Johnson Controls METASYS TC-9102 Series, METASYS TM-9100 Series, METASYS TM-9150, METASYS TC-9102, METASYS TM-9160 Technical Bulletin

...
System 91 Manual
TC-9102
Technical Bulletin
Issue Date 0698
TC-9102 Fan Coil Unit Controller
Introduction Page 3
Model Types 4
Controller Functions 5
Output Types 10
Fan Output Types 12
Installation 15
Mounting 15
Wiring 16
Jumper and Switch Selections 22
Startup 23
Commissioning 23
Specifications & Technical Data 25
Factory-Set Parameters 26
Parameters for Supervisory System 27
Ordering Codes 28
© 1998 Johnson Controls, Inc.
Order No. MN-9100- 2117
1
2 Technical Bulletin—TC- 9102

Introduction

The TC-9102 series of microprocessor-based controllers is designed for the control of Fan Coil Units (FCUs) with heating and cooling, and a single-speed, 3-speed or var iable- speed fan. T h e contr oll er can regul ate water valves, one or 2-stage electric heating, or a cooling unit wher e the compressor has its own short cycle protection.
The comfort temperature set point of the controller may be adjusted via a TM-9100 Series Room Command Module, and the occupied and unoccupied control modes of operation temporarily changed. A window open sensing contact may be connected to switch the controller to the off mode, and a low temperature limit protection feature is available.
The controller is factory-configured to contr ol with default oper ating parameters so that no external setup devi ces ar e necessar y. However , a software package for a PC is available to ver i f y th e cor r ect oper ati on of the controller and to modify the configuration, if necessary.
Winter and summer compensation may be enabled when th e contr oll er receives outdoor air temperature data via the communications bus, and modes of operation may be set by time scheduling programs or control processes in the supervisory system.
2357 2664
Figure 1: TC-9102 Controller Figure 2: TM-9160 Room
Command Module
Technical Bulletin—TC-9102 3
2333
Figure 3: TM-9180 Room Command Module
Model Types
The TC-9102 Controller is available in several model types according to the type of outputs and the range of the integrated or remote set point input. Refer to Ordering Codes at the end of this bulletin for details.
4 Technical Bulletin—TC- 9102
Controller Functions
The controller can be connected to a Room Command Module, from which it receives the room temper atur e, the remote set point and other override signals. The TM-9180 intelligent Room Command Module provides these signals via a serial bus connection to the controller. The other Room Command Modules (TM-9150/9160/9170) provide the signals as individually connected physical inputs to the controller. In addition, an NTC temperature sensor is available for mounting within the FCU.
For installations without a Room Command Module, the controller is available with an integrated set point adjuster. Alternatively, the remote set point and fan override controls may be incorporated into a custom FCU control panel. Refer to the Specifications and Technical Data section of this bulletin for details of the components required.
Occupancy Sensor
Window Contact
Room Command Module
Room Temp.* Remote Setpoint
Occupancy Button Fan Override
(3-speed only)
Communications Bus (Supervisory Control, Outdoor Air Temp.)
Figure 4: Controller with Room Command Module
Room Temp. NTC Sensor
Controller
Occupancy Sensor
Window Contact
Output Heating
Output Cooling
Fan Control
tc2cwrcm
*
NTC sensor may be mounted in FCU.
Output Heating
Controller (Setpoint)
Fan Override (3-speed only)
tc2cwspa
Communications Bus (Supervisory Control, Outdoor Air Temp.)
Figure 5: Controller with Integrated Setpoint Adjuster
Technical Bulletin—TC-9102 5
Output Cooling
Fan Control
Standalone Mode
The controller operates in standalone mode when it is not connected to a supervisory system via the communications bus nor to a TM-9180 Room Command Module. In standalone mode the controller may operate in one of three control modes:
• COMFORT (occupied): control at comfort set point
• STANDBY (unoccupied): control at a standby level set point
• OFF (not in use): low limit control only
The control modes are set by the window contact and occupancy sensor inputs, and may be modified by the occupancy button on the Room Command Module as shown in Table 1.
Table 1: Standalone Modes
WINDOW CONTACT OCCUPANCY SENSOR CONTROL MODE ALTERNATE MODE
(OCCUPANCY BUTTON)
WINDOW OPEN NO ACTION OFF NO ACTION WINDOW CL OSED OCCUPIED COMFORT STANDBY
UNOCCUPIED STANDBY COM FORT
Supervisory Mode
When connected to a supervisory system via the communications bus or to a TM-9180 Room Command Module, the controller may operate in COMFORT, STANDBY or OFF control modes, and additionally in NIGHT mode:
NIGHT (scheduled unoccupied): control at a night level set point. The control modes are set by the supervisory system or TM-9180, and are
modified by the occupancy sensor input and occupancy button on the Room Command Module as shown in Table 2. The window contact input always switches the controller to OFF control mode, and a MANUAL mode is available from the supervisory system to inhibit the action of the occupancy sensor and occupancy button.
Table 2: Supervisory Modes
WINDOW CONTACT
OPEN ANY MODE NO ACTION OFF NO ACTION
CLOSED UNOCCUPIED STANDBY COMFORT (T)*
SUPERVISORY MODE
OFF OCCUPIED OFF OFF
NIGHT OCCUPIED NIGHT COMFORT (T)*
STANDBY OCCUPIED STANDBY COMFORT
COMFORT OCCUPIED COMFO RT STANDBY
OFF/MANUAL OFF NIGHT/MANUAL NO ACTION NIGHT NO ACTION STANDBY/MANUAL STANDBY COMFORT/MANUAL COMFORT
OCCUPANCY SENSOR
UNOCCUPIED OFF OFF
UNOCCUPIED NIGHT COMFORT (T)*
UNOCCUPIED STANDBY COMFORT
CONTROL MO DE ALTERNATE MODE
(OCCUPANCY BUTTON)
*(T) = Timed (Returns t o Cont r ol Mode af ter 1 hour.)
6 Technical Bulletin—TC- 9102
Controller Set Points
The set point in all control modes may be modified from the integrated set point adjuster or from the remote set point dial/control panel on the Room Command Module, according to the controller model type. The controller models with a remote set point of 12-28°C require that a Room Command Module or an external potentiometer is connected to give the set point. Controllers with a remote set point of +/-3 K have internal factory set points of 20°C for heating and 22°C for cooling.
The set point is decreased or increased in the STANDBY control mode by the factory-set “Standby Bias Heating” and “Standby Bias Cooling” values to reduce the heating or cooling energy required when the room is temporarily unoccupied.
When a supervisory system is connected, the set point can be further decreased or increased in the NI GHT control mode to fur ther r educe energy requirements during scheduled unoccupied periods such as nights, weekends and holidays.
In the controller there are two “comfort” set points (Comfort Set Point Heating and Comfort Set Point Cooling), and the difference between these two values determines th e zer o ener gy band wher e neit her heati ng nor cooling is required. The controller calculates two working set points (WSP Heating and WSP Cooling), which are the sum of the comfort set point values, the “Remote Set Point” value coming from the integrated set point adjuster or the Room Command Module, and the “Common Set Point” value. In the supervisory mode an adjustment may be made to the working set points either by changing the “Comfort Set Points,” or by changing the value in the “Common Set Point” parameter of the controller which enables the supervisory system operator to adjust the setpoints for heating and cooling at the same time without affecting the zero energy band. In summary:
Working Set Point (Heating) = Comfort Set Point (Heating) (Supervisory System)
+ Remote Set Point (integrated adjuster or Command Module dial) + Common Set Point (Supervisory System) + STANDBY or NIGHT Bias Heating (if mode is active)
Working Set Point (Cooling) = Comfort Set Point (Cooling) (Supervisory System)
+ Remote Set Point (integrated adjuster or Command Module dial) + Common Set Point (Supervisory System) + STANDBY or NIGHT Bias Cooling (if mode is active)
When the room temperature is below the working set point for heating, the heating output increases according to the proportional band and integral time parameters set for the heating control loop. When the room temperature is above the working set point for cooling, the cooling output increases according to the proportional band and integral time parameters set for the cooling control loop. Heating and cooling control is illustrated in figures 8 and 9.
Technical Bulletin—TC-9102 7
Alternate Mode
When pressed for about one second, the occupancy button on the Room Command Module changes the mode of operation of the controller to the “Alternate Mode” or back to the nor m al “Cont r ol Mode” as shown i n Table 2. The “COMFORT ( T)” alternate mode is active onl y f or a per iod of one hour, after which the controller r evert s to the normal control mode.
Fan Control
The controllers with on/off fan control switch the fan on when the room temperature is below the working set point for heating and above the working set point for cooling, and switch the fan off when the room temperature has entered th e zer o ener gy band by th e value set f or t he f an differential. The fan can optionally be set to continue running in the zero energy band in the COMFORT (occupied) mode, using the software commissioning tool.
In controllers with 3-speed fan control outputs, the fan stages are switched in sequence as the room temper at ur e decr eases or incr eases, and Speed 1 remains on in the zero energy band.
In controllers with a 0 to 10 VDC output for a fan speed controller, the output increases as the room t emper at ur e f all s below th e wor king set point for heating or rises above the working set point for cooling, and maintains a minimum output (set by default at 50%) when the room temperature has entered the zero ener gy band.
For all controllers, in OFF mode the fan is switched off and the heating and cooling outputs are set to the fully closed or off level. Fan control sequences are shown in figures 10, 11 and 12.
3-Speed Fan Override
The speed of a 3-speed fan may be set manually from the Room Command Module when the controller is in COMFORT (occupied) mode. In the “AUTO” position the speed is set by the controller according to the room temperature. In the manual “OFF- 1- 2- 3” positions the fan runs at the selected speed. T h e f an over r ide i s not acti ve in STANDBY, NIGHT or OFF modes.
In controller models with 2-stage on/off heating and cooling outputs, all outputs are switched off when the fan speed is set to “OFF” to protect electrical heating and cooling devices that require a minimum air flow for normal operation. This feature can be enabled for other types of outputs, if required, using the software commissioning tool. Refer to Commissioning later in this document.
Low Limit Mode
The low limit mode is active when the room temperature falls below the low limit set point. The fan is switched on at full speed and the heating output is set to the maximum level until the room temperature rises by the low limit differential value.
8 Technical Bulletin—TC- 9102
Winter/Summer Compensation
Setpoint
Compensation
(K)
When the controller is connected to a super visor y system , t he wint er and/or summer compensation modes may be enabled. The supervisory system must be programmed to set the outdoor air temperature via the communications bus on a periodic basis. After a power interruption the winter and summer compensation modes are temporarily disabled until a new outdoor air temperature value is received. When the outdoor temperature falls below the winter set point, the working set point of the controller will be raised or lowered in accordance with the winter authority slope. When the outdoor temperature rises above the summer set point the working set point of the controller will be raised in accordance with the summer authority slope. The maximum amount of compensation is limited by the Winter Authority Limit and the Summer Authority Limit.
The effect of the wint er and summer com pensati on on the cont ro ller set point is shown below.
-1
-2
-3
-4
-5
5 4
3
2 1
Winter Authority Slope
(+0,1)
0
-20-30
-10
0
Summer Authority Limit
(+5 K)
10 20
30
Summer Authority
Slope (+0,2)
Outdoor Air
Temperature
40 50
(°C)
Winter Authority
Slope (-0,1)
Winter Authority
Limit (-3 K))
Winter
Setpoint
(10°C)
Summer Setpoint
(24°C)
tc2winsu.drw
Figure 6: Winter/Summer Compensation
Technical Bulletin—TC-9102 9
Auto-dial Feature
When the controller is connected to a remo te N2 Bus and super vised by a Metasys N2 Dialer (NU-NDM101-0) which is linked to a Metasys network by a telephone line, the following alarm conditions in the controller will initiate the automatic dial feature:
• Window Open
• Low Limit mode
• High or low alarm limit violation of the room temperature when alarm
limits have been set by the supervisory system.
When any one of these alarm conditions occurs, the N2 Dialer will detect the alarm and connect the remo te N2 Bus t o th e Metasys net wor k. When the telephone line connection is established the controller alarm status will automatically be reset and the controller is then ready to report further alarm condit ions as t hey occur . R efer to the Technical Bulletin of
the NU-NDM101-0 for further information.
Output Types
0 - 10 VDC
DAT - Duration Adjust Type
The heating and cooling outputs are one of the following types, depending on the controller model code:
The output is an analog voltage between 0 and 10 VDC in direct proportion to the controller output from 0 to 100%.
The DAT output is a triac which is switched on for a duration within the set heating or cooling valve cycle time in direct proportion to the controller output from 0 to 100%. To avoid unnecessary switching of the valve actuator when the output is between 0 and 5% the triac remains off, and when the output is between 95 and 100% the triac remains on. The default cycle time is 300 seconds.
ON OFF
50% O utput
DAT Cycle Time
30% Output
DAT Cycle Time
Figure 7: DAT Output
10 Technical Bulletin—TC-9102
(°C)
g
PAT - Position Adjust Type
The PAT output is a pair of triacs which are switched on to open and close an incrementally driven heating or cooling valve. The duration of switching is directly proportional to the change in the controller output and related to the full stroke time of the valve such that a 100% change will completely open or close the valve. At the 0% or 100% position the duration of switching is increased to ensure that the valve is completely at its end position and the appropriate triac is switched on for the full stroke time every two hours to ensure that the valve remains at its end position. To prevent unnecessary wear on the actuator, the triac output will only be switched when the output change exceeds 1% in the same dir ection as t he previous change or 2% if the direction of change is reversed. T he def ault full stroke time is 60 seconds.
100
Heating
Output (%)
0
5
2-Stage On/Off
Cooling
Comfort
Standby
Night
Comfort
Night
Standby
Low Limit
Room
12 14 16 18 20 22 24 26
10 30
Temperature (°C)
tc2hcvdc
Figure 8: Heating/Cooling Control 0-10 VDC, DAT, PAT
The output is a pair of triacs which are switched on in sequence as the controller output increases. The first stage triac is switched as soon as the output is above 0% and the second stage triac is switched when the output is equal to the set load rating for the first stage which is defaulted to 50%. The switching differential is fixed at 5%. When this type of output is used with 3-speed fan control, the output will be switched off whenever the fan speed is manually overridden to the “OFF” position on the Room Control Module. The control diagram is shown below.
O utput (% )
100
Heating
222 222
Low Limit
0
5
12 14 16 18 20 22 24 26
10
1
1
Night
1
Comfort
Stan dby
C oo lin
111
Comfort
Night
Standby
Room Tem perature
30
Figure 9: Heating/Cooling Control - 2-Stage On/Off
Technical Bulletin—TC-9102 11
Fan Output Types
Fan On/Off
ON
OFF
5
The output is a normally open relay contact which closes when the fan is required to run. Terminals are provided to connect the fan supply voltage to the controller in order to facilitate the wiring to the fan motor. The fan supply voltage is not used within the controller.
Night
Low Limit
Standby
Comfort
Standby
Night
Room
12 14 16 18 20 22 24 26
10 30
Temperature (°C)
Figure 10: On/Off Fan Control - Switch Points
3-Speed Fan Control
3
2
1
5
The output is a set of interlocked r elay contact s, one contact f or each speed which closes when that speed is selected to run. T er mi nal s ar e provided to connect the fan supply voltage to the controller in order to facilitate the wiring to the fan motor. The fan supply voltage is not used within the controller.
Low Lim it
Standby
Night
3
Comfort
22
3
1
Comfort
Night
Standby
Room
10 30
12 14 16 18 20 22 24 26
Temperature (°C)
tc2swpts
12 Technical Bulletin—TC-9102
Figure 11: 3-Speed Fan Control - Switch Points
0 to 10 VDC Control Signal
The output is a control signal for driving a fan speed controller with an opto-isolated 0 to 10 VDC input. As the output voltage increases, the fan speed controller must increase the speed of the fan from the minimum speed of the fan motor to its maximum speed. When the output is below the voltage required for the minimum speed, the fan must be switched off.
100
Output (%)
0
5
Heating
Cooling
Comfort
Standby
Night
Comfort
Low Limit
Night
Standby
Minimum Speed Level
12 14 16 18 20 22 24 26
10 30
Figure 12: 0 to 10 VDC Fan Control Signal
Room Tem perature (°C)
tc2facos
Technical Bulletin—TC-9102 13
14 Technical Bulletin—TC-9102

Installation

The TC-9102 series controller is designed to be mounted within the Fan Coil Unit housing or within a control cabinet. The mounting location must be clean and dry, and not subject to extreme heat or cold. The installation and electrical wiring must conform to local codes and should be carried out by authorized personnel only. Users should ensure that all Johnson Controls' products are used safely and without risk to health or property.
Mounting
4.6 mm/
0.18"
101.6 mm/
3.99"
6 mm/
0.24"
For surface mounting, slide the two mounting brackets into the slots at opposite corners of the controller base behind the terminals. Fix to the surface using the 4-mm di amet er self - t apping scr ews.
For DIN rail mounting, place the controller on the upper edge of the r ail and press the controller firmly against the rail until the spring-loaded clip engages the lower edge of the rail. To remove the controller, insert a screw driver into the clip at the base of the controller and pull the clip downwards to release. Alternatively, lift the controller upwar ds against the spring of the retaining clip and pull forward from the top.
120 mm/4.72"
14 mm/
0.55"
118 mm/
4.64"
(Separable Terminals Only)
14 mm/
108 mm/4.25"
0.55" 31 mm/
3
1.22"
itc02dim
Figure 13: TC-9102 Controller Dimensions
Technical Bulletin—TC-9102 15
Note: A minimum of 25 mm of space is required above and below the
controller for the removal of separable terminals.
16 Technical Bulletin—TC-9102
Wiring
Before connecting or disconnecting any wires, ensure that all power supplies have been switched off and all wires are potential-free to prevent equipment damage and avoid electrical shock.
Terminations are made on the terminal blocks, at the top and bottom of the controller, which accept up to 1. 5mm2 wires. Follow the wiring diagrams shown in figures 14 to 20.
When the TC-9102 model with separable terminal blocks is being wired, it is recommended that the removable parts of the blocks be unplugged before terminating the wires, and that they are not plugged in again until the wiring has been fully checked.
Separate extra low voltage (safe) wiring fr om power line voltage wir i ng. A distinctive colour such as white or pink is recommended for low voltage wiring. Keep all cables as short as possible and tie in position. Do not run cables close to transformers or high frequency generating equipment.
The 24 V supply must be stable and not shared with other switched inductive loads. When multiple loads are connected to one transformer, wire each load from th e tr ansf or m er separ ately so th at any possi ble disturbances from one load will have minimal effect on other loads.
Complete and verify all wiring connections before continuing with the installation procedure.
!
CAUTION: Connections to the on/off or 3-speed fan control
terminals may carry up to 250 VAC. Isolate live and neutral supply lines (double-pole switch) before servicing.
Technical Bulletin—TC-9102 17
When using multistranded wire, crimp a metal sleeve over the exposed conductors before inserting into terminals 60...71.
External supply for fan 230 VAC L = Live Isolate before servicing.
Analog 0 -10 VDC
PAT 24 VAC
-
DAT 24 VAC
M
+
_
+
24 VAC Common
24 VAC Supply
N
L
71 70
Fan
61 60
ON-OFF
42 41
Cooling Output Heating Output
See Note 2
Analog InputsDigital Inputs
Digital Common
11 12 1310 14 15 20 21 22 23 24
ON-OFF (2 stages)
2
24 VAC
See Note 1
40 32 31 30 123
Analog Common
Ground
1
Power Supply
System 91 N2
Communication Bus
RT+
RT- COM
SHIELD
Window
Contact
Occupancy Sensor
Mode LED
Note 1: F or P A T, DAT and ON-OFF outputs, terminals 1, 31 and 41 are
Note 2: Wir ing for Cooling Output is the same as shown for Heating O utput. Note 3: See also figures 17-20 for Room Command Modul e Wi r ing.
Figure 14: TC-9102 Controller Wiring - On/Off Fan Control
18 Technical Bulletin—TC-9102
tc2onoff
See Note 3
NTC
Sensor
internal ly connected. For 0-10 VDC output s, terminals 30 and 40 are internal ly connected
Remote Set Point
.
When using multistranded wire, crimp a metal sleeve over the exposed conductors before inserting into terminals 60...71.
External supply for fan 230 VAC L = Live Isolate before servicing.
N
L
Fan
Low Med.
3-Speed
High
Analog 0 -10 VDC
PAT 24 VAC
-
DAT 24 VAC
ON-OFF (2 stages) 24 VAC
See Note 1
2
M
+
-
+
24 VAC Common
1
24 VAC Supply
Ground
Window
Contact
63 6271 70 61 60 42
Digital Inputs
Digital Common
40
41
Cooling Output
See Note 2
Analog Inputs
Analog
32
Heating Output
Common
11 12 1310 14 15 20 21 22 23 24 50
Occupancy Sensor
Mode LED
NTC
Sensor
Remote Set Point
30
31
52
51
Fan Control Override
3 2 1
Power Supply
System 91 N2
Communication Bus
COM
RT-
RT+
See Note 3
SHIELD
tc2wir3s
Note 1: F or P A T, DAT and ON-OFF outputs, terminals 1, 31 and 41 are
internal ly connected. For 0-10 VDC output s, terminals 30 and 40 are internal ly connected. Note 2: Wir ing for Cooling Output is the same as shown for Heating O utput. Note 3: See also figures 17-20 for Room Command Modul e Wi r ing.
Figure 15: TC-9102 Controller Wiring - 3-Speed Fan Control
Technical Bulletin—TC-9102 19
0 -10 VDC
Fan Speed Control
+
-
Analog 0 -10 VDC
PAT 24 VAC
-
DAT 24 VAC
ON-OFF (2 stages) 24 VAC
See Note 1
2
+
-
M
+
24 VAC Common
1
24 VAC Supply
Ground
Window Contact
61
Digital Inputs
Digital Common
114212 1310 14 15 20
Mode LED
Occupancy
Sensor
NTC
Sensor
4160
40 32 31 30
Cooling Output
See Note 2
Analog Inputs
21 22
23
Remote Set Point
Heating Output
Analog Common
24
See Note 3
3
Power Supply
System 91 N2
Communication Bus
RT- COM SHIELDRT+
tc2wivdc
12
Note 1: For P A T, DAT and ON-OFF outputs, terminals 1, 31 and 41 are
Note 2: Wiring for Cool ing Output is the same as shown for Heating Output. Note 3: See also figures 17-20 for Room Command Modul e Wi r ing.
20 Technical Bulletin—TC-9102
internal ly connected. For 0-10 VDC output s, terminals 30, 40 and 60 are internally
connected.
Figure 16: TC-9102 Controller Wiring -
0 to 10 VDC Fan Control
TC-9102 Controller
52
TM-9150/TM-9160 Room Command Module
51 50
51
3-Speed Fan Override*
24
Internal Connections
23 22 21 20 15 14
Max. 50 m
23 22
21/24
20 15 14
Remote Set Point**
Common NTC S e nso r
Mode LED
Occupancy Button
tc2wwntc
(Min. 0.8 mm diameter wire)
*Only for modules with 3-speed fan override (see ordering codes). **Model TM-9160 only.
Figure 17: TC-9102 Controller Wiring to Room Command
Module with Integral NTC Sensor
TC-9102
Controller
Internal Connections
52 51 50 24 23 22 21 20 15 14
NTC Sensor (Unit Mounted)
Max. 50 m
(Min. 0.8 mm diam eter wire)
TM-9170 Room Command Module
51
23 22
21/24
15 14
tc2wontc
3-Speed Fan Override*
Remote Set Point
Common
Mode LED
Occupancy Button
*Only for modules with 3-speed fan override (see ordering codes).
Technical Bulletin—TC-9102 21
Figure 18: TC-9102 Controller Wiring to Room Command
Module with Unit Mounted NTC Sensor
22 Technical Bulletin—TC-9102
TC-9102 Controller
TM-9180 Room Command Module
TB1
23 22 21 20 15 14
Max. 50 m
22
Voltage Supply
21/24
Common 20 15
Data clock
Transmit/Receive
14
tc2wtm80
(Min. 0.8 mm diameter wire)
Figure 19: TC-9102 Controller Wiring to TM-9180 Room
Command Module
TC-9102 Controller
TM-9180 Room Command Module
24 23 22 21
TB1
23 22
Voltage Supply
21/24
Common
NTC Sensor
20 15 14
(Unit Mounted)
Max. 50 m
20 15
Data clock Transmit/Receive
14
tc2wntc
(Min. 0.8 mm diameter wire)
Figure 20: TC-9102 Controller Wiring to TM-9180 Room
Command Module with Unit Mounted NTC Sensor
Technical Bulletin—TC-9102 23
Jumper and Switch Selections
!
CAUTION: Connections to the on/off or 3-speed fan control
terminals may carry up to 250 VAC. Isolate live and neutral supply lines (double-pole switch) before servicing.
To reach the jumpers and swit ches, open the cont r oll er by gr i pping th e cover with thumb and finger on both sides above center and pull the cover off using the lower edge as a hi nge. Replace t he cover by r est ing the lower edge of the cover against the base and then pressing the cover firmly to engage all four retaining lugs.
Address Switches and Zone Jumpers
If the controller is connected to a communications bus, a network address must be set. Refer to the project documentation for the address setting for the controller. Addresses 0 to 63 can be set on the address switches. The zone jumpers allow addressing up to 255 as follows:
Zone 1 Jumper Zone 2 Jumper Address Switch Network Address OUT OUT 0 to 63 0 to 63 IN OUT 0 to 63 64 to 127 OUT IN 0 to 63 128 to 191 IN IN 0 to 63 192 to 255
The setting on the Address Switches is in binary format:
Switch Numb e r : 1 2 3 4 5 6 Decimal Equivalent: 1 2 4 8 16 32
Example (Address 43):
Switch Numb e r : 1 2 3 4 5 6 Switch Position: ON ON OFF ON OFF ON Decimal Equivalent: 43 = 1 + 2 + 0 + 8 + 0 + 32
Jumpers
Remove the half of the factory setting (gain x 2). (Factor y setting is 2K.)
When the delivered by the factory), the integral action of the contr oller is disabled. Insert the jumper to obtain the factory set default value of four minutes (0.25 repeats per minute).
Set Jumpers TM-9180 with LCD Display (lower position) or a TM-9150/9160/9170 (upper position) is connected.
24 Technical Bulletin—TC-9102
Gain Jumper JP2 (RED)
to reduce the proportional band to
Integral Time Jumper JP2 (BLUE)
as shown in Figure 20, depending on whether a
JP3
is not installed (as
Power LED
Integral Time Jumper (Blue)
Gain Jumper (Red)
Factory Settings (4 spare jumpers packed with
12 34
controller)
Zone 1 Jumper (Black)
Zone 2 Jumper (Black)
Receive/ Transmit LED
Address Switches
SW1
123456
ON
Address Switches (Side View)
JP2
U1
1 2 3
JP3
tc2jmpsw
1 2 3
Jumpers for TM-9180 Module with LCD Display
or
1 2 3
Jumpers for other TM-91xx Modules (factory settings)
Startup
Commission­ing
Figure 21: TC-9102 Controller Jumpers and Switches
When all jumpers and address switches have been set, and all connections have been made and verified, 24 VAC power may be applied. T he Power LED should be lit. If the communications bus is active the R/T LED will flash. If the Power LE D is not lit, check the 24 V supply.
The Configuration Tools for Windows® (WS-EURPRO-0) or T C-9100 Commissioning Tool software (TC-9100-TOOL) running on a PC is required to verify the operation of the controller and to change parameters. Refer to the Configuration Tools for Windows Manual or the TC-9100 Commissioning Tool User’s Guide for further information.
Technical Bulletin—TC-9102 25
26 Technical Bulletin—TC-9102

Specifications & Technical Data

Supply Voltage
Power Consumpti on
Ambient Operati ng
Conditions
Ambient Stor age
Conditions
Terminations
Communication
Interfaces
Controller Addressi ng
Inputs
Outputs
24 VAC, +15% to -10%, 50-60 Hz.
3 VA for controller and room comm and module. (Add power consumption of connected actuat ing devices. )
0° to 50°C 10 to 90% RH noncondensing
-20° to 70°C 10 to 90% RH noncondensing
Screw terminal blocks for 1.5 mm Separable terminal blocks are available as an option.
Optically isolated RS-485 interface for N2 bus connection at 9600 baud. Room Command Module (TM-9180) int er f ace at 600 baud - non- isolat ed
synchronous bus.
0-255 selectable on DIP switches (6) and jumpers (2)
Window Contact: Closed (<1 Kohm) = window closed Occupancy Sensor: Closed (<1 Kohm) = occupied Room Temperature Sensor: NTC Thermistor 0-40 °C* Remote Set Point: 10 Kohm potentiometer* 3-Speed Fan Override: 10 Kohm potentiometer* Occupancy Button: Momentary Contact* *from Room Command M odule TM- 9150/9160/9170
Heating/Cooling
Analog: 0-10 VDC, maximum 10 mA DAT: Tr iac rat ed at 24 VAC, maximum 0.5 A* PAT: 2 x triacs rated at 24 VAC, maximum 0.5 A* 2-Stage On/Off : 2 x triacs rated at 24 VAC, maximum 0.5 A*
* Maximum 1 mA current leakage
Fan Control
On/Off: Relay contact rated at 250 VAC, maximum 3A 3-Speed: Relay contact rated at 250 VAC, maximum 3A Variable Fan Speed: 0- 10 VDC, maxim um 10m A
2
(maximum) cable.
Mounting
Dimensions (H x W x D)
Housing
Shipping Weight
CE Compliance
DIN rail or surface (two brackets supplied with controller). 118 mm x 108 mm x 31 mm ( st andar d t er m inals) 146 mm x 108 mm x 31 mm ( separ able ter m inals)
Material: ABS + polycarbonate, self-extinguishing UL94-VO Protection: IP30 (IEC529)
0.3 kg Directive 89/336/EEC EN 50081-1, EN 50082-1 Directive 73/23/EEC EN 60730
Technical Bulletin—TC-9102 27
Factory-Set Paramet ers
Table 3: Factory-Set Parameters
Comfort Set Point Heating 20°C +/-3 K Remote Set Point. See Note 2.
-1 K 12-28°C Remote Set Point
Comfort Set Point Cooling 22°C +/-3 K Remote Set Point. See Note 2.
+1 K 12-28°C Remote Set Point Prop. Band Heating -2 K -1 K when RED jumper OUT. See Note 1. Integral Time Heating 4 minutes Disabled when BLUE jumper OUT. See Note 1. Standby Bias Heating -2 K Night Bias Heating -4 K Prop. Band Cooling +2 K +1 K when RED jumper OUT. See Note 1. Integral Time Cooling 4 minut es Disabled when BLUE jumper OUT. See Note 1. Standby Bias Cooling +2 K Night Bias Cooling +4 K Heating Valve Stroke (PAT) 60 seconds +/- 1% Dead Band Heating Valve Cycle (DAT) 300 seconds 5% minimum On/Off Heating Stage 1 Load (2St) 50 % 5% differential Cooling Valve Stroke (PAT) 60 seconds +/- 1% Dead Band Cooling Valve Cycle (DAT) 300 seconds 5% minimum O n/ O ff Cooling Stage 1 Load (2St) 50 % 5% differential Fan On/Off Differential 1 K Fan always On in Comfort No Yes = Fan On in zero energy band in Comfort. Min. Fan Output (0-10 VDC) 50 % Low Limit Set Point 12°C Low Limit Differential 2 K Winter Compensation Disabled Requires O ut door Air Tem p via Bus when enabled. Winter Set Point 10°C Winter Authority Slope -0. 1 Winter Authority Limit -3 K Summer Compensation Disabled Requires Outdoor Air Temp via Bus when enabled. Summer Se t Point 24°C Summer Authority Slope 0.2 Summer Authority Limit 5 K Room Temp Filter Const. 10 seconds Remote S.P.Filter Const. 60 seconds Common Set Point 0°C Valid range = - 3 t o 28. See Note 2. Unit Mount Sensor No Yes = Hard wired temperature sensor is used and
TM-9180 is connected.
Note 1: Controllers are delivered from the factory with the RED
Note 2: When the Remote Set Point is +/-3 K, the Common Set Point
28 Technical Bulletin—TC-9102
jumper “IN” and the BL UE ju mper “OUT” unless otherwise
specified.
may be set to the desired mean room temperature (e.g. 21°C)
and the Comfort Set Point Heating and Comfort Set Point
Cooling set as biases of -1K and +1K, respectively.
Paramet ers for Supervisory System
Room Temperature °C AI1 Read Remote Set Point °C or K AI2 Read Working Set Point Heating °C WSP1 Read Working Set Point Cooling °C WSP2 Rea d Control Output Heating % OCM1 Read Control Output Cooling % OCM2* Read Heating/Cooling Mode Cool/Heat L1A* Read Operating Status Comfort/Standby/ Night/ Off MODS Read Alternate Mode Off/On ALT Read Window Contact Closed/Open WI N Read Occupancy Sensor Occupied/Unoccupied OCC Read Low Limit Mode Off/On AFM Read Winter Set Point Compensation K WAC Read Summer Set Point Compensation K SAC Read Requested Operating Mode Comfort/Standby/Night/ Off MODC Write Set Outdoor Temperature °C XAI4 Read/Write Set Common Set Point °C or K PM6K1 Read/Write
The following table lists the parameters which are available for monitoring by Metasys supervisory systems. For details of configuration procedures and override possibilities, refer to the technical documentation of the system which is to be used.
Table 4: Supervisory System Parameters
Parameter Descri pt i on Units Tag Name Function
On/Off Fan Control:
Fan Status Off/On DO2 Read
3-Speed Fan Control:
Fan Speed 1 Off/On DO5 Read Fan Speed 2 Off/On DO6 Read Fan Speed 3 Off/On DO7 Read Fan Override Auto/Hold FOV Read
Fan Speed Controller :
Control Output Fan % OCM3 Read
*Note: For 0-10 VDC control signal outputs, OCM1 and OCM2 operate
in parallel and indicate the output level in Heating or Cooling. Therefore, at the supervisory system, OCM1 should be monitored as the “Heating/Cooling Control Output” and L1A can be monitored to indicate whether the controller is in heating or cooling mode. (Requires Metasys Release 9.0 or later.)
Technical Bulletin—TC-9102 29
Ordering Codes
Ordering Code Hardwar e
TC-91a2-b220 TC-91x2-x220 2 x 0 to 10 VDC 0 to 10 VDC Fan Control 12 -28°C TC-91a2-b225 TC-91x2-x220 2 x 0 to 10 VDC 0 to 10 VDC Fan Control +/-3 K TC-91a2-b440 TC-91x2-x330 2 x DAT 0 to 10 VDC Fan Control 12 -28°C TC-91a2-b445 TC-91x2-x330 2 x DAT 0 to 10 VDC Fan Control +/-3 K TC-91a2-b550 TC-91x2-x330 2 x PAT 0 to 10 VDC Fan Control 12 -28°C TC-91a2-b555 TC-91x2-x330 2 x PAT 0 to 10 VDC Fan Control +/-3 K TC-91a2-b660 TC-91x2-x330 2 x 2 Stage On/Off 0 to 10 VDC Fan Control 12 -28°C TC-91a2-b655 TC-91x2-x330 2 x 2 Stage On/Off 0 to 10 VDC Fan Control +/-3 K TC-91a2-b221 TC-91x2-x221 2 x 0 to 10 VDC On/Off Fan 12-28°C TC-91a2-b226 TC-91x2-x221 2 x 0 to 10 VDC On/Off Fan +/-3 K TC-91a2-b441 TC-91x2-x331 2 x DAT On/Off Fan 12-28°C TC-91a2-b446 TC-91x2-x331 2 x DAT On/Off Fan +/-3 K TC-91a2-b551 TC-91x2-x331 2 x PAT On/ Off Fan 12-28°C TC-91a2-b556 TC-91x2-x331 2 x PAT On/ Off Fan +/-3 K TC-91a2-b661 TC-91x2-x331 2 x 2 Stage On/Off On/O ff Fan 12-28°C TC-91a2-b666 TC-91x2-x331 2 x 2 Stage On/Off On/O ff Fan +/-3 K TC-91a2-b222 TC-91x2-x222 2 x 0 to 10 VDC 3-Speed Fan 12-28°C TC-91a2-b227 TC-91x2-x222 2 x 0 to 10 VDC 3-Speed Fan +/-3 K TC-91a2-b442 TC-91x2-x332 2 x DAT 3-Speed Fan 12-28°C TC-91a2-b447 TC-91x2-x332 2 x DAT 3-Speed Fan +/-3 K TC-91a2-b552 TC-91x2-x332 2 x PAT 3-Speed Fan 12-28°C TC-91a2-b557 TC-91x2-x332 2 x PAT 3-Speed Fan +/-3 K TC-91a2-b662 TC-91x2-x332 2 x 2 Stage On/Off 3-Speed Fan 12-28°C TC-91a2-b667 TC-91x2-x332 2 x 2 Stage On/Off 3-Speed Fan +/-3 K Controller for remot e set point : a = 0, with int egr at ed set point : a = 1 Controller with standard term inals: b = 0, with separ able ter m inals: b = 1 Notes: 1. Ordering codes must be used in orders t o t he Lom agna f act ory.
2. The Hardware Configuration Code is shown in the EuroPRO Configuration Tool to indicate t he basic hardware configuration of the cont r oller which is being commissioned. The sof t war e conf igurat ion of the controller, as indicated by the O r der ing Code, m ay be changed in EuroPRO t o any ot her software configuration with the sam e har dwar e conf igurat ion. For exam ple, TC-91a2- b442 could be changed to TC-91a2-b552 because both have the same har dwar e conf iguration, TC-91x2-x332.
3. Modules with PWM control signal outputs have been discontinued. Contact your local Johnson Controls office for details of r eplacement controllers.
Table 5: TC-9102 Controller Ordering Codes
Outputs Set Point Configurati on Code (used in EuroPRO)
Range
30 Technical Bulletin—TC-9102
Table 6: Room Command Module Ordering Codes
Ordering Code Description
TM-9150-0000 Occupancy Button NTC Sensor w/o S.P. dial TM-9160-0000 Occupancy Button NTC Sensor 12-28°C TM-9160-0005 Occupancy Button NTC Sensor +/- 3 K TM-9160-0002 Occupancy Button NTC Sensor 12-28°C 3- Speed Fan Ov er r ide TM-9160-0007 Occupancy Button NTC Sensor +/- 3 K 3-Speed Fan O v er r ide TM-9170-0000 Occupancy Button w/o Sensor 12-28°C TM-9170-0005 Occupancy Button w/o Sensor +/- 3 K TM-9170-0002 Occupancy Button w/o Sensor 12-28°C 3-Speed Fan Override TM-9170-0007 Occupancy Button w/o Sensor +/- 3 K 3-Speed Fan Override TM-9180-0100 LCD Display with View Mode and Clock Setting only TM-9180-0200 LCD Display with View Mode and Programming Mode Note:All models above with off-white cover and grey base.
Add “-W” to code for white cover and white base, e. g. , TM-9150-0000-W. Add “-K” to code for set point dial with serr at ed edge ( not for TM-9150 or TM- 9180),
e.g. TM-9160-0005- K, TM-9160-0005-WK.
Table 7: Software and Accessories Ordering Codes
Ordering Code Description
TE-9100-8501 Unit Mount NTC Temperature Sensor (1.5-m cable) TC-9100-TOOL Commissioning Software for DOS (3. 5" diskett e) WS-EURPRO-0 Configuration Tools Software for Windows®, New (3.5" diskettes) WS-EURPRO-6 Configuration Tools Software for Windows®, Upgrade (3.5" diskettes)
Technical Bulletin—TC-9102 31
32 Technical Bulletin—TC-9102
Technical Bulletin—TC-9102 33
Notes
Johnson Controls, Inc.
Westendhof 8 TC-9102 Technical Bulletin 45143 Essen Rev. Level 0698 Germany Printed in Germany
System 91 Manual
34 Technical Bulletin—TC-9102
Loading...