Johnson Controls METASYS TC-9102 Series, METASYS TM-9100 Series, METASYS TM-9150, METASYS TC-9102, METASYS TM-9160 Technical Bulletin

...
System 91 Manual
TC-9102
Technical Bulletin
Issue Date 0698
TC-9102 Fan Coil Unit Controller
Introduction Page 3
Model Types 4
Controller Functions 5
Output Types 10
Fan Output Types 12
Installation 15
Mounting 15
Wiring 16
Jumper and Switch Selections 22
Startup 23
Commissioning 23
Specifications & Technical Data 25
Factory-Set Parameters 26
Parameters for Supervisory System 27
Ordering Codes 28
© 1998 Johnson Controls, Inc.
Order No. MN-9100- 2117
1
2 Technical Bulletin—TC- 9102

Introduction

The TC-9102 series of microprocessor-based controllers is designed for the control of Fan Coil Units (FCUs) with heating and cooling, and a single-speed, 3-speed or var iable- speed fan. T h e contr oll er can regul ate water valves, one or 2-stage electric heating, or a cooling unit wher e the compressor has its own short cycle protection.
The comfort temperature set point of the controller may be adjusted via a TM-9100 Series Room Command Module, and the occupied and unoccupied control modes of operation temporarily changed. A window open sensing contact may be connected to switch the controller to the off mode, and a low temperature limit protection feature is available.
The controller is factory-configured to contr ol with default oper ating parameters so that no external setup devi ces ar e necessar y. However , a software package for a PC is available to ver i f y th e cor r ect oper ati on of the controller and to modify the configuration, if necessary.
Winter and summer compensation may be enabled when th e contr oll er receives outdoor air temperature data via the communications bus, and modes of operation may be set by time scheduling programs or control processes in the supervisory system.
2357 2664
Figure 1: TC-9102 Controller Figure 2: TM-9160 Room
Command Module
Technical Bulletin—TC-9102 3
2333
Figure 3: TM-9180 Room Command Module
Model Types
The TC-9102 Controller is available in several model types according to the type of outputs and the range of the integrated or remote set point input. Refer to Ordering Codes at the end of this bulletin for details.
4 Technical Bulletin—TC- 9102
Controller Functions
The controller can be connected to a Room Command Module, from which it receives the room temper atur e, the remote set point and other override signals. The TM-9180 intelligent Room Command Module provides these signals via a serial bus connection to the controller. The other Room Command Modules (TM-9150/9160/9170) provide the signals as individually connected physical inputs to the controller. In addition, an NTC temperature sensor is available for mounting within the FCU.
For installations without a Room Command Module, the controller is available with an integrated set point adjuster. Alternatively, the remote set point and fan override controls may be incorporated into a custom FCU control panel. Refer to the Specifications and Technical Data section of this bulletin for details of the components required.
Occupancy Sensor
Window Contact
Room Command Module
Room Temp.* Remote Setpoint
Occupancy Button Fan Override
(3-speed only)
Communications Bus (Supervisory Control, Outdoor Air Temp.)
Figure 4: Controller with Room Command Module
Room Temp. NTC Sensor
Controller
Occupancy Sensor
Window Contact
Output Heating
Output Cooling
Fan Control
tc2cwrcm
*
NTC sensor may be mounted in FCU.
Output Heating
Controller (Setpoint)
Fan Override (3-speed only)
tc2cwspa
Communications Bus (Supervisory Control, Outdoor Air Temp.)
Figure 5: Controller with Integrated Setpoint Adjuster
Technical Bulletin—TC-9102 5
Output Cooling
Fan Control
Standalone Mode
The controller operates in standalone mode when it is not connected to a supervisory system via the communications bus nor to a TM-9180 Room Command Module. In standalone mode the controller may operate in one of three control modes:
• COMFORT (occupied): control at comfort set point
• STANDBY (unoccupied): control at a standby level set point
• OFF (not in use): low limit control only
The control modes are set by the window contact and occupancy sensor inputs, and may be modified by the occupancy button on the Room Command Module as shown in Table 1.
Table 1: Standalone Modes
WINDOW CONTACT OCCUPANCY SENSOR CONTROL MODE ALTERNATE MODE
(OCCUPANCY BUTTON)
WINDOW OPEN NO ACTION OFF NO ACTION WINDOW CL OSED OCCUPIED COMFORT STANDBY
UNOCCUPIED STANDBY COM FORT
Supervisory Mode
When connected to a supervisory system via the communications bus or to a TM-9180 Room Command Module, the controller may operate in COMFORT, STANDBY or OFF control modes, and additionally in NIGHT mode:
NIGHT (scheduled unoccupied): control at a night level set point. The control modes are set by the supervisory system or TM-9180, and are
modified by the occupancy sensor input and occupancy button on the Room Command Module as shown in Table 2. The window contact input always switches the controller to OFF control mode, and a MANUAL mode is available from the supervisory system to inhibit the action of the occupancy sensor and occupancy button.
Table 2: Supervisory Modes
WINDOW CONTACT
OPEN ANY MODE NO ACTION OFF NO ACTION
CLOSED UNOCCUPIED STANDBY COMFORT (T)*
SUPERVISORY MODE
OFF OCCUPIED OFF OFF
NIGHT OCCUPIED NIGHT COMFORT (T)*
STANDBY OCCUPIED STANDBY COMFORT
COMFORT OCCUPIED COMFO RT STANDBY
OFF/MANUAL OFF NIGHT/MANUAL NO ACTION NIGHT NO ACTION STANDBY/MANUAL STANDBY COMFORT/MANUAL COMFORT
OCCUPANCY SENSOR
UNOCCUPIED OFF OFF
UNOCCUPIED NIGHT COMFORT (T)*
UNOCCUPIED STANDBY COMFORT
CONTROL MO DE ALTERNATE MODE
(OCCUPANCY BUTTON)
*(T) = Timed (Returns t o Cont r ol Mode af ter 1 hour.)
6 Technical Bulletin—TC- 9102
Controller Set Points
The set point in all control modes may be modified from the integrated set point adjuster or from the remote set point dial/control panel on the Room Command Module, according to the controller model type. The controller models with a remote set point of 12-28°C require that a Room Command Module or an external potentiometer is connected to give the set point. Controllers with a remote set point of +/-3 K have internal factory set points of 20°C for heating and 22°C for cooling.
The set point is decreased or increased in the STANDBY control mode by the factory-set “Standby Bias Heating” and “Standby Bias Cooling” values to reduce the heating or cooling energy required when the room is temporarily unoccupied.
When a supervisory system is connected, the set point can be further decreased or increased in the NI GHT control mode to fur ther r educe energy requirements during scheduled unoccupied periods such as nights, weekends and holidays.
In the controller there are two “comfort” set points (Comfort Set Point Heating and Comfort Set Point Cooling), and the difference between these two values determines th e zer o ener gy band wher e neit her heati ng nor cooling is required. The controller calculates two working set points (WSP Heating and WSP Cooling), which are the sum of the comfort set point values, the “Remote Set Point” value coming from the integrated set point adjuster or the Room Command Module, and the “Common Set Point” value. In the supervisory mode an adjustment may be made to the working set points either by changing the “Comfort Set Points,” or by changing the value in the “Common Set Point” parameter of the controller which enables the supervisory system operator to adjust the setpoints for heating and cooling at the same time without affecting the zero energy band. In summary:
Working Set Point (Heating) = Comfort Set Point (Heating) (Supervisory System)
+ Remote Set Point (integrated adjuster or Command Module dial) + Common Set Point (Supervisory System) + STANDBY or NIGHT Bias Heating (if mode is active)
Working Set Point (Cooling) = Comfort Set Point (Cooling) (Supervisory System)
+ Remote Set Point (integrated adjuster or Command Module dial) + Common Set Point (Supervisory System) + STANDBY or NIGHT Bias Cooling (if mode is active)
When the room temperature is below the working set point for heating, the heating output increases according to the proportional band and integral time parameters set for the heating control loop. When the room temperature is above the working set point for cooling, the cooling output increases according to the proportional band and integral time parameters set for the cooling control loop. Heating and cooling control is illustrated in figures 8 and 9.
Technical Bulletin—TC-9102 7
Alternate Mode
When pressed for about one second, the occupancy button on the Room Command Module changes the mode of operation of the controller to the “Alternate Mode” or back to the nor m al “Cont r ol Mode” as shown i n Table 2. The “COMFORT ( T)” alternate mode is active onl y f or a per iod of one hour, after which the controller r evert s to the normal control mode.
Fan Control
The controllers with on/off fan control switch the fan on when the room temperature is below the working set point for heating and above the working set point for cooling, and switch the fan off when the room temperature has entered th e zer o ener gy band by th e value set f or t he f an differential. The fan can optionally be set to continue running in the zero energy band in the COMFORT (occupied) mode, using the software commissioning tool.
In controllers with 3-speed fan control outputs, the fan stages are switched in sequence as the room temper at ur e decr eases or incr eases, and Speed 1 remains on in the zero energy band.
In controllers with a 0 to 10 VDC output for a fan speed controller, the output increases as the room t emper at ur e f all s below th e wor king set point for heating or rises above the working set point for cooling, and maintains a minimum output (set by default at 50%) when the room temperature has entered the zero ener gy band.
For all controllers, in OFF mode the fan is switched off and the heating and cooling outputs are set to the fully closed or off level. Fan control sequences are shown in figures 10, 11 and 12.
3-Speed Fan Override
The speed of a 3-speed fan may be set manually from the Room Command Module when the controller is in COMFORT (occupied) mode. In the “AUTO” position the speed is set by the controller according to the room temperature. In the manual “OFF- 1- 2- 3” positions the fan runs at the selected speed. T h e f an over r ide i s not acti ve in STANDBY, NIGHT or OFF modes.
In controller models with 2-stage on/off heating and cooling outputs, all outputs are switched off when the fan speed is set to “OFF” to protect electrical heating and cooling devices that require a minimum air flow for normal operation. This feature can be enabled for other types of outputs, if required, using the software commissioning tool. Refer to Commissioning later in this document.
Low Limit Mode
The low limit mode is active when the room temperature falls below the low limit set point. The fan is switched on at full speed and the heating output is set to the maximum level until the room temperature rises by the low limit differential value.
8 Technical Bulletin—TC- 9102
Winter/Summer Compensation
Setpoint
Compensation
(K)
When the controller is connected to a super visor y system , t he wint er and/or summer compensation modes may be enabled. The supervisory system must be programmed to set the outdoor air temperature via the communications bus on a periodic basis. After a power interruption the winter and summer compensation modes are temporarily disabled until a new outdoor air temperature value is received. When the outdoor temperature falls below the winter set point, the working set point of the controller will be raised or lowered in accordance with the winter authority slope. When the outdoor temperature rises above the summer set point the working set point of the controller will be raised in accordance with the summer authority slope. The maximum amount of compensation is limited by the Winter Authority Limit and the Summer Authority Limit.
The effect of the wint er and summer com pensati on on the cont ro ller set point is shown below.
-1
-2
-3
-4
-5
5 4
3
2 1
Winter Authority Slope
(+0,1)
0
-20-30
-10
0
Summer Authority Limit
(+5 K)
10 20
30
Summer Authority
Slope (+0,2)
Outdoor Air
Temperature
40 50
(°C)
Winter Authority
Slope (-0,1)
Winter Authority
Limit (-3 K))
Winter
Setpoint
(10°C)
Summer Setpoint
(24°C)
tc2winsu.drw
Figure 6: Winter/Summer Compensation
Technical Bulletin—TC-9102 9
Auto-dial Feature
When the controller is connected to a remo te N2 Bus and super vised by a Metasys N2 Dialer (NU-NDM101-0) which is linked to a Metasys network by a telephone line, the following alarm conditions in the controller will initiate the automatic dial feature:
• Window Open
• Low Limit mode
• High or low alarm limit violation of the room temperature when alarm
limits have been set by the supervisory system.
When any one of these alarm conditions occurs, the N2 Dialer will detect the alarm and connect the remo te N2 Bus t o th e Metasys net wor k. When the telephone line connection is established the controller alarm status will automatically be reset and the controller is then ready to report further alarm condit ions as t hey occur . R efer to the Technical Bulletin of
the NU-NDM101-0 for further information.
Output Types
0 - 10 VDC
DAT - Duration Adjust Type
The heating and cooling outputs are one of the following types, depending on the controller model code:
The output is an analog voltage between 0 and 10 VDC in direct proportion to the controller output from 0 to 100%.
The DAT output is a triac which is switched on for a duration within the set heating or cooling valve cycle time in direct proportion to the controller output from 0 to 100%. To avoid unnecessary switching of the valve actuator when the output is between 0 and 5% the triac remains off, and when the output is between 95 and 100% the triac remains on. The default cycle time is 300 seconds.
ON OFF
50% O utput
DAT Cycle Time
30% Output
DAT Cycle Time
Figure 7: DAT Output
10 Technical Bulletin—TC-9102
(°C)
g
PAT - Position Adjust Type
The PAT output is a pair of triacs which are switched on to open and close an incrementally driven heating or cooling valve. The duration of switching is directly proportional to the change in the controller output and related to the full stroke time of the valve such that a 100% change will completely open or close the valve. At the 0% or 100% position the duration of switching is increased to ensure that the valve is completely at its end position and the appropriate triac is switched on for the full stroke time every two hours to ensure that the valve remains at its end position. To prevent unnecessary wear on the actuator, the triac output will only be switched when the output change exceeds 1% in the same dir ection as t he previous change or 2% if the direction of change is reversed. T he def ault full stroke time is 60 seconds.
100
Heating
Output (%)
0
5
2-Stage On/Off
Cooling
Comfort
Standby
Night
Comfort
Night
Standby
Low Limit
Room
12 14 16 18 20 22 24 26
10 30
Temperature (°C)
tc2hcvdc
Figure 8: Heating/Cooling Control 0-10 VDC, DAT, PAT
The output is a pair of triacs which are switched on in sequence as the controller output increases. The first stage triac is switched as soon as the output is above 0% and the second stage triac is switched when the output is equal to the set load rating for the first stage which is defaulted to 50%. The switching differential is fixed at 5%. When this type of output is used with 3-speed fan control, the output will be switched off whenever the fan speed is manually overridden to the “OFF” position on the Room Control Module. The control diagram is shown below.
O utput (% )
100
Heating
222 222
Low Limit
0
5
12 14 16 18 20 22 24 26
10
1
1
Night
1
Comfort
Stan dby
C oo lin
111
Comfort
Night
Standby
Room Tem perature
30
Figure 9: Heating/Cooling Control - 2-Stage On/Off
Technical Bulletin—TC-9102 11
Loading...
+ 23 hidden pages