The TC-9102 series of microprocessor-based controllers is designed for
the control of Fan Coil Units (FCUs) with heating and cooling, and a
single-speed, 3-speed or var iable- speed fan. T h e contr oll er can regul ate
water valves, one or 2-stage electric heating, or a cooling unit wher e the
compressor has its own short cycle protection.
The comfort temperature set point of the controller may be adjusted via a
TM-9100 Series Room Command Module, and the occupied and
unoccupied control modes of operation temporarily changed. A window
open sensing contact may be connected to switch the controller to the off
mode, and a low temperature limit protection feature is available.
The controller is factory-configured to contr ol with default oper ating
parameters so that no external setup devi ces ar e necessar y. However , a
software package for a PC is available to ver i f y th e cor r ect oper ati on of
the controller and to modify the configuration, if necessary.
Winter and summer compensation may be enabled when th e contr oll er
receives outdoor air temperature data via the communications bus, and
modes of operation may be set by time scheduling programs or control
processes in the supervisory system.
The TC-9102 Controller is available in several model types according to
the type of outputs and the range of the integrated or remote set point
input. Refer to Ordering Codes at the end of this bulletin for details.
4 Technical Bulletin—TC- 9102
Controller
Functions
The controller can be connected to a Room Command Module, from
which it receives the room temper atur e, the remote set point and other
override signals. The TM-9180 intelligent Room Command Module
provides these signals via a serial bus connection to the controller. The
other Room Command Modules (TM-9150/9160/9170) provide the
signals as individually connected physical inputs to the controller. In
addition, an NTC temperature sensor is available for mounting within the
FCU.
For installations without a Room Command Module, the controller is
available with an integrated set point adjuster. Alternatively, the remote
set point and fan override controls may be incorporated into a custom
FCU control panel. Refer to the Specifications and Technical Data
section of this bulletin for details of the components required.
Occupancy Sensor
Window Contact
Room
Command
Module
Room Temp.*
Remote Setpoint
Occupancy Button
Fan Override
(3-speed only)
Communications Bus
(Supervisory Control,
Outdoor Air Temp.)
Figure 4: Controller with Room Command Module
Room Temp.
NTC Sensor
Controller
Occupancy Sensor
Window Contact
Output Heating
Output Cooling
Fan Control
tc2cwrcm
*
NTC sensor may be
mounted in FCU.
Output Heating
Controller
(Setpoint)
Fan Override
(3-speed only)
tc2cwspa
Communications Bus
(Supervisory Control,
Outdoor Air Temp.)
Figure 5: Controller with Integrated Setpoint Adjuster
Technical Bulletin—TC-9102 5
Output Cooling
Fan Control
Standalone
Mode
The controller operates in standalone mode when it is not connected to a
supervisory system via the communications bus nor to a TM-9180 Room
Command Module. In standalone mode the controller may operate in one
of three control modes:
• COMFORT (occupied): control at comfort set point
• STANDBY (unoccupied): control at a standby level set point
• OFF (not in use): low limit control only
The control modes are set by the window contact and occupancy sensor
inputs, and may be modified by the occupancy button on the Room
Command Module as shown in Table 1.
When connected to a supervisory system via the communications bus or
to a TM-9180 Room Command Module, the controller may operate in
COMFORT, STANDBY or OFF control modes, and additionally in
NIGHT mode:
NIGHT (scheduled unoccupied): control at a night level set point.
The control modes are set by the supervisory system or TM-9180, and are
modified by the occupancy sensor input and occupancy button on the
Room Command Module as shown in Table 2. The window contact input
always switches the controller to OFF control mode, and a MANUAL
mode is available from the supervisory system to inhibit the action of the
occupancy sensor and occupancy button.
*(T) = Timed (Returns t o Cont r ol Mode af ter 1 hour.)
6 Technical Bulletin—TC- 9102
Controller Set
Points
The set point in all control modes may be modified from the integrated
set point adjuster or from the remote set point dial/control panel on the
Room Command Module, according to the controller model type. The
controller models with a remote set point of 12-28°C require that a Room
Command Module or an external potentiometer is connected to give the
set point. Controllers with a remote set point of +/-3 K have internal
factory set points of 20°C for heating and 22°C for cooling.
The set point is decreased or increased in the STANDBY control mode
by the factory-set “Standby Bias Heating” and “Standby Bias Cooling”
values to reduce the heating or cooling energy required when the room is
temporarily unoccupied.
When a supervisory system is connected, the set point can be further
decreased or increased in the NI GHT control mode to fur ther r educe
energy requirements during scheduled unoccupied periods such as nights,
weekends and holidays.
In the controller there are two “comfort” set points (Comfort Set Point
Heating and Comfort Set Point Cooling), and the difference between
these two values determines th e zer o ener gy band wher e neit her heati ng
nor cooling is required. The controller calculates two working set points
(WSP Heating and WSP Cooling), which are the sum of the comfort set
point values, the “Remote Set Point” value coming from the integrated
set point adjuster or the Room Command Module, and the “Common Set
Point” value. In the supervisory mode an adjustment may be made to the
working set points either by changing the “Comfort Set Points,” or by
changing the value in the “Common Set Point” parameter of the
controller which enables the supervisory system operator to adjust the
setpoints for heating and cooling at the same time without affecting the
zero energy band. In summary:
Working Set Point (Heating) = Comfort Set Point (Heating) (Supervisory System)
+ Remote Set Point (integrated adjuster or Command Module dial)
+ Common Set Point (Supervisory System)
+ STANDBY or NIGHT Bias Heating (if mode is active)
Working Set Point (Cooling) = Comfort Set Point (Cooling) (Supervisory System)
+ Remote Set Point (integrated adjuster or Command Module dial)
+ Common Set Point (Supervisory System)
+ STANDBY or NIGHT Bias Cooling (if mode is active)
When the room temperature is below the working set point for heating,
the heating output increases according to the proportional band and
integral time parameters set for the heating control loop. When the room
temperature is above the working set point for cooling, the cooling output
increases according to the proportional band and integral time parameters
set for the cooling control loop. Heating and cooling control is illustrated
in figures 8 and 9.
Technical Bulletin—TC-9102 7
Alternate Mode
When pressed for about one second, the occupancy button on the Room
Command Module changes the mode of operation of the controller to the
“Alternate Mode” or back to the nor m al “Cont r ol Mode” as shown i n
Table 2. The “COMFORT ( T)” alternate mode is active onl y f or a per iod
of one hour, after which the controller r evert s to the normal control
mode.
Fan Control
The controllers with on/off fan control switch the fan on when the room
temperature is below the working set point for heating and above the
working set point for cooling, and switch the fan off when the room
temperature has entered th e zer o ener gy band by th e value set f or t he f an
differential. The fan can optionally be set to continue running in the zero
energy band in the COMFORT (occupied) mode, using the software
commissioning tool.
In controllers with 3-speed fan control outputs, the fan stages are
switched in sequence as the room temper at ur e decr eases or incr eases, and
Speed 1 remains on in the zero energy band.
In controllers with a 0 to 10 VDC output for a fan speed controller, the
output increases as the room t emper at ur e f all s below th e wor king set
point for heating or rises above the working set point for cooling, and
maintains a minimum output (set by default at 50%) when the room
temperature has entered the zero ener gy band.
For all controllers, in OFF mode the fan is switched off and the heating
and cooling outputs are set to the fully closed or off level. Fan control
sequences are shown in figures 10, 11 and 12.
3-Speed Fan Override
The speed of a 3-speed fan may be set manually from the Room
Command Module when the controller is in COMFORT (occupied)
mode. In the “AUTO” position the speed is set by the controller
according to the room temperature. In the manual “OFF- 1- 2- 3” positions
the fan runs at the selected speed. T h e f an over r ide i s not acti ve in
STANDBY, NIGHT or OFF modes.
In controller models with 2-stage on/off heating and cooling outputs, all
outputs are switched off when the fan speed is set to “OFF” to protect
electrical heating and cooling devices that require a minimum air flow for
normal operation. This feature can be enabled for other types of outputs,
if required, using the software commissioning tool. Refer to
Commissioning later in this document.
Low Limit Mode
The low limit mode is active when the room temperature falls below the
low limit set point. The fan is switched on at full speed and the heating
output is set to the maximum level until the room temperature rises by the
low limit differential value.
8 Technical Bulletin—TC- 9102
Winter/Summer
Compensation
Setpoint
Compensation
(K)
When the controller is connected to a super visor y system , t he wint er
and/or summer compensation modes may be enabled. The supervisory
system must be programmed to set the outdoor air temperature via the
communications bus on a periodic basis. After a power interruption the
winter and summer compensation modes are temporarily disabled until a
new outdoor air temperature value is received. When the outdoor
temperature falls below the winter set point, the working set point of the
controller will be raised or lowered in accordance with the winter
authority slope. When the outdoor temperature rises above the summer
set point the working set point of the controller will be raised in
accordance with the summer authority slope. The maximum amount of
compensation is limited by the Winter Authority Limit and the Summer
Authority Limit.
The effect of the wint er and summer com pensati on on the cont ro ller set
point is shown below.
-1
-2
-3
-4
-5
5
4
3
2
1
Winter Authority Slope
(+0,1)
0
-20-30
-10
0
Summer Authority Limit
(+5 K)
1020
30
Summer Authority
Slope (+0,2)
Outdoor Air
Temperature
4050
(°C)
Winter Authority
Slope (-0,1)
Winter Authority
Limit (-3 K))
Winter
Setpoint
(10°C)
Summer
Setpoint
(24°C)
tc2winsu.drw
Figure 6: Winter/Summer Compensation
Technical Bulletin—TC-9102 9
Auto-dial
Feature
When the controller is connected to a remo te N2 Bus and super vised by a
Metasys N2 Dialer (NU-NDM101-0) which is linked to a Metasys
network by a telephone line, the following alarm conditions in the
controller will initiate the automatic dial feature:
• Window Open
• Low Limit mode
• High or low alarm limit violation of the room temperature when alarm
limits have been set by the supervisory system.
When any one of these alarm conditions occurs, the N2 Dialer will detect
the alarm and connect the remo te N2 Bus t o th e Metasys net wor k. When
the telephone line connection is established the controller alarm status
will automatically be reset and the controller is then ready to report
further alarm condit ions as t hey occur . R efer to the Technical Bulletin of
the NU-NDM101-0 for further information.
Output Types
0 - 10 VDC
DAT - Duration
Adjust Type
The heating and cooling outputs are one of the following types,
depending on the controller model code:
The output is an analog voltage between 0 and 10 VDC in direct
proportion to the controller output from 0 to 100%.
The DAT output is a triac which is switched on for a duration within the
set heating or cooling valve cycle time in direct proportion to the
controller output from 0 to 100%. To avoid unnecessary switching of the
valve actuator when the output is between 0 and 5% the triac remains off,
and when the output is between 95 and 100% the triac remains on. The
default cycle time is 300 seconds.
ON
OFF
50% O utput
DAT Cycle Time
30% Output
DAT Cycle Time
Figure 7: DAT Output
10 Technical Bulletin—TC-9102
(°C)
g
PAT - Position
Adjust Type
The PAT output is a pair of triacs which are switched on to open and
close an incrementally driven heating or cooling valve. The duration of
switching is directly proportional to the change in the controller output
and related to the full stroke time of the valve such that a 100% change
will completely open or close the valve. At the 0% or 100% position the
duration of switching is increased to ensure that the valve is completely at
its end position and the appropriate triac is switched on for the full stroke
time every two hours to ensure that the valve remains at its end position.
To prevent unnecessary wear on the actuator, the triac output will only be
switched when the output change exceeds 1% in the same dir ection as t he
previous change or 2% if the direction of change is reversed. T he def ault
full stroke time is 60 seconds.
100
Heating
Output (%)
0
5
2-Stage On/Off
Cooling
Comfort
Standby
Night
Comfort
Night
Standby
Low Limit
Room
1214161820222426
1030
Temperature (°C)
tc2hcvdc
Figure 8: Heating/Cooling Control 0-10 VDC, DAT, PAT
The output is a pair of triacs which are switched on in sequence as the
controller output increases. The first stage triac is switched as soon as the
output is above 0% and the second stage triac is switched when the output
is equal to the set load rating for the first stage which is defaulted to 50%.
The switching differential is fixed at 5%. When this type of output is used
with 3-speed fan control, the output will be switched off whenever the
fan speed is manually overridden to the “OFF” position on the Room
Control Module. The control diagram is shown below.
O utput (% )
100
Heating
222 222
Low Limit
0
5
1214161820222426
10
1
1
Night
1
Comfort
Stan dby
C oo lin
111
Comfort
Night
Standby
Room
Tem perature
30
Figure 9: Heating/Cooling Control - 2-Stage On/Off
Technical Bulletin—TC-9102 11
Fan Output
Types
Fan On/Off
ON
OFF
5
The output is a normally open relay contact which closes when the fan is
required to run. Terminals are provided to connect the fan supply voltage
to the controller in order to facilitate the wiring to the fan motor. The fan
supply voltage is not used within the controller.
Night
Low Limit
Standby
Comfort
Standby
Night
Room
1214161820222426
1030
Temperature (°C)
Figure 10: On/Off Fan Control - Switch Points
3-Speed Fan
Control
3
2
1
5
The output is a set of interlocked r elay contact s, one contact f or each
speed which closes when that speed is selected to run. T er mi nal s ar e
provided to connect the fan supply voltage to the controller in order to
facilitate the wiring to the fan motor. The fan supply voltage is not used
within the controller.
Low Lim it
Standby
Night
3
Comfort
22
3
1
Comfort
Night
Standby
Room
1030
1214161820222426
Temperature (°C)
tc2swpts
12 Technical Bulletin—TC-9102
Figure 11: 3-Speed Fan Control - Switch Points
0 to 10 VDC
Control Signal
The output is a control signal for driving a fan speed controller with an
opto-isolated 0 to 10 VDC input. As the output voltage increases, the fan
speed controller must increase the speed of the fan from the minimum
speed of the fan motor to its maximum speed. When the output is below
the voltage required for the minimum speed, the fan must be switched
off.
100
Output (%)
0
5
Heating
Cooling
Comfort
Standby
Night
Comfort
Low Limit
Night
Standby
Minimum
Speed Level
1214161820222426
1030
Figure 12: 0 to 10 VDC Fan Control Signal
Room
Tem perature (°C)
tc2facos
Technical Bulletin—TC-9102 13
14 Technical Bulletin—TC-9102
Installation
The TC-9102 series controller is designed to be mounted within the Fan
Coil Unit housing or within a control cabinet. The mounting location
must be clean and dry, and not subject to extreme heat or cold. The
installation and electrical wiring must conform to local codes and should
be carried out by authorized personnel only. Users should ensure that all
Johnson Controls' products are used safely and without risk to health or
property.
Mounting
4.6 mm/
0.18"
101.6 mm/
3.99"
6 mm/
0.24"
For surface mounting, slide the two mounting brackets into the slots at
opposite corners of the controller base behind the terminals. Fix to the
surface using the 4-mm di amet er self - t apping scr ews.
For DIN rail mounting, place the controller on the upper edge of the r ail
and press the controller firmly against the rail until the spring-loaded clip
engages the lower edge of the rail. To remove the controller, insert a
screw driver into the clip at the base of the controller and pull the clip
downwards to release. Alternatively, lift the controller upwar ds against
the spring of the retaining clip and pull forward from the top.
120 mm/4.72"
14 mm/
0.55"
118 mm/
4.64"
(Separable Terminals
Only)
14 mm/
108 mm/4.25"
0.55"
31 mm/
3
1.22"
itc02dim
Figure 13: TC-9102 Controller Dimensions
Technical Bulletin—TC-9102 15
Note: A minimum of 25 mm of space is required above and below the
controller for the removal of separable terminals.
16 Technical Bulletin—TC-9102
Wiring
Before connecting or disconnecting any wires, ensure that all power
supplies have been switched off and all wires are potential-free to prevent
equipment damage and avoid electrical shock.
Terminations are made on the terminal blocks, at the top and bottom of
the controller, which accept up to 1. 5mm2 wires. Follow the wiring
diagrams shown in figures 14 to 20.
When the TC-9102 model with separable terminal blocks is being wired,
it is recommended that the removable parts of the blocks be unplugged
before terminating the wires, and that they are not plugged in again until
the wiring has been fully checked.
Separate extra low voltage (safe) wiring fr om power line voltage wir i ng.
A distinctive colour such as white or pink is recommended for low
voltage wiring. Keep all cables as short as possible and tie in position. Do
not run cables close to transformers or high frequency generating
equipment.
The 24 V supply must be stable and not shared with other switched
inductive loads. When multiple loads are connected to one transformer,
wire each load from th e tr ansf or m er separ ately so th at any possi ble
disturbances from one load will have minimal effect on other loads.
Complete and verify all wiring connections before continuing with the
installation procedure.
!
CAUTION: Connections to the on/off or 3-speed fan control
terminals may carry up to 250 VAC. Isolate live and
neutral supply lines (double-pole switch) before
servicing.
Technical Bulletin—TC-9102 17
When using multistranded wire,
crimp a metal sleeve over the exposed
conductors before inserting into
terminals 60...71.
External supply for fan
230 VAC L = Live
Isolate before servicing.
Analog 0 -10 VDC
PAT 24 VAC
-
DAT 24 VAC
M
+
_
+
24 VAC
Common
24 VAC
Supply
N
L
7170
Fan
6160
ON-OFF
4241
Cooling Output Heating Output
See Note 2
Analog InputsDigital Inputs
Digital Common
1112131014152021222324
ON-OFF
(2 stages)
2
24 VAC
See Note 1
40323130123
Analog
Common
Ground
1
Power Supply
System 91 N2
Communication Bus
RT+
RT- COM
SHIELD
Window
Contact
Occupancy
Sensor
Mode LED
Note 1:F or P A T, DAT and ON-OFF outputs, terminals 1, 31 and 41 are
Note 2:Wir ing for Cooling Output is the same as shown for Heating O utput.
Note 3:See also figures 17-20 for Room Command Modul e Wi r ing.
Figure 14: TC-9102 Controller Wiring - On/Off Fan Control
18 Technical Bulletin—TC-9102
tc2onoff
See Note 3
NTC
Sensor
internal ly connected.
For 0-10 VDC output s, terminals 30 and 40 are internal ly connected
Remote
Set Point
.
When using multistranded wire,
crimp a metal sleeve over the exposed
conductors before inserting into
terminals 60...71.
External supply for fan
230 VAC L = Live
Isolate before servicing.
N
L
Fan
LowMed.
3-Speed
High
Analog 0 -10 VDC
PAT 24 VAC
-
DAT 24 VAC
ON-OFF
(2 stages)
24 VAC
See Note 1
2
M
+
-
+
24 VAC
Common
1
24 VAC
Supply
Ground
Window
Contact
63627170616042
Digital Inputs
Digital Common
40
41
Cooling Output
See Note 2
Analog Inputs
Analog
32
Heating Output
Common
111213101415202122232450
Occupancy
Sensor
Mode LED
NTC
Sensor
Remote
Set Point
30
31
52
51
Fan Control
Override
321
Power Supply
System 91 N2
Communication Bus
COM
RT-
RT+
See Note 3
SHIELD
tc2wir3s
Note 1:F or P A T, DAT and ON-OFF outputs, terminals 1, 31 and 41 are
internal ly connected.
For 0-10 VDC output s, terminals 30 and 40 are internal ly connected.
Note 2:Wir ing for Cooling Output is the same as shown for Heating O utput.
Note 3:See also figures 17-20 for Room Command Modul e Wi r ing.
Figure 15: TC-9102 Controller Wiring - 3-Speed Fan Control
Technical Bulletin—TC-9102 19
0 -10 VDC
Fan Speed Control
+
-
Analog 0 -10 VDC
PAT 24 VAC
-
DAT 24 VAC
ON-OFF
(2 stages)
24 VAC
See Note 1
2
+
-
M
+
24 VAC
Common
1
24 VAC
Supply
Ground
Window
Contact
61
Digital Inputs
Digital Common
1142121310141520
Mode LED
Occupancy
Sensor
NTC
Sensor
4160
40323130
Cooling Output
See Note 2
Analog Inputs
2122
23
Remote
Set Point
Heating Output
Analog
Common
24
See Note 3
3
Power Supply
System 91 N2
Communication Bus
RT- COM SHIELDRT+
tc2wivdc
12
Note 1: For P A T, DAT and ON-OFF outputs, terminals 1, 31 and 41 are
Note 2: Wiring for Cool ing Output is the same as shown for Heating Output.
Note 3:See also figures 17-20 for Room Command Modul e Wi r ing.
20 Technical Bulletin—TC-9102
internal ly connected.
For 0-10 VDC output s, terminals 30, 40 and 60 are internally
connected.
Figure 16: TC-9102 Controller Wiring -
0 to 10 VDC Fan Control
TC-9102 Controller
52
TM-9150/TM-9160
Room Command Module
51
50
51
3-Speed Fan
Override*
24
Internal
Connections
23
22
21
20
15
14
Max. 50 m
23
22
21/24
20
15
14
Remote
Set Point**
Common
NTC S e nso r
Mode LED
Occupancy Button
tc2wwntc
(Min. 0.8 mm diameter wire)
*Only for modules with 3-speed fan override (see ordering codes).
**Model TM-9160 only.
Figure 17: TC-9102 Controller Wiring to Room Command
Module with Integral NTC Sensor
TC-9102
Controller
Internal
Connections
52
51
50
24
23
22
21
20
15
14
NTC Sensor
(Unit Mounted)
Max. 50 m
(Min. 0.8 mm diam eter wire)
TM-9170 Room
Command Module
51
23
22
21/24
15
14
tc2wontc
3-Speed Fan
Override*
Remote
Set Point
Common
Mode LED
Occupancy Button
*Only for modules with 3-speed fan override (see ordering codes).
Technical Bulletin—TC-9102 21
Figure 18: TC-9102 Controller Wiring to Room Command
Module with Unit Mounted NTC Sensor
22 Technical Bulletin—TC-9102
TC-9102
Controller
TM-9180 Room
Command Module
TB1
23
22
21
20
15
14
Max. 50 m
22
Voltage Supply
21/24
Common
20
15
Data clock
Transmit/Receive
14
tc2wtm80
(Min. 0.8 mm diameter wire)
Figure 19: TC-9102 Controller Wiring to TM-9180 Room
Command Module
TC-9102
Controller
TM-9180 Room
Command Module
24
23
22
21
TB1
23
22
Voltage Supply
21/24
Common
NTC Sensor
20
15
14
(Unit Mounted)
Max. 50 m
20
15
Data clock
Transmit/Receive
14
tc2wntc
(Min. 0.8 mm diameter wire)
Figure 20: TC-9102 Controller Wiring to TM-9180 Room
Command Module with Unit Mounted NTC Sensor
Technical Bulletin—TC-9102 23
Jumper and
Switch
Selections
!
CAUTION: Connections to the on/off or 3-speed fan control
terminals may carry up to 250 VAC. Isolate live and
neutral supply lines (double-pole switch) before
servicing.
To reach the jumpers and swit ches, open the cont r oll er by gr i pping th e
cover with thumb and finger on both sides above center and pull the
cover off using the lower edge as a hi nge. Replace t he cover by r est ing
the lower edge of the cover against the base and then pressing the cover
firmly to engage all four retaining lugs.
Address
Switches and
Zone Jumpers
If the controller is connected to a communications bus, a network address
must be set. Refer to the project documentation for the address setting for
the controller. Addresses 0 to 63 can be set on the address switches. The
zone jumpers allow addressing up to 255 as follows:
Zone 1 JumperZone 2 JumperAddress SwitchNetwork Address
OUTOUT0 to 630 to 63
INOUT0 to 6364 to 127
OUTIN0 to 63128 to 191
ININ0 to 63192 to 255
The setting on the Address Switches is in binary format:
Switch Numb e r :123456
Decimal Equivalent:12481632
Example (Address 43):
Switch Numb e r :123456
Switch Position:ONONOFFONOFFON
Decimal Equivalent:43 =1 + 2 +0 +8 +0 +32
Jumpers
Remove the
half of the factory setting (gain x 2). (Factor y setting is 2K.)
When the
delivered by the factory), the integral action of the contr oller is disabled.
Insert the jumper to obtain the factory set default value of four minutes
(0.25 repeats per minute).
Set Jumpers
TM-9180 with LCD Display (lower position) or a TM-9150/9160/9170
(upper position) is connected.
24 Technical Bulletin—TC-9102
Gain Jumper JP2 (RED)
to reduce the proportional band to
Integral Time Jumper JP2 (BLUE)
as shown in Figure 20, depending on whether a
JP3
is not installed (as
Power
LED
Integral Time Jumper (Blue)
Gain Jumper (Red)
Factory Settings
(4 spare jumpers
packed with
12 34
controller)
Zone 1 Jumper (Black)
Zone 2 Jumper (Black)
Receive/
Transmit
LED
Address
Switches
SW1
123456
ON
Address Switches
(Side View)
JP2
U1
1 2 3
JP3
tc2jmpsw
1 2 3
Jumpers for TM-9180 Module
with LCD Display
or
1 2 3
Jumpers for other TM-91xx
Modules (factory settings)
Startup
Commissioning
Figure 21: TC-9102 Controller Jumpers and Switches
When all jumpers and address switches have been set, and all connections
have been made and verified, 24 VAC power may be applied. T he Power
LED should be lit. If the communications bus is active the R/T LED will
flash. If the Power LE D is not lit, check the 24 V supply.
The Configuration Tools for Windows® (WS-EURPRO-0) or T C-9100
Commissioning Tool software (TC-9100-TOOL) running on a PC is
required to verify the operation of the controller and to change
parameters. Refer to the Configuration Tools for Windows Manual or theTC-9100 Commissioning Tool User’s Guide for further information.
Technical Bulletin—TC-9102 25
26 Technical Bulletin—TC-9102
Specifications &
Technical Data
Supply Voltage
Power Consumpti on
Ambient Operati ng
Conditions
Ambient Stor age
Conditions
Terminations
Communication
Interfaces
Controller Addressi ng
Inputs
Outputs
24 VAC, +15% to -10%, 50-60 Hz.
3 VA for controller and room comm and module.
(Add power consumption of connected actuat ing devices. )
0° to 50°C
10 to 90% RH noncondensing
-20° to 70°C
10 to 90% RH noncondensing
Screw terminal blocks for 1.5 mm
Separable terminal blocks are available as an option.
Optically isolated RS-485 interface for N2 bus connection at 9600 baud.
Room Command Module (TM-9180) int er f ace at 600 baud - non- isolat ed
synchronous bus.
0-255 selectable on DIP switches (6) and jumpers (2)
Window Contact:Closed (<1 Kohm) = window closed
Occupancy Sensor:Closed (<1 Kohm) = occupied
Room Temperature Sensor:NTC Thermistor 0-40 °C*
Remote Set Point:10 Kohm potentiometer*
3-Speed Fan Override: 10 Kohm potentiometer*
Occupancy Button:Momentary Contact*
*from Room Command M odule TM- 9150/9160/9170
Heating/Cooling
Analog:0-10 VDC, maximum 10 mA
DAT:Tr iac rat ed at 24 VAC, maximum 0.5 A*
PAT:2 x triacs rated at 24 VAC, maximum 0.5 A*
2-Stage On/Off :2 x triacs rated at 24 VAC, maximum 0.5 A*
* Maximum 1 mA current leakage
Fan Control
On/Off:Relay contact rated at 250 VAC, maximum 3A
3-Speed:Relay contact rated at 250 VAC, maximum 3A
Variable Fan Speed: 0- 10 VDC, maxim um 10m A
2
(maximum) cable.
Mounting
Dimensions (H x W x D)
Housing
Shipping Weight
CE Compliance
DIN rail or surface (two brackets supplied with controller).
118 mm x 108 mm x 31 mm ( st andar d t er m inals)
146 mm x 108 mm x 31 mm ( separ able ter m inals)
0.3 kg
Directive 89/336/EEC EN 50081-1, EN 50082-1
Directive 73/23/EEC EN 60730
Technical Bulletin—TC-9102 27
Factory-Set
Paramet ers
Table 3: Factory-Set Parameters
Comfort Set Point Heating20°C+/-3 K Remote Set Point. See Note 2.
-1 K12-28°C Remote Set Point
Comfort Set Point Cooling22°C+/-3 K Remote Set Point. See Note 2.
+1 K12-28°C Remote Set Point
Prop. Band Heating-2 K-1 K when RED jumper OUT. See Note 1.
Integral Time Heating4 minutesDisabled when BLUE jumper OUT. See Note 1.
Standby Bias Heating-2 K
Night Bias Heating-4 K
Prop. Band Cooling+2 K+1 K when RED jumper OUT. See Note 1.
Integral Time Cooling4 minut esDisabled when BLUE jumper OUT. See Note 1.
Standby Bias Cooling+2 K
Night Bias Cooling+4 K
Heating Valve Stroke (PAT)60 seconds+/- 1% Dead Band
Heating Valve Cycle (DAT)300 seconds5% minimum On/Off
Heating Stage 1 Load (2St)50 %5% differential
Cooling Valve Stroke (PAT)60 seconds+/- 1% Dead Band
Cooling Valve Cycle (DAT)300 seconds5% minimum O n/ O ff
Cooling Stage 1 Load (2St)50 %5% differential
Fan On/Off Differential1 K
Fan always On in ComfortNoYes = Fan On in zero energy band in Comfort.
Min. Fan Output (0-10 VDC)50 %
Low Limit Set Point12°C
Low Limit Differential2 K
Winter CompensationDisabledRequires O ut door Air Tem p via Bus when enabled.
Winter Set Point10°C
Winter Authority Slope-0. 1
Winter Authority Limit-3 K
Summer CompensationDisabledRequires Outdoor Air Temp via Bus when enabled.
Summer Se t Point24°C
Summer Authority Slope0.2
Summer Authority Limit5 K
Room Temp Filter Const.10 seconds
Remote S.P.Filter Const.60 seconds
Common Set Point0°CValid range = - 3 t o 28. See Note 2.
Unit Mount SensorNoYes = Hard wired temperature sensor is used and
TM-9180 is connected.
Note 1:Controllers are delivered from the factory with the RED
Note 2:When the Remote Set Point is +/-3 K, the Common Set Point
28 Technical Bulletin—TC-9102
jumper “IN” and the BL UE ju mper “OUT” unless otherwise
specified.
may be set to the desired mean room temperature (e.g. 21°C)
and the Comfort Set Point Heating and Comfort Set Point
Cooling set as biases of -1K and +1K, respectively.
Paramet ers for
Supervisory
System
Room Temperature°CAI1Read
Remote Set Point°C or KAI2Read
Working Set Point Heating°CWSP1Read
Working Set Point Cooling°CWSP2Rea d
Control Output Heating%OCM1Read
Control Output Cooling%OCM2*Read
Heating/Cooling ModeCool/HeatL1A*Read
Operating StatusComfort/Standby/ Night/ OffMODSRead
Alternate ModeOff/OnALTRead
Window ContactClosed/OpenWI NRead
Occupancy SensorOccupied/UnoccupiedOCCRead
Low Limit ModeOff/OnAFMRead
Winter Set Point CompensationKWACRead
Summer Set Point CompensationKSACRead
Requested Operating ModeComfort/Standby/Night/ OffMODCWrite
Set Outdoor Temperature°CXAI4Read/Write
Set Common Set Point°C or KPM6K1Read/Write
The following table lists the parameters which are available for
monitoring by Metasys supervisory systems. For details of configuration
procedures and override possibilities, refer to the technical documentation
of the system which is to be used.
Table 4: Supervisory System Parameters
Parameter Descri pt i onUnitsTag NameFunction
On/Off Fan Control:
Fan StatusOff/OnDO2Read
3-Speed Fan Control:
Fan Speed 1Off/OnDO5Read
Fan Speed 2Off/OnDO6Read
Fan Speed 3Off/OnDO7Read
Fan OverrideAuto/HoldFOVRead
Fan Speed Controller :
Control Output Fan%OCM3Read
*Note: For 0-10 VDC control signal outputs, OCM1 and OCM2 operate
in parallel and indicate the output level in Heating or Cooling.
Therefore, at the supervisory system, OCM1 should be monitored
as the “Heating/Cooling Control Output” and L1A can be
monitored to indicate whether the controller is in heating or
cooling mode. (Requires Metasys Release 9.0 or later.)
Technical Bulletin—TC-9102 29
Ordering
Codes
Ordering CodeHardwar e
TC-91a2-b220TC-91x2-x2202 x 0 to 10 VDC0 to 10 VDC Fan Control12 -28°C
TC-91a2-b225TC-91x2-x2202 x 0 to 10 VDC0 to 10 VDC Fan Control+/-3 K
TC-91a2-b440TC-91x2-x3302 x DAT0 to 10 VDC Fan Control12 -28°C
TC-91a2-b445TC-91x2-x3302 x DAT0 to 10 VDC Fan Control+/-3 K
TC-91a2-b550TC-91x2-x3302 x PAT0 to 10 VDC Fan Control12 -28°C
TC-91a2-b555TC-91x2-x3302 x PAT0 to 10 VDC Fan Control+/-3 K
TC-91a2-b660TC-91x2-x3302 x 2 Stage On/Off0 to 10 VDC Fan Control12 -28°C
TC-91a2-b655TC-91x2-x3302 x 2 Stage On/Off0 to 10 VDC Fan Control+/-3 K
TC-91a2-b221TC-91x2-x2212 x 0 to 10 VDCOn/Off Fan12-28°C
TC-91a2-b226TC-91x2-x2212 x 0 to 10 VDCOn/Off Fan+/-3 K
TC-91a2-b441TC-91x2-x3312 x DATOn/Off Fan12-28°C
TC-91a2-b446TC-91x2-x3312 x DATOn/Off Fan+/-3 K
TC-91a2-b551TC-91x2-x3312 x PATOn/ Off Fan12-28°C
TC-91a2-b556TC-91x2-x3312 x PATOn/ Off Fan+/-3 K
TC-91a2-b661TC-91x2-x3312 x 2 Stage On/OffOn/O ff Fan12-28°C
TC-91a2-b666TC-91x2-x3312 x 2 Stage On/OffOn/O ff Fan+/-3 K
TC-91a2-b222TC-91x2-x2222 x 0 to 10 VDC3-Speed Fan12-28°C
TC-91a2-b227TC-91x2-x2222 x 0 to 10 VDC3-Speed Fan+/-3 K
TC-91a2-b442TC-91x2-x3322 x DAT3-Speed Fan12-28°C
TC-91a2-b447TC-91x2-x3322 x DAT3-Speed Fan+/-3 K
TC-91a2-b552TC-91x2-x3322 x PAT3-Speed Fan12-28°C
TC-91a2-b557TC-91x2-x3322 x PAT3-Speed Fan+/-3 K
TC-91a2-b662TC-91x2-x3322 x 2 Stage On/Off3-Speed Fan12-28°C
TC-91a2-b667TC-91x2-x3322 x 2 Stage On/Off3-Speed Fan+/-3 K
Controller for remot e set point : a = 0, with int egr at ed set point : a = 1
Controller with standard term inals: b = 0, with separ able ter m inals: b = 1
Notes: 1. Ordering codes must be used in orders t o t he Lom agna f act ory.
2. The Hardware Configuration Code is shown in the EuroPRO Configuration Tool to indicate t he basic
hardware configuration of the cont r oller which is being commissioned. The sof t war e conf igurat ion of
the controller, as indicated by the O r der ing Code, m ay be changed in EuroPRO t o any ot her
software configuration with the sam e har dwar e conf igurat ion. For exam ple, TC-91a2- b442 could be
changed to TC-91a2-b552 because both have the same har dwar e conf iguration, TC-91x2-x332.
3. Modules with PWM control signal outputs have been discontinued. Contact your local Johnson
Controls office for details of r eplacement controllers.
Table 5: TC-9102 Controller Ordering Codes
OutputsSet Point
Configurati on
Code (used in
EuroPRO)
Range
30 Technical Bulletin—TC-9102
Table 6: Room Command Module Ordering Codes
Ordering CodeDescription
TM-9150-0000Occupancy ButtonNTC Sensorw/o S.P. dial
TM-9160-0000Occupancy ButtonNTC Sensor12-28°C
TM-9160-0005Occupancy ButtonNTC Sensor+/- 3 K
TM-9160-0002Occupancy ButtonNTC Sensor12-28°C3- Speed Fan Ov er r ide
TM-9160-0007Occupancy ButtonNTC Sensor+/- 3 K3-Speed Fan O v er r ide
TM-9170-0000Occupancy Buttonw/o Sensor12-28°C
TM-9170-0005Occupancy Buttonw/o Sensor+/- 3 K
TM-9170-0002Occupancy Buttonw/o Sensor12-28°C3-Speed Fan Override
TM-9170-0007Occupancy Buttonw/o Sensor+/- 3 K3-Speed Fan Override
TM-9180-0100LCD Displaywith View Mode and Clock Setting only
TM-9180-0200LCD Displaywith View Mode and Programming Mode
Note:All models above with off-white cover and grey base.
Add “-W” to code for white cover and white base, e. g. , TM-9150-0000-W.
Add “-K” to code for set point dial with serr at ed edge ( not for TM-9150 or TM- 9180),
e.g. TM-9160-0005- K, TM-9160-0005-WK.
Table 7: Software and Accessories Ordering Codes
Ordering CodeDescription
TE-9100-8501Unit Mount NTC Temperature Sensor (1.5-m cable)
TC-9100-TOOLCommissioning Software for DOS (3. 5" diskett e)
WS-EURPRO-0Configuration Tools Software for Windows®, New (3.5" diskettes)
WS-EURPRO-6Configuration Tools Software for Windows®, Upgrade (3.5" diskettes)