIC, Venting Systems and Air Supply
for Appliances
STEP 4 -Duct Systems
• US and CANADA: Air Conditioning Contractors Association
(ACCA) Manual D, Sheet Metal and Air Conditioning Contractors
Association National Association (SMACNA), or American Society of Heating, Refrigeration, and Air Conditioning Engineers
(ASHRAE) 1997 Fundamentals Handbook Chapter 32.
STEP 5 -Acoustical Lining and Fibrous Glass Duct
• US and CANADA: Current edition of SMACNA and NFPA 90B as
tested by UL Standard 181 for Class I Rigid Air Ducts
STEP 6 -Gas Piping and Gas Pipe Pressure Testing
• US: NFGC; chapters 2, 3, 4, & 9 and National Plumbing Codes
• CANADA: NSCNGPIC Part 5
STEP 7 -Electrical Connections
• US: National Electrical Code (NEC) ANSI/NFPA 70
• CANADA: Canadian Electrical Code CSA C22.1
These instructions cover minimum requirements and conform to existing national standards and safety codes. In some instances these
instructions exceed certain local codes and ordinances, especially
those who have not kept up with changing residential and non-HUD
modular home construction practices. These instructions are required
as a minimum for a safe installation.
Johnson Controls Unitary Products3
Page 4
420705-UIM-C-0310
FOR FURNACES INSTALLED IN THE COMMONWEALTH OF MASSACHUSETTS ONLY
For all side wall horizontally vented gas fueled equipment installed in
every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less
than seven (7) feet above finished grade in the area of the venting,
including but not limited to decks and porches, the following requirements shall be satisfied:
1.INSTALLATION OF CARBON MONOXIDE DETECTORS. At
the time of installation of the side wall horizontal vented gas
fueled equipment, the installing plumber or gasfitter shall
observe that a hard wired carbon monoxide detector with an
alarm and battery back-up is installed on the floor level where
the gas equipment is to be installed. In addition, the installing
plumber or gasfitter shall observe that a battery operated or
hard wired carbon monoxide detector with an alarm is installed
on each additional level of the dwelling, building or structure
served by the side wall horizontal vented gas fueled equipment.
It shall be the responsibility of the property owner to secure the
services of qualified licensed professionals for the installation of
hard wired carbon monoxide detectors
a.In the event that the side wall horizontally vented gas
fueled equipment is installed in a crawl space or an attic,
the hard wired carbon monoxide detector with alarm and
battery back-up may be installed on the next adjacent floor
level.
b.In the event that the requirements of this subdivision can
not be met at the time of completion of installation, the
owner shall have a period of thirty (30) days to comply with
the above requirements; provided, however, that during
said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2.APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the
above provisions shall comply with NFPA 720 and be ANSI/UL
2034 listed and IAS certified.
3.SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum
height of eight (8) feet above grade directly in line with the
exhaust vent terminal for the horizontally vented gas fueled
heating appliance or equipment. The sign shall read, in print
size no less than one-half (1/2) inch in size, "GAS VENT
DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS".
4.INSPECTION. The state or local gas inspector of the side wall
horizontally vented gas fueled equipment shall not approve the
installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance
with the provisions of 248 CMR 5.08(2)(a)1 through 4.
INSPECTION
As soon as a unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of the damage
should be noted on the carrier’s freight bill. A separate request for
inspection by the carrier’s agent should be made in writing. Also, before
installation, the unit should be checked for screws or bolts which may
have loosened in transit. There are no shipping or spacer brackets
which need to be removed from the interior of this unit.
FURNACE LOCATION AND CLEARANCES
The furnace shall be located using the following guidelines:
1.Where a minimum amount of air intake/vent piping and elbows will
be required.
2.As centralized with the air distribution as possible.
3.Where adequate combustion air will be available (particularly
when the appliance is not using outdoor combustion air).
4.Where it will not interfere with proper air circulation in the confined
space.
5.Where the outdoor vent terminal will not be blocked or restricted.
Refer to “VENT CLEARANCES” located in SECTION VII of these
instructions. These minimum clearances must be maintained in
the installation.
6.Where the unit will be installed in a level position with no more than
1/4” (6.4 mm) slope side-to-side and front-to-back to provide
proper condensate drainage.
Installation in freezing temperatures:
1.Furnace shall be installed in an area where ventilation facilities
provide for safe limits of ambient temperature under normal operating conditions. Ambient temperatures must not fall below 32°F
(0°C) unless the condensate system is protected from freezing.
Improper installation in an ambient below 32ºF (0.0° C) could create
a hazard, resulting in damage, injury or death.
2.Do not allow return air temperature to be below 55º F (13° C) for
extended periods. To do so may cause condensation to occur in
the main heat exchanger, leading to premature heat exchanger
failure.
3.If this furnace is installed in an unconditioned space and an
extended power failure occurs, there will be potential damage to
the internal components. Following a power failure situation, do
not operate the unit until inspection and repairs are performed.
Liquid anti-freeze will cause damage to internal plastic parts of this
furnace. D O NOT attempt to winterize the furnace using liquid
anti-freeze.
Clearances for access/service:
Ample clearances should be provided to permit easy access to the unit.
The following minimum clearances are recommended:
1.Twenty-four (24) inches (61 cm) between the front of the furnace
and an adjacent wall or another appliance, when access is
required for servicing and cleaning.
2.Eighteen (18) inches (46 cm) at the side where access is required
for passage to the front when servicing or for inspection or replacement of flue/vent connections.
In all cases, accessibility clearances shall take precedence over clearances for combustible materials where accessibility clearances are
greater.
Installation in a residential garage:
A gas-fired furnace for installation in a residential garage must be
installed so the burner(s) and the ignition source are located not less
than 18 inches (46 cm) above the floor, and the furnace must be located
or protected to avoid physical damage by vehicles.
Table 1:
Unit Clearances to Combustibles
ApplicationUpflowDownflow
Top 1" 0"
Vent0" 0"
Rear0" 0"
Side0" 0"
Front*0" 0"
FloorCombustible
ClosetYesYes
Line ContactNoNo
1. For combustible floors only when used with special sub-base.
* - 24" clearance in front and 18" on side recommended for service access.
All furnaces approved for alcove installation.
Combustible
1
4Johnson Controls Unitary Products
Page 5
420705-UIM-C-0310
Factory
installed
For duct attachment,
if needed.
Tie down
perforated
strap
Attach to
wall stud with a
nail or screw
Attach to Furnace
with screw
Vent
Pipe
Vent
Pipe
Vent
Drain
WALL
WALL
SUPPLY AIR DUCT
Combustion
Air Pipe
Combustion Air Pipe
SECTION II: DUCTWORK
DUCTWORK GENERAL INFORMATION
The duct system’s design and installation must:
1.Handle an air volume appropriate for the served space and within
the operating parameters of the furnace specifications.
2.Be installed in accordance of National Fire Protection Association
as outlined in NFPA standard 90B (latest editions) or applicable
national, provincial, state, and local fire and safety codes.
3.For Manufactured (Mobile) Home and Modular Home ReturnDuct System Installations: The return air duct and the return air
plenum are not required by the furnace manufacturer provided the
combustion air and vent system have been installed and maintained as a Two Pipe Sealed Combustion Air System and provided
a return air duct and plenum are not required by state, local or
regional codes.
4.Complete a path for heated or cooled air to circulate through the
air conditioning and heating equipment and to and from the conditioned space.
The cooling coil must be installed in the supply air duct, downstream of the furnace. Cooled air may not be passed over the heat
exchanger.
When the furnace is used with a cooling coil, the coil must be installed
parallel with, or in the supply air side of the furnace to avoid condensation in the primary heat exchanger. When a parallel flow arrangement is
used, dampers or other means used to control airflow must be adequate to prevent chilled air from entering the furnace. If manually operated, the damper must be equipped with means to prevent the furnace
or the air conditioner from operating unless the damper is in full heat or
cool position.
When replacing an existing furnace, if the existing plenum is not the
same size as the new furnace then the existing plenum must be
removed and a new plenum installed that is the proper size for the new
furnace. If the plenum is shorter than 12” (30.5 cm) the turbulent air flow
may cause the limit controls not to operate as designed, or the limit controls may not operate at all.
The duct system is a very important part of the installation. If the duct
system is improperly sized the furnace will not operate properly.
The ducts attached to the furnace plenum, should be of sufficient size
so that the furnace operates at the specified external static pressure
and within the air temperature rise specified on the nameplate.
The minimum plenum height is 12” (30.5 cm). The furnace will not
operate properly on a shorter plenum height. The minimum recommended rectangular duct height is 4 inches (10 cm) attached to the
plenum.
If a matching cooling coil is used, it may be placed directly on the furnace outlet and sealed to prevent leakage. If thermoplastic evaporator
‘A’ coil drain pans are to be installed in the upflow/horizontal configuration, then extra 2” minimum spacing may be needed to ensure against
drain pan distortion.
On all installations without a coil, a removable access panel is recommended in the outlet duct such that smoke or reflected light would be
observable inside the casing to indicate the presence of leaks in the
heat exchanger. This access cover shall be attached in such a manner
as to prevent leaks.
DUCT FLANGES
Four flanges are provided to attach ductwork to the furnace. These
flanges are rotated down for shipment. In order to use the flanges,
remove the screw holding an individual flange, rotate the flange so it is
in the upward position and reinstall the screw then repeat this for all 4
flanges.
If the flanges are not used, they must remain in the rotated down position as shipped.
FIGURE 1: Duct Attachment
DUCTWORK INSTALLATION AND SUPPLY PLENUM
CONNECTION - UPFLOW
Attach the supply plenum to the furnace outlet. The use of
an approved flexible duct connector is recommended on all
installations. This connection should be sealed to prevent
air leakage. The sheet metal should be crosshatched to
eliminate any popping of the sheet metal when the indoor
fan is energized.
Attachment to Structure
A furnace for installation in a manufactured (mobile) home must be
securely attached to the building structure. The perforated strap supplied with the furnace may be used for that purpose. Refer to Figure 2.
The duct system must be properly sized to obtain the correct airflow
for the furnace size that is being installed.
Refer to T able 6 or the furnace rating plate for the correct rise range
and static pressures.
If the ducts are undersized, the result will be high duct static pressures and/or high temperature rises which can result in a heat
exchanger OVERHEATING CONDITION. This condition can result
in premature heat exchanger failure, which can result in personal
injury, property damage, or death.
Johnson Controls Unitary Products5
FIGURE 2: Attachment to Structure
Page 6
420705-UIM-C-0310
FURNACE
WARM AIR PLENUM
WITH 1” FLANGES
FIBERGLASS
INSULATION
FIBERGLASS TAPE
UNDER FLANGE
COMBUSTIBLE FLOOR
BASE ACCESSORY
FLOOR BASE AND DUCTWORK INSTALLATION DOWNFLOW
Installations on combustible material or directly on any
floors must use a combustible floor base shown in Figure 3.
Follow the instructions supplied with the combustible floor
base accessory. This combustible floor base can be
replaced with a matching cooling coil, properly sealed to
prevent leaks. Follow the instructions supplied with the
cooling coil cabinet for installing the cabinet to the duct connector. Plug intake and vent pipe holes in bottom panel and
move grommet to desired vent side exit.
Downflow Air Conditioning Coil Cabinet
The furnace should be installed with coil cabinet part number specifically intended for downflow application. If a matching cooling coil is
used, it may be placed directly on the furnace outlet and sealed to prevent leakage. For details of the coil cabinet dimensions and installation
requirements, refer to the installation instructions supplied with the coil
cabinet.
Attach the air conditioning coil cabinet to the duct connector, and then
position the furnace on top of the coil cabinet. The connection to the furnace, air conditioning coil cabinet, duct connector, and supply air duct
must be sealed to prevent air leakage.
DOWNFLOW DUCT CONNECTORS
All downflow installations must use a suitable duct connector approved
by the furnace manufacturer for use with this furnace. The duct connectors are designed to be connected to the rectangular duct under the
floor and sealed. Refer to the instructions supplied with the duct connector for proper installation. Refer to the separate accessory parts list
at the end of these instructions for the approved accessory duct connectors.
DOWNFLOW RETURN PLEN UM CONN ECTION
The return air duct and the return air plenum are not required by the furnace manufacturer provided the combustion air and vent system have
been installed and maintained as a Two Pipe Sealed Combustion Air
System and provided a return air duct and plenum are not required by
state, local or regional codes.
• If a return air duct system and return plenum are required by
state, local or regional codes then the return plenum may be connected to the furnace inlet and must terminate outside the space
containing the furnace. The external air filter accessory shown in
Figure 4 is designed and recommended for use inside the return
plenum. Attach the return plenum to the furnace inlet duct
flanges. This is typically through the use of S cleat material when
a metal plenum is used. Installations where a return air duct system is utilized, the use of a listed flexible duct connector is recommended. The connection of the plenum to the furnace and all the
ducts connecting to the plenum must be sealed to prevent air
leakage. The sheet metal should be crosshatched to eliminate
any popping of the sheet metal when the indoor fan is energized.
The duct system is a very important part of the installation. If the
duct system is improperly sized the furnace will not operate properly. The ducts attached to the furnace must be of sufficient size
so that the furnace operates at the specified external static pressure and within the air temperature rise specified on the nameplate and in Table 3.
• If the return air duct and plenum are not required by state, local or
regional codes then the filter can be attached to the top of the furnace as shown in Figure 6.
When replacing an existing the furnace, if a return air plenum is
used and the existing plenum is not the same size as the new furnace, then the existing plenum must be removed and a new plenum
installed that is the proper size for the new furnace. If a return duct
mounted filter rack or filter grille is being used, see the instructions
provided with that accessory for proper hole cut size.
FIGURE 3: Combustible Floor Base Accessory
RESIDENTIAL AND MODULAR HOME UPFLOW
RETURN PLENUM CONNECTION
Return air may enter the furnace through the side(s) or bottom depending on the type of application. Return air may not be connected into the
rear panel of the unit.
BOTTOM RETURN AND ATTIC INSTALLATIONS
Bottom return applications normally pull return air through a base platform or return air plenum. Be sure the return platform structure or return
air plenum is suitable to support the weight of the furnace.
The internal bottom panel must be removed for this application.
Attic installations must meet all minimum clearances to combustibles
and have floor support with required service accessibility.
Downflow Filters
Downflow furnaces typically are installed with the filters located above
the furnace, extending into the return air plenum or duct. Any branch
duct (rectangular or round duct) attached to the plenum must attach to
the vertical plenum above the filter height.
Filter(s) may be located in the duct system external to the furnace using
an external duct filter box attached to the furnace plenum or at the end
of the duct in a return filter grille(s). The use of straps and/or supports is
required to support the weight of the external filter box.
FIGURE 4: Mobile Home Filter Frame Accessories
6Johnson Controls Unitary Products
Page 7
420705-UIM-C-0310
Screw x2
Blend Air
Bracket
18”
Max.
9155 Series
Filter Kit
Gas
Furnace
Blend Air Bracket (3500-5241)
mounted to wall next to furnace
Blend Air
Damper
Coil
Cabinet
Run flexible duct tubing
as close to the wall
as possible
UPFLOW
DOWNFLOW
Furnace
Furnace
Alternate Flange Location
(Used for downflow installations)
Factory Flange
Location(Used for
upflow installations)
BLEND AIR INSTALLATIONS
Upflow
This bracket is to be used only for Alcove application on the 90% Gas
Furnaces. It helps in installation of Blend Air Damper Tube close to the
furnace. It is recommended that the Blend Air be installed with the help
of this bracket as close to the furnace as possible. The Blend Air
Bracket Assembly should be installed no higher than 18 inches above
the furnace. See Figure 6.
FIGURE 5: Blend Air Bracket
Downflow
This bracket is to be used only for Alcove application on the 95% Gas
Furnaces. It helps in installation of Blend Air Damper Tube close to the
furnace. It is recommended that the Blend Air be installed with the help
of this bracket as close to the furnace as possible. The Blend Air
Bracket Assembly should be installed as close to the return air grille as
possible. See Figure 5.
COIL INSTALLATION
On all installations without a coil, a removable access panel is recommended in the outlet duct such that smoke or reflected light
would be observable inside the casing to indicate the presence of
leaks in the heat exchanger. This access cover shall be attached in
such a manner as to prevent leaks.
COIL/FURNACE ASSEMBLY - MC/FC/PC SERIES
COILS
FIGURE 7: Vertical Applications
FURNACE ASSEMBLY - MC & FC SERIES COILS
These coils are factory shipped for installation in either upflow or downflow applications with no conversion.
Position the coil casing over or under the furnace opening as shown in
Figure 7 after configuring coil flanges as required see “Coil Flange” section below.
COIL FLANGE INSTALLATION
The coils include removable flanges to allow proper fit up with furnaces
having various inlet and outlet flange configurations. The two flanges
are attached to the top of the coil in the factory during production. For
proper configuration of flanges. Refer to Figure 8.
FIGURE 6: Blend Air Installation (Optional)
Johnson Controls Unitary Products7
FIGURE 8: Coil Flange
Page 8
420705-UIM-C-0310
Flexible
Duct Collar
Do not drill
or Screw
this flange
Field
Fabricated
Ductwork
Upflow
Coil
Upflow
Furnace
Secondary
Drain
Primary
Drain
D
C
(Min)
Alternate
Drain Location
FURNACE
WARM AIR PLENUM
WITH 1” FLANGES
FIBERGLASS
INSULATION
FIBERGLASS TAPE
UNDER FLANGE
COMBUSTIBLE FLOOR
BASE ACCESSORY
LEFT SIDE VENTRIGHT SIDE VENT
Rotate vent
blower 90°
either way
FURNACE ASSEMBLY - PC SERIES COILS
These upflow coils are designed for installation on top of upflow furnaces only.
If the coil is used with a furnace of a different size, use a 45° transition
to allow proper air distribution through the coil.
1.Position the coil casing over the furnace opening as shown in Figure 9.
2.Place the ductwork over the coil casing flange and secure.
3.Check for air leakage between the furnace and coil casing and
seal appropriately.
Do not drill any holes or drive any screws into the front duct
flange on the coil in order to prevent damaging coil tubing. See
Figure 9.
DOWNFLOW DUCT CONNECTORS
All downflow installations must use a suitable duct connector approved
by the furnace manufacturer for use with this furnace. The duct connectors are designed to be connected to the rectangular duct under the
floor and sealed. Refer to the instructions supplied with the duct connector for proper installation. Refer to the separate accessory parts list
at the end of these instructions for the approved accessory duct connectors.
FIGURE 9: PC Series Upflow Coil Installation
Table 2: Coil Projection Dimensions - PC Series Coils
COIL SIZEDIMENSION “C” INCH
PC183-1/2
PC244-1/2
PC30, PC32, PC354-1/2
PC42, PC43, PC36, PC375-1/2
PC486-1/2
PC609
Dimension “C” should be at least 2/3 of dimension “D”. See Figure 9.
CRITICAL COIL PROJECTION
The coil assembly must be located in the duct such that a minimum distance is maintained between the top of the coil and the top of the duct.
Refer to Table 6.
FIGURE 10: Combustible Floor Base Accessory
DOWNFLOW APPLICATION
Furnace is shipped in downflow configuration. It may be necessary to
rotate the vent blower 180° left so that the vent pipe passes through the
side of the furnace casing. See Figure 11.
All applications require the use of a field installed filter. All filters and
mounting provision must be field supplied.
Filters must be installed external to the furnace cabinet. DO NOT
attempt to install filters inside the furnace.
Single side return above 1800 CFM is approved as long as the filter
velocity does not exceed filter manufacturer’s recommendation and
a transition is used to allow use on a 20x25 filter.
1200 (34.0)B16 x 2516 x 25
1600 (45.3)B16 x 2516 x 25
1600 (45.3)C16 x 2520 x 25
2000 (56.6)C(2) 16 x 2520 x 25
2200 (62.3)C(2) 16 x 2520 x 25
2000 (56.6)D(2) 16 x 2522 x 25
1.Air velocity through throwaway type filters may not exceed 300 feet per min-
2.Do not exceed 1800 CFM using a single side return and a 16x25 filter. For
Johnson Controls Unitary Products9
ute (91.4 m/min). All velocities over this require the use of high velocity filters.
CFM greater than 1800, you may use two side returns or one side and the
bottom or one side return with a transition to allow use of a 20x25 filter.
Size
Side
Size
(in)
Cabinet Dimensions (Inches)
Approximate
Operating Weights
AA (cm)BB (cm)CC (cm)Lbs
SIDE RETURN - UPFLOW ONLY
Locate the “L” shaped corner locators. These indicate the size of the cutout to be made in the furnace side panel. Refer to Figure 13.
Bottom
(in)
FIGURE 13: Side Return Cutout Markings
Install the side filter rack following the instructions provided with that
accessory. If a filter(s) is provided at another location in the return air
system, the ductwork may be directly attached to the furnace side
panel.
Some accessories such as electronic air cleaners and pleated
media may require a larger side opening. Follow the instructions
supplied with that accessory for side opening requirements. Do not
cut the opening larger than the dimensions shown in Figure 12.
Page 10
420705-UIM-C-0310
INLET
WRENCH
BOSS
INLET
PRESSURE
PORT
ON
OFF
ON/OFF SWITCH
(Shown in ON position)
MAIN REGULATOR
ADJUSTMENT
OUTLET
OUTLET
PRESSURE
PORT
VENT PORT
Upflow
Configuration
Downflow
Configuration
External
Manual
Shut-off
Valve
External
Manual
Shut-off
Valve
To Gas
Supply
To Gas
Supply
To Gas
Supply
To Gas
Supply
Drip
Leg
Drip
Leg
Drip
Leg
Drip
Leg
Gas
Pipe
Gas
Valve
Gas
Pipe
Gas
Valve
Ground
Union
Ground
Union
Ground
Union
Ground
Union
NOTE: Ground Union maybe installed inside or outside unit.
SECTION IV: GAS PIPING
GAS SAFETY
Plan your gas supply before determining the correct gas pipe entry.
Use 90-degree service elbow(s), or short nipples and conventional
90-degree elbow(s) to enter through the cabinet access holes.
FIGURE 14: Gas Valve
An overpressure protection device, such as a pressure regulator,
must be installed in the gas piping system upstream of the furnace
and must act to limit the downstream pressure to the gas valve so it
does not exceed 0.5 PSI (14" w.c. (3.48 kPa). Pressures exceeding
0.5 PSI (14” w.c. (3.48 kPa) at the gas valve will cause damage to
the gas valve, resulting in a fire or explosion or cause damage to
the furnace or some of its components that will result in property
damage and loss of life.
GAS PIPING INSTALLATION
Properly sized wrought iron, approved flexible or steel pipe must be
used when making gas connections to the unit. If local codes allow the
use of a flexible gas appliance connection, always use a new listed connector. Do not use a connector that has previously serviced another gas
appliance.
Some utility companies or local codes require pipe sizes larger than the
minimum sizes listed in these instructions and in the codes. The furnace
rating plate and the instructions in this section specify the type of gas
approved for this furnace - only use those approved gases. The installation of a drip leg and ground union is required. Refer to Figure 15.
FIGURE 15: Upflow/Downflow Gas Piping
An accessible manual shutoff valve must be installed upstream of
the furnace gas controls and within 6 feet (1.8 m) of the furnace.
The furnace must be isolated from the gas supply piping system by
closing its individual external manual shutoff valve during any pressure
testing of the gas supply piping system at pressures equal to or less
than 1/2 psig (3.5 kPa).
The gas valve body is a very thin casting that cannot take any
external pressure. Never apply a pipe wrench to the body of the gas
valve when installing piping. A wrench must be placed on the octagon hub located on the gas inlet side of the valve. Placing a wrench
to the body of the gas valve will damage the valve causing improper
operation and/or the valve to leak.
Gas piping may be connected from either side of the furnace using any
of the gas pipe entry knockouts on both sides of the furnace. Refer to
Figure 12.
10Johnson Controls Unitary Products
GAS ORIFICE CONVERSION FOR PROPANE (LP)
This furnace is constructed at the factory for natural gas-fired operation,
but may be converted to operate on propane (LP) gas by using a factory-supplied LP conversion kit.
The gas supply must be shut off prior to disconnecting the electrical power, before proceeding with the conversion.
SHOCK HAZARD - Turn off electrical supply to furnace.
1.Shut off gas supply at valve upstream from furnace or at meter as
required.
2.Disconnect gas supply piping from gas valve on furnace.
3.Disconnect electrical wires from gas valve, noting which wires are
connected to which terminals
4.Remove the screws that attach the gas manifold to the burner support box.
5.Remove and discard natural gas orifices.
Page 11
6.Remove LP (propane) orifices from the bag in the Customer
Packet.
7.Install the LP (propane) gas orifices supplied with the furnace.
Tighten to 15 - 25 inch - pounds of torque.
8.Reinstall the manifold in the assembly by reversing the removal
process.
9.Reconnect the wires to the proper terminals on the gas valve.
10. Unscrew the gas valve regulator with the blue cap and turn it
upside down so the letters “LP” are upright. Replace the blue cap
on the regulator.
11. Remove the natural gas tag and replace with the propane gas tag
supplied in the orifice bag.
12. Remove the blue conversion label on the furnace door after the
furnace has been converted.
13. Reconnect the gas supply piping to the gas valve and insure that
all gas connections are tight.
14. Remove pressure tap plugs from gas valve and connect water
gauge to the pressure tap ports. See Figure 14 for location of the
gas valve pressure taps and pressure regulator adjustment.
15. Turn on gas supply to furnace and check all gas connections with
suitable leak detector.
Table 5: Nominal Manifold Pressure - High Fire
Manifold Pressures (in wc)Manifold Pressures (kpa)
Never use an open flame to check for leaks. Fire or explosion
could occur. Since some leak solutions including soap and
water may cause corrosion or stress cracking, the piping must
be rinsed with water after testing unless it has been determined
that the leak test solution is non-corrosive.
HIGH ALTITUDE GAS ORIFICE CONVERSION
This furnace is constructed at the factory for natural gas-fired operation
at 0 –7,999 feet (0-m – 2,438 m) above sea level.
The manifold pressure must be changed in order to maintain proper
and safe operation when the furnace is installed in a location where the
altitude is greater than 7,999 feet (2,438 m) above sea level. Refer to
Table 5 for proper manifold pressure settings.
HIGH ALTITUDE PRESSURE SWITCH CONVERSION
For installation where the altitude is less than 5,000 feet (1,524m), it is
not required that the pressure switch be changed unless you are in an
area subject to low pressure inversions.
For altitudes above 5,000 feet, see kits below.
S1-1PS3306 - 080
S1-1PS3307 - 060
S1-1PS3302 - 100, 120
29.80.870.870.87
(MJ/cu m)
Gas Heating Value
PROPANE AND HIGH ALTITUDE CONVERSION KITS
It is very important to choose the correct kit and/or gas orifices for the altitude and the type of gas for which the furnace is being installed.
Only use natural gas in furnaces designed for natural gas. Only use propane (LP) gas for furnaces that have been properly converted to use pro-
pane (LP) gas. Do not use this furnace with butane gas.
Incorrect gas orifices or a furnace that has been improperly converted will create an extremely dangerous condition resulting in premature heat
exchanger failure, excessive sooting, high levels of carbon monoxide, personal injury, property damage, a fire hazard and/or death.
High altitude and propane (LP) conversions are required in order for the appliance to satisfactory meet the application.
An authorized distributor or dealer must make all gas conversions.
In Canada, a certified conversion station or other qualified agency, using factory specified and/or approved parts, must perform the conversion.
The installer must take every precaution to insure that the furnace has been converted to the proper gas orifice size when the furnace is installed.
Do not attempt to drill out any orifices to obtain the proper orifice size. Drilling out a gas orifice will cause misalignment of the burner flames,
causing premature heat exchanger burnout, high levels of carbon monoxide, excessive sooting, a fire hazard, personal injury, property damage
and/or death.
SECTION V: ELECTRICAL POWER
ELECTRICAL POWER CONNECTIONS
Field wiring to the unit must be grounded. Electric wires that are field
installed shall conform to the temperature limitation for 63°F (35°C) rise
wire when installed in accordance with instructions. Refer to Table 6 in
these instructions for specific furnace electrical data.
Johnson Controls Unitary Products11
Use copper conductors only.
Page 12
420705-UIM-C-0310
Electrical Entry
Junction
Box
L1-Hot
Neutral
Connect ground
lead to screw
BLK
WHT
BLK
WHT
GRN
BLK (HOT)
WHT (NEUTRAL)
GRN
NOMINAL
115 VOLT
ROOM
THERMOSTAT
FURNACE
CONTROL
CONDENSING
UNIT
TO AIR CONDITIONER
CONTROLS
R
W
G
Y
C
R
W
G
C
COMMON T’STAT CONNECTION
Y/Y2
Table 6: Ratings & Physical / Electrical Data
InputOutput
Nominal
MBH kW MBH kWCFM
Airflow
m
3
AFUE
/min
Air Temp.
%
Rise
°F°C°F°CHP Amps
6017.65716.7120034.095.530-60 19-3616071.11/34.811 x 81510.014
8023.47622.3120034.095.535-65 19-3616573.91/34.811 x 81510.014
8023.47622.3160045.395.535-65 19-3615568.31/27.511 x 101511.514
100 29.39527.8160045.395.535-6519-3616573.91/27.511 x 101511.514
100 29.39527.8200056.695.535-6519-3615568.3114.5 11 x 112017.012
120 35.1 114 33.4 200056.695.535-6519-3616071.1114.5 11 x 112017.012
Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local code s.
The furnace shall be installed so that the electrical components are protected from water.
Max. Outlet
Air Temp
Blower
Blower
Size
Max
Over-Current
Protect
Total Unit
Amps
Min. wire Size
(awg) @ 75 ft
one way
SUPPLY VOLTAGE CONNECTIONS
FIGURE 16: Electrical Wiring
1.Provide a power supply separate from all other circuits. Install
overcurrent protection and disconnect switch per local/national
electrical codes. The switch should be close to the unit for convenience in servicing. With the disconnect or fused switch in the OFF
position, check all wiring against the unit wiring label. Refer to the
wiring diagram in this instruction.
3.The furnace's control system requires correct polarity of the power
supply and a proper ground connection. Refer to Figure 16.
The power connection leads and wiring box may be relocated to the
left side of the furnace. Remove the screws and cut wire tie holding
excess wiring. Reposition on the left side of the furnace and fasten
using holes provided.
LOW VOLTAGE CONTROL WIRING CONNECTIONS
Install the field-supplied thermostat by following the instructions that
come with the thermostat. With the thermostat set in the OFF position
and the main electrical source disconnected, connect the thermostat
wiring from the wiring connections on the thermostat to the terminal
board on the ignition module, as shown in Figure 18. Electronic thermostats may require the common wire to be connected. Apply strain relief
to thermostat wires passing through cabinet. If air conditioning equipment is installed, use thermostat wiring to connect the Y and C terminals on the furnace control board to the proper wires on the condensing
unit (unit outside).
Set the heat anticipator in the room thermostat to 0.4 amps. Setting
it lower will cause short cycles. Setting it higher will cause the room
temperature to exceed the set points.
FIGURE 17: Line Wiring Connections
2.Remove the screws retaining the wiring box cover. Route the
power wiring through the opening in the unit into the junction box
with a conduit connector or other proper connection. In the junction box there will be 3 wires, a Black Wire, a White Wire. Connect
the power supply as shown on the unit-wiring label on the inside of
the blower compartment door or the wiring schematic in this section. The black furnace lead must be connected to the L1 (hot)
wire from the power supply. The white furnace screw must be connected to neutral. Connect the power supply ground to the green
screw (equipment ground) An alternate wiring method is to use a
field provided 2” (5.1 cm) x 4” (10.2 cm) box and cover on the ou tside of the furnace. Route the furnace leads into the box using a
protective bushing where the wires pass through the furnace
panel. After making the wiring connections replace the wiring box
cover and screws. Refer to Figure 16.
12Johnson Controls Unitary Products
Some electronic thermostats do not have adjustable heat anticipators. They should be set to six cycles per hour. Follow the thermostat manufacturer's instructions.
The 24-volt, 40 VA transformer is sized for the furnace components
only, and should not be connected to power auxiliary devices such as
humidifiers, air cleaners, etc. The transformer may provide power for an
air conditioning unit contactor.
FIGURE 18: Single Stage Heat Thermostat Connections
Page 13
ACCESSORY CONNECTIONS
115 VOLT
HUMIDIFER
115 VOLT
ELECTRONIC
AIR CLEANER
EAC HOT
HUM. HOT
BLK
WHT
EAC
HUM
NEUTRALS
SWITCHED
CIRCUITS
BLK
WHT
NOTICE
To Open Or
Vented Drain
Tee
5” Min.
Open Stand Pipe
(Anti-siphon air vent)
NOTICE
The furnace control will allow power-switching control of various accessories. Refer to Figure 19, for connection details.
420705-UIM-C-0310
The furnace, evaporator coil, and humidifier drains may be combined and drained together. The evaporator coil drain may have an
external, field-supplied trap prior to the furnace drain connection to
prevent conditioned air leakage. All drain connections (furnace,
evaporator coil, or humidifier) must be terminated into an open or
vented drain as close to the respective equipment as possible.
Regular maintenance is required on condensate drainage system.
Condensate must be disposed of properly. Follow local plumbing
or wastewater codes. The drain line must maintain a 1/4" per foot
(20 mm/m) downward slope to the drain.
FIGURE 19: Accessory Connections
ELECTRONIC AIR CLEANER CONNECTION
Two 1/4” (0.64 cm) spade terminals (EAC and NEUTRAL) for electronic
air cleaner connections are located on the control board. The terminals
provide 115 VAC (1.0 amp maximum) during circulating blower operation.
HUMIDIFIER CONNECTION
Two 1/4” (0.64 cm) spade terminals (HUM and NEUTRAL) for humidifier connections are located on the control board. The terminals provide
115 VAC (1.0 amp maximum) during heating system operation.
A mounting hole is provided on the control panel next to the furnace
control board for mounting a humidifier transformer if required.
SECTION VI: CONDENSATE PIPING AND
FURNACE VENTING CONFIGURATION
CONDENSATE DRAIN LOCATION
As shipped from the factory:
• For all 040, 060, & 080K input furnaces the main drain is plumbed
through the casing right-side opening when viewed from the front
of the furnace.
• For all 100, 120, & 130K input furnaces the main drain is plumbed
through the casing left-side opening when viewed from the front
of the furnace.
If an external vent tee is being installed, then it must have its own
condensate trap before it is disposed into an open or vented drain.
This is not to be considered as a second trap as referenced
elsewhere in this document.
The Figures 22 - 23 show the condensate drain arrangement for the
various possible furnace and vent blower positions.
The condensate hoses must slope downwards at all points.
The furnace condensate pan is self priming and contains an internal
trap to prevent flue gas leaking. Do not install an external condensate trap.
When drain hose routing changes are required (shown in Figures 22-
23), be sure to cap all un-used openings.
If rerouting hoses - excess length should be cut off so that no sagging
loops will collect and hold condensate - which will cause the furnace to
not operate.
No hose clamps are needed for connecting to the condensate pan.
Johnson Controls Unitary Products13
FIGURE 20: Typical. Condensate drain, vertical installation
The condensate will flow to the drain better if an open stand pipe is
installed in the drain line. See Figure 20.
If evaporator coil or humidifier drains are combined with the furnace
drain, then the open stand pipe could be raised higher, above the 5”
minimum.
A loop has been added to the pressure switch vacuum hose. However, ensure that all pressure switch hoses are routed such that
they prevent any condensate from entering the pressure switch.
Page 14
420705-UIM-C-0310
Connect to Drain
Trap
Combustion Air Pipe
Tee with Drain Trap
Exhaust Pipe
It is possible for condensation to form inside the combustion air
(intake) pipe in the summer months if significant length of combustion air pipe passes through conditioned space. This problem can
be averted by the addition of a simple drain tee, or a drain tee with a
drain on the combustion air pipe as close to the furnace as possible, as shown in Figure 21. This is true for all long horizontal venting in any furnace configuration. This will prevent the condensate
from entering the furnace.
CONDENSATE DRAIN TERMINATION
A condensate sump pump MUST be used if required by local codes, or
if no indoor floor drain is available. The condensate sump pump must
be approved for use with acidic condensate.
DO NOT terminate the condensate drain in a chimney, or where the
drain line may freeze. If the drain line will be exposed to temperatures below freezing, adequate measures must be taken to prevent
the drain line from freezing. Failure to provide proper protection
from freezing can result in improper operation or damage to the
equipment and possible property damage. When exposed to temperatures below freezing, use of a 3 to 6 watt per foot at 115 VAC,
40°F (4.4°C) self-regulating, shielded and waterproof heat tape is
recommended on the drain line outside the furnace.
DO NOT trap the drain line at any other location than at the condensate drain trap supplied with the furnace.
Liquid anti-freeze will cause damage to internal plastic parts of this
furnace. DO NOT attempt to winterize the furnace using liquid
anti-freeze.
FIGURE 21: Typical. Combustion Pipe Drain Tee
14Johnson Controls Unitary Products
Page 15
INDUCER ROTATED FOR
LEFT SIDE VENTING
UPFLOW
AS RECEIVED
INDUCER ROTATED FOR
RIGHT SIDE VENTING
When drain hose routing changes are required, be sure to cap all un-used openings.
If rerouting hoses - excess length should be cut off so that no sagging loops will collect
and hold condensate, which will cause the furnace to not operate.
Shorten
pressure
switch hose
Re-route and
shorten
pressure
switch hose
Shorten
rain gutter
hose
Move rain
gutter hose
to this position
For 100, 120 input furnaces, the condensate
drain is plumbed toward the left casing outlet from the factory.
For 060 & 080K input furnaces, the condensate
drain is plumbed toward the right casing outlet from the factory.
Condensate drain may exit cabinet on either side.
1
2
1
2
420705-UIM-C-0310
FIGURE 22: Upflow Configuration
Johnson Controls Unitary Products15
Page 16
420705-UIM-C-0310
AIRFLOW
AIRFLOW
Move rain
gutter hose
to this position
DOWNFLOW - INDUCER ROTATED
FOR LEFT SIDE VENTING
DOWNFLOW - INDUCER ROTATED
FOR RIGHT SIDE VENTING
Move pressure switch
hose to this position.
NOTE: May require
the longer hose that
is provided with
wider cabinets
Move condensate drain
hose to this position
(May exit either side
of the cabinet)
Move rain gutter
hose to this position
When drain hose routing changes are required, be sure to cap all un-used openings.
If rerouting hoses - excess length should be cut off so that no sagging loops will collect
and hold condensate, which will cause the furnace to not operate.
1
2
3
FIGURE 23: Downflow Configuration
16Johnson Controls Unitary Products
Page 17
420705-UIM-C-0310
A
A
A
A
STANDARD ELBOW
LONG (SWEEP) ELBOW
SECTION VII: COMBUSTION AIR AND
VENT SYSTEM
COMBUSTION AIR AND VENT SAFETY
This Category IV, dual certified direct vent furnace is designed for residential or MH application. It may be installed without modification to the
condensate system in a basement, garage, equipment room, alcove,
attic or any other indoor location where all required clearance to combustibles and other restrictions are met. The combustion air and the
venting system must be installed in accordance with Section 5.3, Air for
Combustion and Ventilation, of the National Fuel Gas Code Z223.1/
NFPA 54 (latest edition), or Sections 7.2, 7.3 or 7.4 of CSA B149.1,
National Gas and Propane Codes (latest edition) or applicable provisions of the local building code and these instructions.
The “VENT SYSTEM” must be installed as specified in these
instructions for Manufactured (Mobile) Home and Modular Homes.
The sealed combustion air / vent system is the only configuration
that can be installed in a Manufactured (Mobile) Home.
Vertical vent termination must be secured for transit.
This furnace may not be common vented with any other appliance,
since it requires separate, properly sized air intake and vent lines.
The furnace shall not be connected to any type of B, BW or L vent
or vent connector, and not connected to any portion of a factorybuilt or masonry chimney
The furnace shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel.
When combustion air pipe is installed above a suspended ceiling or
when it passes through a warm and humid space, the pipe must be
insulated with 1/2” Armaflex or other heat resistant type insulation if
two feet or more of pipe is exposed.
Vent piping must be insulated if it will be subjected to freezing temperatures such as routing through unheated areas or through an
unused chimney.
3.Three vent terminal elbows (two for the vent and one for the combustion air intake) are already accounted for and need not be
included in the equivalent length calculation.
4.All combustion air and vent pipe must conform to American
National Standards Institute (ANSI) and American Society for Testing and Materials (ASTM) standards D1785 (Schedule 40 PVC),
D2665 (PVC-DWV), F891 (PVC-DWV Cellular Core), D2261
(ABS-DWV) or F628 (Schedule 40 ABS). Pipe cement and primer
must conform to ASTM Standard D2546 (PVC) or D2235 (ABS). If
ABS pipe is to be used, any joint where ABS pipe is joined to PVC
pipe must be glued with cement that is approved for use with
BOTH materials. Metallic materials must not
be used for venting or
air intake.
5.If a flexible connector is used in the vent system, it must be made
of a material that is resistant to acidic exposure and to at least
225° F temperature. Flexible connectors are also allowed in the
combustion air pipe.
6.All models are supplied with 2" vent connections. When the pipe
must be increased to 3" diameter, the transition from 2" to 3" must
be done as close to the furnace as possible. For upflow models,
the transition from 2" to 3" should be done immediately above the
furnace. For downflow or horizontal models, the transition from 2"
to 3" pipe should be done immediately after exiting the furnace.
7.In Canada, vents shall be certified to ULC S636, Standard for T ype
BH Gas Venting Systems.
8.In Canada, the first three feet (900 mm) of the vent must be readily
accessible for inspection.
9.For single pipe systems it is recommended to install the combustion air coupling provided and install approximately 18” of PVC
pipe on the furnace.
The size of pipe required will be determined by the furnace model, the
total length of pipe required and the number of elbows required.
Table 7 lists the maximum equivalent length of pipe allowed for each
model of furnace. The equivalent length of elbows is shown in Table 9.
The equivalent length of the vent system is the total length of straight
pipe PLUS the equivalent length of all of the elbows.
The following rules must also be followed:
1.Long radius (sweep) elbows are recommended. Standard elbows
may be used, but since they have a longer equivalent length, they
will reduce the total length of pipe that will be allowed. Short radius
(plumbing vent) elbows are not allowed. The standard dimensions
of the acceptable elbows are shown below.
2.The maximum equivalent length listed in Table 7 is for the vent piping and the air intake piping separately. For example, if the table
allows 65 equivalent feet for a particular model, then the vent can
have 65 equivalent feet of pipe, AND the combustion air intake can
have another 65 equivalent feet of pipe.
Dimensions are those required in Standard ASTM D-3311.
Page 18
420705-UIM-C-0310
TABLE 9:
Example:
An 80,000 BTUH furnace requires 32 feet of pipe and five 90º elbows.
Using 2" pipe and standard elbows, the total equivalent length will be:
This exceeds the 65 foot maximum equivalent length of 2" pipe allowed
for that model and is thus not
By using sweep elbows, the total equivalent length will be:
This is less than the 65 foot maximum equivalent length of 2" pipe
allowed for that model and is thus acceptable.
Alternatively, using 3" pipe and standard elbows, the total equivalent
length will be:
This is less than the 90 foot maximum equivalent length of 3" pipe
allowed for that model and is thus acceptable.
TABLE 10:
Equivalent Length of Fittings
FittingEquivalent Length
2" 90º sweep elbow5 feet of 2" pipe
2" 45º sweep elbow2-1/2 feet of 2" pipe
2" 90º standard elbow7 feet of 2" pipe
2" 45º standard elbow3-1/2 feet of 2" pipe
3" 90º sweep elbow5 feet of 3" pipe
3" 45º sweep elbow2-1/2 feet of 3" pipe
3" 90º standard elbow7 feet of 3" pipe
3" 45º standard elbow3-1/2 feet of 3" pipe
2" corrugated connector10 feet of 2" pipe
3" corrugated connector10 feet of 3" pipe
32 feet of 2" pipe =32 equivalent feet
5 - 90º standard 2" elbows = (5 x 7) = 35 equivalent feet
Total = 67 equivalent feet of 2" pipe
acceptable.
32 feet of 2" pipe =32 equivalent feet
5 - 90º sweep 2" elbows = (5 x 5) = 25 equivalent feet
Total = 57 equivalent feet of 2" pipe
32 feet of 3" pipe =32 equivalent feet
5 - 90º standard 3" elbows = (5 x 7) = 35 equivalent feet
Total = 67 equivalent feet of 3" pipe
Combustion Air Intake and Vent Connection Size at Furnace
(All Models)
FURNACE VENT CONNECTION SIZES
Furnace InputAll
Intake Pipe Size2” (5.1 cm)
Vent Pipe Size2” (5.1 cm)
Furnace vent pipe connections are sized for 2” (5.1 cm). pipe. Any
pipe size change must be made outside the furnace casing in a vertical pipe section to allow proper drainage of condensate. An offset
using two 45º (degree) elbows will be required for plenum clearance when the vent is increased to 3” (7.6 cm).
Accessory concentric vent / intake termination kits 1CT0302 and
1CT0303, and for Canadian applications 1CT0302-636 and
1CT0303-636 are available and approved for use with these furnaces. Horizontal sidewall vent terminations kits 1HT0901 &
1HT0902 are also approved for use with these furnaces.
COMBUSTION AIR AND VENT PIPING ASSEMBLY
The final assembly procedure for the combustion air and vent piping is
as follows:
1.Cut piping to the proper length beginning at the furnace.
2.Deburr the piping inside and outside.
3.Chamfer (bevel) the outer edges of the piping.
4.Dry-fit the vent piping assembly from the furnace to the outside termination checking for proper fit support and slope.
5.Dry-fit the combustion air piping assembly checking for proper fit,
support and slope on the following systems:
a.Sealed combustion air systems from the furnace to the out-
side termination.
b.Ventilated combustion air systems from the furnace to the
attic or crawl space termination.
Solvent cements are flammable and must be used in well-ventilated
areas only. Keep them away from heat, sparks and open flames.
Do not breathe vapors and avoid contact with skin and eyes.
6.Disassemble the combustion air and vent piping, apply cement
primer and the cement per the manufactures instructions. Primer
and cement must conform to ASTM D2564 for PVC, or ASTM
D2235 for ABS piping.
7.All joints must provide a permanent airtight and watertight seal.
8.Support the combustion air and vent piping such that it is angled a
minimum of 1/4” per foot (21 mm/m) so that condensate will flow
back towards the furnace. Piping should be supported with pipe
hangers to prevent sagging.
9.Seal around the openings where the combustion air and / or vent
piping pass through the roof or sidewalls.
COMBUSTION AIR / VENTING
18Johnson Controls Unitary Products
The vent must be installed with the minimum required clearances,
and must comply with local codes and requirements.
Page 19
VENT CLEARANCES
L
E
D
B
V
V
V
X
V
B
V
J
X
B
B
B
V
V
F
V
C
B
X
V
I
V
G
H
A
M
K
OPERABLE
FIXED
CLOSED
VENT TERMINAL
AIR SUPPLY
AREA WHERE TERMINAL IS NOT PERMITTED
FIXED
CLOSED
FIGURE 25: Home Layout
420705-UIM-C-0310
Direct Vent Terminal Clearances
A. Clearance above grade, veranda, porch, deck, or
C. Clearance to permanently closed window12” (30.5 cm)12” (30.5 cm)
D. Vertical clearance to ventilated soffit located
above the terminal within a horizontal distance
of 2 feet (61 cm) from the center line of the terminal
E. Clearance to unventilated soffit
F. Clearance to outside corner
12” (30.5 cm) or in accordance with local installation
codes and the requirements of the gas supplier.
12” (30.5 cm) or in accordance with local installation
codes and the requirements of the gas supplier.
12” (30.5 cm) or in accordance with local installation
codes and the requirements of the gas supplier.
12” (30.5 cm) or in accordance with local installation
codes and the requirements of the gas supplier.
12” (30.5 cm) or in accordance with local installation
codes and the requirements of the gas supplier.
12” (30.5 cm) or in accordance with local installation
codes and the requirements of the gas supplier.
G. Clearance to inside corner3 feet (91.4 cm)3 feet (91.4 cm)
H. Clearance to each side of center line
extended above meter/regulator assembly
Above a meter/regulator assembly within 3 feet
(91.4 cm) horizontally of the vertical center-line of the
regulator vent outlet to a maximum vertical distance of
15 feet (4.5 m) above the meter/regulator assembly.
I. Clearance to service regulator vent outlet3 feet (91.4 cm)
J. Clearance to non-mechanical air supply inlet to
building or the combustion air inlet to any other
appliance
12” (30.5 cm) for models 100,000 BTUH (30 kW),
36” (91 cm) for models >100,000 BTUH (30 kW).
K. Clearance to a mechanical supply inlet6 feet (1.83 m)
L. Clearance above paved sidewalk or paved
driveway located on public property
7 feet (2.13 m)†
M. Clearance under veranda, porch, deck, or balcony 12” (30.5 cm)‡
Above a meter/regulator assembly within 3 feet
(91 cm) horizontally of the vertical center-line of the
regulator vent outlet to a maximum vertical distance of
15 feet (4.5 m) above the meter/regulator assembly.
3 feet (91.4 cm) or in accordance with local installatio n
codes and the requirements of the gas supplier.
3 feet (91.4 cm) above if within 10 feet (3 m)
horizontally.
7 feet (2.13 m) or in accordance with local installation
codes and the requirements of the gas supplier.
12” (30.5 cm) or in accordance with local installation
codes and the requirements of the gas supplier
.
1. In accordance with the current CSA B149.1-00, Natural Gas and Propane Installation Code.
2. In accordance with the current ANSI Z223.1 / NFPA 54, National Gas Code.
3. In accordance with the current ANSI Z21.47 * CSA 2.3 American National Standard.
†A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
†† 12” (30.5 cm) up from the bottom edge of the structure for Two-pipe (direct vent) applications per ANSI Z223.1 / NFPA 54, Nat ional Gas Code.
‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides benea th the floor and the distance between th e top of the vent termina-
tion and the underside of the veranda, porch, or deck is greater than 12” (30.5 cm) as specified in CSA B149.1-00.
A vent shall not terminate less than 12” (30.5 cm) above a grade level.
Any fresh air or make up inlet for dryer or furnace area is considered to be forced air inlet.
Avoid areas where condensate drippage may cause problems such as above planters, patios, or adjacent to windows where steam may cause fogging.
A terminus of a vent shall be fitted with a cap in accordance with the vent manufacturer’s installation instructions, or in accordance with the installation instructions for a
special venting system.
Responsibility for the provision of proper adequate venting and air supply for application shall rest with the installer.
Vent shall extend high enough above build ing, or a neighboring obstruction, so that wind from any direction will not create a positive pressure in the vicinity of the vent.
Consideration must be given for degradation of building materials by flue gases. Sidewall termination may require sealing or shielding of building
surfaces with a corrosion resistant material to protect against combustion product corrosion. Consideration must be given to wind direction in
order to prevent flue products and/or condensate from being blown against the building surfaces. If a metal shield is used it must be a stainless
steel material at a minimum dimension of 20 inches (51 cm). It is recommended that a retaining type collar be used that is attached to the building surface to prevent movement of the vent pipe.
12” vertical separation
between combustion air
intake and vent.
12” minimum
below overhang
12” minimum
separation between
bottom of
combustion air pipe
and bottom of vent.
Maintain 12”
minimum clearance
above highest
anticipated snow
level or grade,
whichever is higher.
12” MIN.
12” MIN.
OVERHANG
12” Minimum
below overhang
12” Minimum
separation between
bottom of
combustion air
intake and
bottom of vent
Maintain 12”
minimumclearance
above highest
anticipated snow
level or grade,
whichever is higher
VENT
2”
MIN.
COMBUSTION AIR
MIN.
6”
VENT SYSTEM
This furnace is certified to be installed with one of two possible vent
configurations.
1.Horizontal vent system. This vent system can be installed completely horizontal or combinations of horizontal, vertical, or offset
using elbows.
2.Vertical vent system. This vent system can be installed completely
vertical or a combination of horizontal, vertical, or offset using
elbows.
VENT APPLICATIONS AND TERMINATION
When selecting the location for a combustion air / vent termination, the
following should be considered:
1.Observe all clearances listed in vent clearances in these instructions.
2.Termination should be positioned where vent vapors will not damage plants or shrubs or air conditioning equipment.
3.Termination should be located where it will not be affected by wind
gusts, light snow, airborne leaves or allow recirculation of flue
gases.
4.Termination should be located where it will not be damaged or
exposed to flying stones, balls, etc.
5.Termination should be positioned where vent vapors are not objectionable.
6.Horizontal portions of the vent system must slope upwards and be
supported to prevent sagging.
7.Direct vent systems must be installed so the vent and the combustion air pipes terminate in the same atmospheric zone. Refer to
Figures 26 or 27.
VENTING MULTIPLE UNITS
Multiple units can be installed in a space or structure as a two-pipe configuration.
The combustion air side of the two-pipe configuration shown in Figure
27 can be installed so the combustion air pipe terminates as described
in outdoor combustion air or ventilated combustion air sections in these
instructions. Follow the instructions for outdoor combustion air or ventilated combustion air and the instructions for installing the vent system
with the vent terminating as shown in Figures 28 or 29. The two-pipe
system must have a separate combustion air pipe and a separate vent
pipe for each furnace. Under NO circumstances can the two combustion air or vent pipes be tied together. The combustion air and vent
pipes must terminate in the same atmospheric zone.
FIGURE 28: Double Horizontal Combustion Air Intake and Vent
FIGURE 29: Double Vertical Combustion Air Intake and Vent
Termination
COMBUSTION AIR SUPPLY
All installations must comply with Section 5.3, Air for Combustion and
Ventilation of the National Fuel Gas Code, ANSI Z223.1 or Sections
7.2, 7.3 or 7.4 of CAN/CGA B149.1 or .2 Installation Code - latest editions.
This furnace is certified to be installed with one only possible combustion air intake configurations.
1.OUTDOOR COMBUSTION AIR:
where the combustion air is supplied through a PVC or ABS pipe
that is connected to the PVC coupling attached to the furnace and
is terminated in the same atmospheric zone as the vent. This type
of installation is approved on all models. Refer to Figure 20.
This is a direct vent configuration
Page 21
420705-UIM-C-0310
NOTICE
Connects to
collar on top
of burner box
Vent pipe cements
into socket just
above top panel
Or vent pipe may be
clamped into outlet
of drain coupling
Outdoor Combustion Air
Combustion Air Intake/Vent Connections
This installation requires combustion air to be brought in from outdoors.
This requires a properly sized pipe (Shown in Figure 30) that will bring
air in from the outdoors to the furnace combustion air intake collar on
the burner box. The second pipe (Shown in Figure 30) is the furnace
vent pipe.
FIGURE 30: Direct Vent Air Intake Connection and Vent Connection
The combustion air intake pipe should be located either through the
wall (horizontal or side vent) or through the roof (vertical vent). Care
should be taken to locate side vented systems where trees or shrubs
will not block or restrict supply air from entering the terminal.
Also, the terminal assembly should be located as far as possible from a
swimming pool or a location where swimming pool chemicals might be
stored. Be sure the terminal assembly follows the outdoor clearances
listed in Section #1 “Outdoor Air Contaminants.”
An unconfined space is not less than 50 cu.ft (1.42 m
hr (0.2928 kW) input rating for all of the appliances installed in that
area.
Rooms communicating directly with the space containing the appliances are considered part of the unconfined space, if openings are furnished with doors.
A confined space is an area with less than 50 cu.ft (1.42 m
Btu/hr (0.2928 kW) input rating for all of the appliances installed in that
area. The following must be considered to obtain proper air for combustion and ventilation in confined spaces.
An optional plastic birdscreen is shipped in the loose parts bag with
every furnace. This may be installed in the intake collar to prevent
any small objects from entering the furnace.
This type of installation requires that the supply air to the appliance(s) be of a sufficient amount to support all of the appliance (s)
in the area. Operation of a mechanical exhaust, such as an exhaust
fan, kitchen ventilation system, clothes dryer or fireplace may create conditions requiring special attention to avoid unsatisfactory
operation of gas appliances. A venting problem or a lack of supply
air will result in a hazardous condition, which can cause the appliance to soot and generate dangerous levels of CARBON MONOXIDE, which can lead to serious injury, property damage and / or
death.
3
) per 1,000 Btu/
3
) per 1,000
Combustion Air Source From Outdoors
The blocking effects of louvers, grilles and screens must be given consideration in calculating free area. If the free area of a specific louver or
grille is not known, refer to Table 11, to estimate free area.
Table 11: Estimated Free Area
Wood or Metal
Louvers or Grilles
Screens+
* Do not use less than 1/4”(0.635 cm) mesh
+ Free area of louvers and grille varies widely; the installer should follow
louver or grille manufacturer’s instructions.
Wood 20-25%*
Metal 60-70% *
1/4” (0.635 cm)
mesh or larger 100%
Dampers, Louvers and Grilles (Canada Only)
1.The free area of a supply air opening shall be calculated by sub-
tracting the blockage area of all fixed louvers grilles or screens
from the gross area of the opening.
2.Apertures in a fixed louver, a grille, or screen shall have no dimen-
sion smaller than 0.25” (0.64 cm).
3.A manually operated damper or manually adjustable louvers are
not permitted for use.
4.A automatically operated damper or automatically adjustable lou-
vers shall be interlocked so that the main burner cannot operate
unless either the damper or the louver is in the fully open position.
When a Category I furnace is removed or replaced, the original
venting system may no longer be correctly sized to properly vent
the attached appliances.
An improperly sized vent system can cause CARBON MONOXIDE
to spill into the living space causing personal injury, and or death.
Table 12: Unconfined Space Minimum Area in Square Inch
BTUH Input Rating
60,000
80,000
100,000
120,000
Table 13: Free Area
Minimum Free Area Required for Each Opening
BTUH Input
Rating
60,000
80,000
100,000
120,000
Horizontal Duct
(2,000 BTUH)
30 in
40 in
50 in
60 in
EXAMPLE: Determining Free Area.
Appliance 1 Appliance 2 Total Input
100,000 + 30,000 = (130,000 4,000) = 32.5 Sq. In. Vertical
Appliance 1 Appliance 2 Total Input
100,000 + 30,000 = (130,000 2,000) = 65 Sq. In. Horizontal
Minimum Free Area in Square Feet
Required for Each Opening
2
60 in
(387 cm2)
2
80 in
(516 cm2)
2
100 in
(645 cm2)
2
120 in
(742 cm2)
Vertical Duct or
Opening to Outside
(4,000 BTUH)
2
(193 cm2)15 in2 (97 cm2)
2
(258 cm2)20 in2 (129 cm2)
2
(322 cm2)25 in2 (161 cm2)
2
(387 cm2)30 in2 (193 cm2)
Round Duct
(4,000 BTUH)
5” (13 cm)
5” (13 cm)
6” (15 cm)
7” (18 cm)
Johnson Controls Unitary Products21
Page 22
420705-UIM-C-0310
Gable
Vent
Gas
Vent
Soffit
Vent
Ventilated
Attic
Top Above
Insulation
Optional
Inlet (a)
Outlet
Air (a)
Ventilated
Crawl Space
Gas
Water
Heater
Furnace
Soffit
Vent
Gas
Water
Heater
Inlet
Air (a)
Inlet
Air (b)
Furnace
Gas
Vent
Outlet
Air (a)
Outlet
Air (b)
Inlet
Air (a)
Inlet
Air (b)
Gas
Water
Heater
Furnace
Ventilated
Attic
Top Above
Insulation
Gable
Vent
Gas
Vent
FIGURE 31: Outside and Ambient Combustion Air
Air Supply Openings and Ducts
1.An opening may be used in lieu of a duct to provide to provide the
outside air supply to an appliance unless otherwise permitted by
the authority having jurisdiction. The opening shall be located
within 12” (30.5 cm) horizontally from, the burner level of the appliance. Refer to “AIR SOURCE FROM OUTDOORS AND VENT
AND SUPPLY AIR SAFETY CHECK” in these instructions for
additional information and safety check procedure.
2.The duct shall be either metal, or a material meeting the class 1
requirements of CAN4-S110 Standard for Air Ducts.
3.The duct shall be least the same cross-sectional area as the free
area of the air supply inlet opening to which it connects.
4.The duct shall terminate within 12 in (30.5 cm) above, and within
24 in (61 cm) horizontally from, the burner level of the appliance
having the largest input.
5.A square or rectangular shaped duct shall only be used when the
2
required free area of the supply opening is 9 in
(58.06 cm2) or
larger. When a square or rectangular duct is used, its small dimension shall not be less than 3 in (7.6 cm).
6.An air inlet supply from outdoors shall be equipped with a means
to prevent the direct entry of rain and wind. Such means shall not
reduce the required free area of the air supply opening.
7.An air supply inlet opening from the outdoors shall be located not
less than 12” (30.5 cm) above the outside grade level.
Combustion Air Source from Outdoors
1.Two permanent openings, one within 12 in (30.5 mm) of the top
and one within 12 in (30.5 mm) of bottom of the confined space,
Two permanent openings, shall communicate directly or by means
of ducts with the outdoors, crawl spaces or attic spaces.
2.One permanent openings, commencing within 12 in (30.5 mm) of
the top of the enclosure shall be permitted where the equipment
has clearances of at least 1 in (2.54 cm) from the sides and back
and 6 in (15.24 cm) from the front of the appliance. The opening
shall communicate directly with the outdoors and shall have a minimum free area of:
a.1 square in per 3000 Btu per hour (6.45 cm3 per 0.879 kW) of
the total input rating of all equipment located in the enclosure.
b.Not less than the sum of all vent connectors in the confined
space.
3.The duct shall be least the same cross-sectional area as the free
area of the air supply inlet opening to which it connects.
4.The blocking effects of louvers, grilles and screens must be given
consideration in calculating free area. If the free area of a specific
louver or grille is not known. Refer to Table 11.
Ventilated Combustion Air
(Modular Home Installations Only)
The ventilated attic space or a crawl space from which the combustion
air is taken must comply with the requirements specified in “COMBUSTION AIR SOURCE FROM OUTDOORS” in this instruction or in Section 5.3, Air for Combustion and Ventilation of the National Fuel Gas
Code, ANSI Z223.1 (latest edition). This type installation requires two
properly sized pipes. One brings combustion air from a properly ventilated attic space or crawl space and a second pipe that extends from
the furnace vent connection (top right of unit) to the exterior of the building. Refer to Table 7 for intake pipe sizing, allowable length and elbow
usage. Follow all notes, procedures and required materials in the
SEALED COMBUSTION AIR SUPPLY section in these instructions
when installing the combustion air pipe from the unit and into a ventilated attic space or crawl space. DO NOT terminate vent pipe in an Attic
or Crawl Space.
Ventilated Combustion Air Te rmination
(Modular Home Installations Only
Refer to Figure 32 for required attic termination for the combustion air
intake pipe. For attic termination, use two 90 elbows with the open end
in a downward position. Be sure to maintain 12” (30.5 cm) clearance
above any insulation, flooring or other material.
A crawl space combustion air installation consists of a straight pipe from
the PVC coupling on the burner box that extends into the crawl space
and terminates with a 1/4” (0.63 cm) mesh screen and no elbows.
22Johnson Controls Unitary Products
Page 23
420705-UIM-C-0310
12” Min.
12” minimum
between bottom
of air intake and
any material below.
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbonmonxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances
connected to the venting system are not in operation:
1. Inspect the venting system for proper size and horizontal pitch. Determine that there is no blockage, restriction, leakage, corrosion or other
deficiencies, which could cause an unsafe condition
2. Close all building doors and windows and all doors.
3. Turn on clothes dryers and TURN ON any exhaust fans, such as range hoods and bathroom exhausts, so they shall operate at maximum
speed. Open the fireplace dampers. Do not operate a summer exhaust fan.
4. Follow the lighting instructions. Place the appliance being inspected in operation. Adjust thermostat so the appliance shall operate continuously.
5. Test each appliance (such as a water heater) equipped with a draft hood for spillage (down-draft or no draft) at the draft hood relief opening
after 5 minutes of main burner operation. Appliances that do not have draft hoods need to be checked at the vent pipe as close to the
appliance as possible. Use a combustion analyzer to check the CO2 and CO levels of each appliance. Use a draft gauge to check for a
downdraft or inadequate draft condition.
6. After it has been determined that each appliance properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their normal condition.
7. If improper venting is observed during any of the above tests, a problem exists with either the venting system or the appliance does not
have enough combustion air (Supply Air from outside) to complete combustion. This condition must be corrected before the appliance can
function safely.
NOTE: An unsafe condition exists when the CO reading exceeds 40 ppm and the draft reading is not in excess of - 0.1 in. W.C. (-25 kPa) with
all of the appliance(s) operating at the same time.
8. Any corrections to the venting system and / or to the supply (outside) air system must be in accordance with the National Fuel Gas Code
Z223.1 or CAN/CGA B149.1 Natural Gas and Propane Installation Code (latest editions). If the vent system must be resized, follow the
appropriate tables in Appendix G of the above codes or for this appliance.
FIGURE 32: Attic and Crawl Space Combustion Air Termination
Specially Engineered Installations
The above requirements shall be permitted to be waived where special
engineering, approved by the authority having jurisdiction, provides an
adequate supply of air for combustion and ventilation.
Be sure to instruct the owner not to block this intake pipe.
VENT BLOWER ROTATION
For ease of venting, the vent blower may be rotated 90° in either direction. For upflow installations the vent may exit through the top or either
side of the cabinet. For downflow installations, the vent blower must be
rotated so that the vent exits through either side of the cabinet. See Figures 22-23 for details.
SECTION VIII: START-UP AND
ADJUSTMENTS
The initial start-up of the furnace requires the following additional
procedures:
All electrical connections made in the field and in the factory should
be checked for proper tightness.
When the gas supply is initially connected to the furnace, the gas piping
may be full of air. In order to purge this air, it is recommended that the
ground union be loosened until the odor of gas is detected. When gas is
detected, immediately retighten the union and check for leaks. Allow
five minutes for any gas to dissipate before continuing with the start-up
procedure. Be sure proper ventilation is available to dilute and carry
away any vented gas.
GAS PIPING LEAK CHECK
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in serious
injury, death or property damage.
Never test for gas leaks with an open flame. Use a commercially
available soap solution made specifically for the detection of leaks
to check all connections. A fire or explosion may result causing
property damage, personal injury or loss of life.
Burner ignition may not be satisfactory on first startup due to residual air in the gas line or until gas manifold pressure is adjusted. The
ignition control will make three attempts to light before locking out.
It is recommended that when the gas supply is first connected to the
furnace, the ground union be loosened until the odor of gas is detected.
When gas is detected, immediately tighten the union and check for gas
leaks. Allow five minutes for any gas to dissipate before continuing with
the startup procedure. Be sure that proper ventilation is available to
dilute and carry away any vented gas.
With furnace in operation, check all of the pipe joints, gas valve connections and manual valve connections for leakage using an approved gas
detector, a non-corrosive leak detection fluid or other leak detection
methods. Take appropriate action to stop any leak. If a leak persists,
replace the faulty component.
The furnace and its equipment shutoff valve must be disconnected from
the gas supply during any pressure testing of that system at test pressures in excess of 1/2 PSI (3.45 kPa).
The furnace must be isolated from the gas supply piping system by
closing the equipment shutoff valve during any pressure testing of the
gas supply system.
Johnson Controls Unitary Products23
Page 24
420705-UIM-C-0310
NOTICE
NOTICE
HOT SURFACE IGNITION SYSTEM
Do not attempt to light this furnace by hand (with a match or
any other means). There may be a potential shock hazard from
the components of the hot surface ignition syst em. The furnace can only be lit automatically by its hot surface ignition
system.
CALCULATING THE FURNACE INPUT
(NATURAL GAS)
Burner orifices are sized to provide proper input rate using natural gas
with a heating value of 1030 BTU/Ft
of your gas is significantly different, it may be necessary to replace the
orifices.
DO NOT set manifold pressure less than 3.2” w.c. or more than 3.8”
w.c. for natural gas at sea level. If manifold pressure is outside this
range, change main burner orifices.
If orifice hole appears damaged or it is suspected to have been
redrilled, check orifice hole with a numbered drill bit of correct size.
Never redrill an orifice. A burr-free and squarely aligned orifice hole
is essential for proper flame characteristics.
3
(38.4 MJ/m3). If the heating value
DO NOT bottom out gas valve regulator adjusting screw. This can
result in unregulated manifold pressure and result in excess overfire and heat exchanger failures.
Verify natural gas input rate by clocking meter.
1.Turn off all other gas appliances and pilots.
2.Run furnace for a minimum of 3 minutes in heating operation.
3.Measure time (in sec) for gas meter to complete 1 revolution and
note reading. The 2 cubic feet dial provides a more accurate measurement of gas flow.
4.Refer to Table 14 for cubic feet of gas per hour.
5.Multiply cubic feet per hour by heating valve (BTU/cu ft) to obtain
input.
If clocked rate does not match the input rate from the unit nameplate.
follow steps in next section to adjust the manifold pressure. Repeat
steps 2 - 5 until correct input is achieved.
Be sure to relight any gas appliances that were turned off at the
start of this input check.
Inlet and manifold gas pressure may be measured by connecting the
“U” tube manometer to the gas valve with a piece of tubing. Follow the
appropriate section in the instructions below. Refer to Figure 33 for a
drawing of the locations of the pressure ports on the gas valve.
T urn gas off at the ball valve or gas cock on gas supply line
before the gas valve. Find the pressure ports on the gas
valve marked Out P and In P.
1.The manifold pressure must be taken at the port marked OUT P.
2.The gas line pressure must be taken at the port marked IN P.
3.Using a 3/32” (2.4 mm) Allen wrench, loosen the set screw by turning it 1 turn counter clockwise. DO NOT REMOVE THE SET
SCREW FROM THE PRESSURE PORT.
Read the inlet gas pressure
Connect the positive side of the manometer to the IN P Tap on the gas
valve. Do not connect any tubing to the negative side of the manometer,
as it will reference atmospheric pressure. Refer to Figure 34 for connection details.
1.Turn gas and electrical supplies on and follow the operating
instructions to place the unit back in operation.
Table 15: Inlet Gas Pressure Range
INLET GAS PRESSURE RANGE
Natural GasPropane (LP)
Minimum4.5” W.C. (1.12 kPa)8.0” W.C. (1.99 kPa)
Maximum10.5” W.C. (2.61 kPa)13.0” (3.24 kPa) W.C.
The inlet gas pressure operating range table specifies what the
minimum and maximum gas line pressures must be for the furnace
to operate safely. The gas line pressure MUST BE
a minimum of:
• 7” W.C. (1.74 kPA) for Natural Gas
• 11” W.C. (2.74 kPA) for Propane (LP) Gas
in order to obtain the BTU input specified on the rating plate and/or
the nominal manifold pressure specified in these instructions and
on the rating plate.
2.Once the correct gas inlet pressure has been established, see
Table 15, turn the gas valve to OFF and turn the electrical supply
switch to OFF; then remove the flexible tubing from the gas valve
pressure tap and tighten the pressure tap plug using the 3/32” (2.4
mm) allen wrench.
3.Turn the electrical and gas supplies back on, and with the burners
in operation, check for gas leakage around the gas valve pressure
port for leakage using an approved non-corrosive gas leak detection fluid, or other non-flammable leak detection methods.
Read the manifold gas pressure
Connect the positive side of the manometer to the adapter previously
installed in the OUT P Tap on the gas valve. Do not connect any tubing
to the negative side of the manometer, as it will reference atmospheric
pressure. Refer to Figure 34 for connection details.
1.Refer to Figure 33 for location of pressure regulator adjustment
cap and adjustment screws on main gas valve.
2.Turn gas and electrical supplies on and follow the operating
instructions to place the unit back in operation.
3.Adjust manifold pressure by adjusting gas valve regulator screw
for the appropriate gas per the following:
Table 16: Nominal Manifold Pressure
NOMINAL MANIFOLD PRESSURE
Natural Gas3.5" w.c. (0.87 kPa)
Propane (LP) Gas10.0" w.c. (2.488 kPa)
FIGURE 33: Gas Valve
If gas valve regulator is turned in (clockwise), manifold pressure is
increased. If screw is turned out (counterclockwise), manifold pressure will decrease.
4.After the manifold pressure has been adjusted, re-calculate the
furnace input to make sure you have not exceeded the specified
input on the rating plate. Refer to “CALCULATING THE FURNACE
INPUT (NATURAL GAS)”.
5.Once the correct BTU (kW) input has been established, turn the
gas valve to OFF and turn the electrical supply switch to OFF; then
remove the flexible tubing from the gas valve pressure tap and
tighten the pressure tap plug using the 3/32” (2.4 mm) Allen
wrench.
6.Turn the electrical and gas supplies back on, and with the burners
in operation, check for gas leakage around the gas valve pressure
port for leakage using an approved non-corrosive gas leak detection fluid, or other non-flammable leak detection methods.
MANIFOLD PRESSURE “U” TUBE CONNECTION
The cap for the pressure regulator must be removed entirely to gain
access to the adjustment screw. Loosening or tightening the cap
does not adjust the flow of gas.
The regulated outlet pressure has been calibrated at the factory.
Additional pressure adjustment should not be necessary. If adjustment is necessary, set to the following specifications. After adjustment, check for gas leakage.
26Johnson Controls Unitary Products
FIGURE 34: Reading Gas Pressure
Page 27
420705-UIM-C-0310
PARK
PARK
HI COOL
HEAT
EAC-H
L1
XFMR
NEUTRALS
HUM
TWIN
60
90
120
180
BLOWER
OFF
DELAY
Y/Y2
W
R
G
C
Blower Off Delay Timer
Adjustment Jumper
(in seconds)
ADJUSTMENT OF TEMPERATURE RISE
The temperature rise, or temperature difference between the return
air and the supply (heated) air from the furnace, must be within the
range shown on the furnace rating plate and within the application
limitations shown in Table 6.
The supply air temperature cannot exceed the “Maximum SupplyAir Temperature” specified in these instructions and on the furnace rating plate. Under NO circumstances can the furnace be
allowed to operate above the Maximum Supply Air Temperature.
Operating the furnace above the Maximum Supply Air Temperature
will cause premature heat exchanger failure, high levels of Carbon
Monoxide, a fire hazard, personal injury, property damage, and/or
death.
After about 5 minutes of operation, determine the furnace temperature
rise. Take readings of both the return air and the heated air in the ducts,
about six feet (1.83 m) from the furnace where they will not be affected
by radiant heat. Increase the blower speed to decrease the temperature
rise; decrease the blower speed to increase the rise.
All direct-drive blowers have multi-speed motors. The blower motor
speed taps are located on the furnace control board in the blower compartment. Refer to Figure 35, and the unit-wiring label to change the
blower speed. To use the same speed tap for heating and cooling, the
heat terminal and cool terminal must be connected using a jumper wire
and connected to the desired motor lead. Place all unused motor leads
on Park terminals. Two park terminals are provided.
Do not energize more than one motor speed at a time or damage to
the motor will result.
ADJUSTMENT OF FAN CONTROL SETTINGS
This furnace is equipped with a time-on/time-off heating fan control. The
fan on delay is fixed at 30 seconds. The fan off delay has 4 settings (60,
90, 120 and 180 seconds). The fan off delay is factory set to 120 seconds. The fan-off setting must be long enough to adequately cool the
furnace, but not so long that cold air is blown into the heated space. The
fan-off timing may be adjusted by positioning the jumper on two of the
four pins as shown in Figure 35.
FIGURE 35: Furnace Control Board
Johnson Controls Unitary Products27
Page 28
420705-UIM-C-0310
Blower Performance CFM - Any Position (Without Filter)
Bottom Airflow Data (SCFM)
Models
Input/Airflow/Cabinet
60/1200/B
80/1200/B
80/1600/C
1001600/C
100/2000/C
120/2000/D
Models
Input/Airflow/Cabinet
60/1200/B
80/1200/B
80/1600/C
1001600/C
100/2000/C
120/2000/D
NOTES:
1.Airflow expressed in standard cubic feet per minute (CFM).
2.Return air is through side opposite motor (left side).
3.Motor voltage at 115 V.
Speed
0.10.20.30.40.50.60.70.80.91.0
High 1492 1442 1378 1325 1243 1176 1075 966 849 655
Medium High 1236 1201 1161 1139 1082 1011 919 830 715 590
Medium Low 986 950 961 916 872 831 757 703 600 510
Low 824 795 783 744 713 659 624 554 489 389
High 1597 1537 1484 1435 1370 1286 1230 1155 1075 925
Medium High 1338 1307 1273 1223 1179 1123 1065 998 928 812
Medium Low 1113 1094 1077 1043 1008 972 924 868 803 798
Low 937 916 900 877 854 817 775 718 639 560
High 1919 1865 1802 1738 1671 1600 1517 1414 1322 1201
Medium High 1532 1533 1513 1499 1465 1416 1352 1283 1198 1084
Medium Low 1232 1313 1291 1280 1250 1209 1207 1148 1055 937
Low 826 821 853 858 838 817 794 776 760 711
High 1909 1880 1823 1776 1706 1637 1562 1474 1375 1252
Medium High 1465 1463 1469 1485 1477 1416 1386 1324 1250 1114
High 2343 2253 2167 2071 1979 1881 1785 1668 1473 1351
Medium High 1954 1892 1846 1781 1714 1637 1548 1429 1238 1171
Medium Low 1596 1539 1511 1458 1399 1341 1254 1180 942 988
Low 1299 1261 1229 1177 1111 1053 993 937 882 782
Ext. Static Pressure (in. H2O)
Ext. Static Pressure (in. H2O)
28Johnson Controls Unitary Products
Page 29
420705-UIM-C-0310
SECTION IX: SAFETY CONTROLS
CONTROL CIRCUIT FUSE
A 3-amp fuse is provided on the control circuit board to protect the 24volt transformer from overload caused by control circuit wiring errors.
This is an ATO 3, automotive type fuse and is located on the control
board.
BLOWER DOOR SAFETY SWITCH
Main power to the unit must still be interrupted at the main power
disconnect switch before any service or repair work is to be done to
the unit. Do not rely upon the interlock switch as a main power disconnect.
Blower and burner must never be operated without the blower
panel in place.
This unit is equipped with an electrical interlock switch mounted in the
burner compartment. This switch interrupts all power at the unit when
the panel covering the blower compartment is removed.
Electrical supply to this unit is dependent upon the panel that covers the
blower compartment being in place and properly positioned.
ROLLOUT SWITCH CONTROLS
These controls are mounted on the burner assembly. If the temperature
in the area surrounding burner exceeds its set point, the gas valve is
de-energized. The operation of this control indicates a malfunction in
the combustion air blower, heat exchanger or a blocked vent pipe connection. Corrective action is required. These are manual reset controls
that must be reset before operation can continue.
PRESSURE SWITCHES
This furnace is supplied with two pressure switches, which monitor the
flow through the combustion air/vent piping and condensate drain system. These switches de-energize the gas valve if any of the following
conditions are present. Refer to "CONDENSATE PIPING AND FURNACE VENTING CONFIGURATION" for tubing connections.
1.Blockage of vent piping or terminal.
2.Failure of combustion air blower motor.
3.Blockage of combustion air piping or terminals.
4.Blockage of condensate drain piping.
LIMIT CONTROLS
There is a high temperature limit control located on the furnace vestibule panel near the gas valve. This is an automatic reset control that
provides over temperature protection due to reduced airflow. This may
be caused by:
1.A dirty filter.
2.If the indoor fan motor should fail.
3.Too many supply or return registers closed or blocked off.
The control module will lockout if the limit trips 5 consecutive times. If
this occurs, control will reset & try ignition again after 1 hour.
SECTION X: NORMAL OPERATION AND
DIAGNOSTICS
NORMAL OPERATION SEQUENCE
The following describes the sequence of operation of the furnace. Refer
to Owners Manual for component location.
Continuous Blower
Cooling/heating thermostats have a fan switch that has an ON and
AUTO position. In the ON position the thermostat circuit is completed
between terminals R and G. The motor will operate continuously on the
speed tap wire that is connected to the “HI COOL” cooling terminal on
the control board. To obtain a constant air circulation at lower flow rate,
change the high-speed wire to another low speed wire.
Intermittent Blower - Cooling
Cooling/heating thermostats have a fan switch that has an ON and
AUTO position. In the AUTO position the thermostat circuit is completed
between terminals R and G when there is a call for cooling. The motor
will operate on the speed tap wire that is connected to the “HI COOL”
cooling terminal on the control board. The fan off setting is fixed at 60
seconds to improve cooling efficiency.
Heating Cycle
When the thermostat switch is set on HEAT and the fan is set on AUTO,
and there is a call for heat, a circuit is completed between terminals R
and W of the thermostat. When the proper amount of combustion air is
being provided, the pressure switch will close, the ignition control provides a 17-second ignitor warm-up period, the gas valve then opens,
the gas starts to flow, ignition occurs and the flame sensor begins its
sensing function. The blower motor will energize 30 seconds after the
gas valve opens, if a flame is detected. Normal furnace operation will
continue until the thermostat circuit between R and W is opened, which
causes the ignition system and gas valve to de-energize and the burner
flames to be extinguished. The vent motor will operate for 15 seconds
and the blower motor will operate for the amount of time set by the fanoff delay jumper located on the control board. See Table ?. The heating
cycle is now complete, and ready for the start of the next heating cycle.
If the flame is not detected within 7 seconds of the gas valve opening,
the gas valve is shut off and a retry operation begins. Also, if the flame
is lost for 2 seconds during the 10-second stabilization period, the gas
valve is shut off and a retry operation begins. During a retry operation,
the vent motor starts a 15 second inter-purge and the ignitor warm-up
time is extended to 27 seconds. If the flame is established for more than
10 seconds after ignition during a retry, the control will clear the ignition
attempt (retry) counter. If three retries occur during a call for heat, the
furnace will shut down for one hour. If at the end of the one hour shut
down there is a call for heat, the furnace will initiate a normal start cycle.
If the problem has not been corrected the furnace will again lockout
after three retries.
A momentary loss of gas supply, flame blowout, or a faulty flame probe
circuit will result in a disruption in the flame and be sensed within 1.0
seconds. The gas valve will de-energize and the control will begin a
recycle operation. A normal ignition sequence will begin after a 15 second inter-purge. If during the five recycles the gas supply does not
return, or the fault condition is not corrected the ignition control will lockout for 60 minutes.
During burner operation, a momentary loss of power for 50 milliseconds
or longer will de-energize the gas valve. When the power is restored,
the gas valve will remain de-energized and the ignition sequence will
immediately restart.
IGNITION SYSTEM SEQUENCE
1.Turn the gas supply ON at external valve and main gas valve.
2.Set the thermostat above room temperature to call for heat.
3.System start-up will occur as follows:
a.The induced draft blower motor will start and come up to
speed. Shortly after inducer start-up, the hot surface igniter
will glow for about 17 seconds.
b.After this warm up, the ignition module will energize (open)
the main gas valve.
c.After flame is established, the supply air blower will start in
about 30 seconds.
TROUBLESHOOTING
The following visual checks should be made before troubleshooting:
1.Check to see that the power to the furnace and the ignition control
module is ON.
2.The manual shut-off valves in the gas line to the furnace must be
open.
3.Make sure all wiring connections are secure.
4.Review the sequence of operation. Start the system by setting the
thermostat above the room temperature. Observe the system’s
response. Then use the troubleshooting section in this manual to
check the system’s operation.
Johnson Controls Unitary Products29
Page 30
420705-UIM-C-0310
NOTICE
Never bypass any safety control to allow furnace operation. To
do so will allow furnace to operate under potentially hazardous
conditions.
Do not try to repair controls. Replace defective controls with
UPG Source 1 Parts.
Never adjust pressure switch to allow furnace operation.
FURNACE CONTROL DIAGNOSTICS
The furnace has built-in, self-diagnostic capability. If a system problem
occurs, a blinking LED can flash red, green or amber to indicate various
conditions.
The control continuously monitors its own operation and the operation
of the system. If a failure occurs, the LED will indicate the failure code. If
the failure is internal to the control, the light will stay on continuously. In
this case, the entire control should be replaced, as the control is not
field repairable.
Flash sequence codes 1 through 11 are as follows: LED will turn “on”
for 1/4 second and “off” for 1/4 second. This pattern will be repeated the
number of times equal to the code. For example, six “on” flashes equals
a number 6 fault code. All flash code sequences are broken by a 2 second “off” period.
SLOW GREEN FLASH: Normal operation.
SLOW AMBER FLASH: Normal operation with call for heat.
RAPID RED FLASH: Twinning error, incorrect 24V phasing. Check
twinning wiring.
RAPID AMBER FLASH: Flame sense current is below 1.5 microamps.
Check and clean flame sensor. Check for proper gas flow. Verify that
current is greater than 1.5 microamps at flame current test pad.
4AMBER FLASHES: The control is receiving a “Y” signal from the
thermostat without a “G” signal, indicating improper thermostat wiring.
1 RED FLASH: This indicates that flame was sensed when there was
not a call for heat. The control will turn on both the inducer motor and
supply air blower. A gas valve that leaks or is slow closing would typically cause this fault.
2 RED FLASHES: This indicates that the normally open pressure
switch contacts are stuck in the closed position. The control confirms
these contacts are open at the beginning of each heat cycle. This would
indicate a faulty pressure switch or miswiring.
3 RED FLASHES: This indicates the normally open pressure switch
contact did not close after the inducer was energized. This could be
caused by a number of problems: faulty inducer, blocked vent pipe, broken pressure switch hose or faulty pressure switch.
4 RED FLASHES: This indicates that the main limit switch has opened
its normally closed contacts. The control will operate the supply air
blower and inducer. This condition may be caused by: dirty filter,
improperly sized duct system, incorrect blower speed setting, incorrect
firing rate or faulty blower motor. Also, this fault code could be caused
by a blown fuse located on the control board.
5 RED FLASHES: This fault is indicated if the normally closed contacts
in the rollout switch opens. The rollout control is manually reset. If it has
opened, check for proper combustion air, proper inducer operation, and
primary heat exchanger failure or burner problem. Be sure to reset the
switch and cycle power (24 VAC) to the control after correcting the failure condition. Also, this fault code could be caused by a blown fuse
located on the control board.
6 RED FLASHES: This indicates that after the unit was operating, the
pressure switch opened 4 times during the call for heat. If the main
blower is in a “Delay on” mode, it will complete it, and any subsequent
delay off period. The furnace will lock out for one hour and then restart.
7 RED FLASHES: This fault code indicates that the flame could not be
established. This no-light condition occurred 3 times (2 retries) during
the call for heat before locking out. Low gas pressure, faulty gas valve,
dirty or faulty flame sensor, faulty hot surface ignitor or burner problem
may cause this. The furnace will lock out for one hour and then restart.
8 RED FLASHES: This fault is indicated if the flame is lost 5 times (4
recycles) during the heating cycle. This could be caused by low gas
pressure, dirty or faulty flame sensor or faulty gas valve. The furnace
will lock out for one hour and then restart.
9 RED FLASHES: Indicates reversed line voltage polarity or grounding
problem. Both heating and cooling operations will be affected. Check
polarity at furnace and branch. Check furnace grounding. Check that
flame probe is not shorted to chassis.
10 RED FLASHES: Flame sensed with no call for heat. Check gas
valve and gas valve wiring.
11 RED FLA SHES: This indicates that a primary or auxiliary limit switch
has opened its normally-closed contacts and has remained open for
more than five minutes. This condition is usually caused by a failed
blower motor or blower wheel. Cycle power (24 VAC) to the control to
reset the hard lockout condition after correcting the failure condition.
12 RED FLASHES: This code indicates an open igniter circuit, which
could be a disconnected or loose wire or a cracked or broken igniter.
STEADY ON RED: Control failure. Replace control board.
60-MINUTE AUTOMATIC RESET FROM LOCKOUT: This control
includes a “watchdog” type circuit that will reset from a lockout condition
after 60 minutes. Operational faults 6,7,8 will be reset. This provides
protection to an unoccupied structure if a temporary condition exists
causing a furnace malfunction. An example would be a low incoming
gas supply pressure preventing unit operation. When the gas pressure
is restored, at some point the “watchdog” would restart the unit and provide heat for the house.
If a flame is detected the control flashes the LED for 1/8 of a second
and then enters a flame stabilization period.
IGNITION CONTROL FLAME SENSE LEVELS
Normal flame sense current is approximately
3.7 microamps DC (µa)
Low flame signal warning starts at 1.5 microamps.
Low flame signal control lockout point is
0.1 microamps DC (µa)
DIAGNOSTIC FAULT CODE STORAGE AND
RETRIEVAL
The control in this furnace is equipped with memory that will store up to
five error codes to allow a service technician to diagnose problems
more easily. This memory will be retained even if power to the furnace
is lost. This feature should only be used by a qualified service tech-
nician.
If more than five error codes have occurred since the last reset, only the
five most recent will be retained. The furnace control board has a button, labeled "LAST ERROR" that is used to retrieve error codes. This
function will only work if there are no active thermostat signals. So any
call for heating, cooling or continuous fan must be terminated before
attempting to retrieve error codes.
To retrieve the error codes, push the LAST ERROR button. The LED on
the control will then flash the error codes that are in memory, starting
with the most recent. There will be a two-second pause between each
flash code. After the error codes have all been displayed, the LED will
resume the normal slow green flash after a five second pause. To
repeat the series of error codes, push the button again.
If there are no error codes in memory, the LED will flash two green
flashes. To clear the memory, push the LAST ERROR button and hold it
for more than five seconds. The LED will flash three green flashes when
the memory has been cleared, then will resume the normal slow green
flash after a five-second pause.
30Johnson Controls Unitary Products
Page 31
FIGURE 36: Furnace Control Event Schedule
Thermostat Calling for Heat
Thermostat Satisfied
(Seconds)
THERMOSTAT
INDUCER
IGNITOR
MAIN VALVE
HUMIDIFIER
ELECTRONIC
AIR CLEANER
CIRCULATING
BLOWER
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
15
Sec.
Post
Purge
Fan on Delay
30 Seconds
0
2
1722
52
0
60, 90, 120, 180 SEC.
Selectable Fan Off Delay
SECTION XI: REPLACEMENT PARTS LIST
DESCRIPTION
MOTOR
MOTOR, DIRECT DRIVE BLOWER
BLOWER, COMBUSTION
ELECTRICAL
CAPACITOR, RUN
SWITCH, LIMIT
CONTROL, FURNACE
IGNITER
SENSOR, FLAME
SWITCHES, PRESSURE
SWITCH, DOOR
TRANSFORMER
VALVE, GAS
CONTROL, TEMPERATURE