The ZT unit measures 6.88 x 7.31 x 1.52 inch (175 x 186 x 39 mm), and
weighs 1.25 lb (0.57 kg). A coiled, 6-pin telephone-type cord is included.
The cord is 17 inches long and stretches to 5 feet. The ZT contains a
5-year lithium battery, factory installed.
The Wall Mount Base with ZT measures 6.94 x 7.44 x 2.00
(176 x189 x 51 mm).
The Utility Mount Base with ZT measures 6.94 x 7.44 x 6.00
(176 x 189 x 152 mm) when mounted on the ENC100.
Installation of the Zone Terminal must meet the following standards:
●Ambient operating conditions: 32 to 122°F (0 to 50°C)
●10 to 90% non-condensing relative humidity
●86°F (30°C) maximum dew point
Notes:Do not mount the Zone Terminal on a vibrating surface.
The atmosphere must be free of corrosive chemical vapors that
may damage electronic equipment.
●Use mild soap and water with a soft cloth to wipe surfaces of the ZT
clean.
●Do not immerse the ZT unit in water.
●Wipe clean with pure isopropyl alcohol, if surface becomes
Before you mount the ZT or connect it to a controller, the clear plastic
insert that describes the displayed values must be in place.
1.To open the ZT, lay the ZT flat and press the white tab on the top of
the ZT while pulling the front cover towards you.
2.Align the insert to the lower left front of the ZT.
3.Press the pieces back together.
View
from
here.
Figure 1: Template Installation
Connecting the
Wiring
Prior to final connection, the ZT must be downloaded using the ZT PRO
software tool which is part of the HVAC PRO Rev. 3.0 or later. Refer to
the HVAC PRO for Windows User’s Manual, Zone Terminal section.
If the ZT is connected 50 feet or less from the controller, install 24 AWG
(6-conductor) telephone cable between the controller and the ZT.
If the ZT is connected up to 500 feet from the controller, install 18 AWG
wire. The ZT requires 24 VAC, Common, and Zone Bus. The Zone Bus
and Common should be twisted pair.
The ZT can be connected directly to the:
●Air Handling Unit (AHU)
●Function Module Kit (FMK)
●Relay Kit (RLY) through a CBLCON-0
●Actuator (M100C)
●Zone Sensor (TE-6400)
●Humidity Sensor (HE-6400)
Figure 2 shows you where to locate the telephone-style plugs in these
components.
2 Zone Terminal Installation Sheet
CBLCON-0
AHU103
Controller
FMK 102
Remote
RLY100/50
M100C
TE-6400
Figure 2: Connecting the Zone Terminal
Zone Terminal Installation Sheet 3
conect2
Other remote connections include permanently connecting to a UNT or
12345678
1 2 3 4 5 6
BINAR Y IN
ANALOG IN PUTS
BINAR Y OUTPU TS
BINARY INPU T
AN ALOG INP UTS
1 2 3 4 5 6
1 2 3 4
ANAL OG INPUTS
COMMON
TO
ZONE
STAT
BIN AR Y OU TPU T
1 2 3 4 5 6
24 V AC
1 2 3 4 5 6
0-10V DC
ANA LOG
OUTP UT
CO NCT2
VAV using the CBLCON-0 and TE-6400 Zone Sensor (Figure 3).
+15 VDC
Connect
STAT here.
2 4
V A C
C O M
Z O N E
B U S
Connect VAV/UNT
here.
8
8
6
6
6
Connect ZT here.
Green LED
Red LED
+15 VDC
24 VA C
24 V AC
TR AC S
CO M MO N
COM MO N
COM MO N
Switch must
be in
normal position.
4 Zone Terminal Installation Sheet
Figure 3: Connecting Remote ZT to UNT/VAV with
CBLCON-0 and Zone Sensor
The Zone Terminal can be connected directly to a VAV/UNT through a
!
Zone Sensor without the use of the CBLCON-0 (Figure 4). This is a
portable application.
Zone Terminal
VAV/UNT
AS-UNT101-0
+15VDC
ANALOG INPUTS
BINARY IN
1 2 3 4 5 6 1 2 3 4
BINARY COM
ANALOG INPUTS
COMMON
BINARY INANALOG INPUTSBINARY OUTPU TS ANA OUT
BINARY OUTPUT
COM
1 2 3 4 5 6 1 2
PWR
IN
24V
24VAC TO LOADS
AC
TE-6400
CONCT3J
Figure 4: Remote Connect ZT to VAV/UNT through the
Zone Sensor
OFF
0-10VDC
ANALOG
OUTPUT
ANALOG
OUTPUT
COMMON
CAUTION: The ZT must be plugged into a 6-pin telephone-type
jack. Plugging the ZT into an 8-pin jack destroys the
8-pin receptacle and prevents the ZT from powering
up.
Zone Terminal Installation Sheet 5
KNOCKOUT
Physical
and Bases
Installation
Installation of
Wall Mountings
For optimum viewing, mount the top of the ZT 65 inches from the floor.
Enclosure Kit
and Base
Before attaching the Enclosure Kit (ENC100-0) to the wall, remove the
top or bottom rectangular knockouts with a needle-nose pliers, depending
on the end through which the wires will run.
Knock wire
passage out
on top or
bottom.
Figure 5: Remove Knockouts
6 Zone Terminal Installation Sheet
Attach the Enclosure Kit (ENC100-0) to a flat surface or wall for direct
connection of the ZT to an application specific controller. Pull wire
through before attaching standoffs and screws for the plastic base.
MT&BASE
Figure 6: Attaching the Enclosure Kit and Utility Mounting Base
Zone Terminal Installation Sheet 7
Attach the base, pulling the telephone jack type cord through the opening
as shown below. Plug the cord into the back of the ZT, and snap the ZT
into position.
ENCMTBAS
Figure 7: Connecting and Mounting the ZT
8 Zone Terminal Installation Sheet
WALMTZT
Wall Mount
Installation
For office or other types of remote connections, attach the Wall Mount to
a flat surface or wall. Use three screws and plastic anchors (not
provided). For easy reading, mount the ZT at least 65 inches from the
floor to the top of the ZT.
1.Position the Zone Terminal Wall Mounting Base on the wall.
2.Mark the three mounting hole locations and remove the base.
3.Drill three holes for No. 6 anchors (not included) and install the
anchors for mounting the base.
4.Thread the ZTU cable through the access hole in the back of the base.
5.Secure the Wall Mounting Base to the wall with three No. 6 screws.
6.Plug the ZTU cable in the back of the ZTU, and snap the ZTU into
the base.
Figure 8: Attaching ZT and Wall Mount
Zone Terminal Installation Sheet 9
ztcontr
Mounting the ZTU
UPM
Externally on the
Using the wall mounting base, follow the instructions below to mount the
Zone Terminal on a UPM.
ME TA S Y S
N2
Zone
AHU103
Zone
Terminal
Mounted on
the Outside
Bus
AL A RM
Figure 9: Mounting the Zone Terminal on a UPM
1.Position the Zone Terminal Wall Mounting Base flush on the cover at
eye level (approximately 65 inches from the floor to top of ZT).
2.Mark mounting holes.
3.Mark cable hole.
4.Drill three size 3/32 inch pilot holes for mounting the base.
5.Drill 5/8 to 1 inch hole for cable.
6.Mount the base to the UPM cover using three No. 6 thread forming or
sheet metal screws. Use a No. 6 x 3/4 inch screw for the top hole and
two No. 6 x 1/2 inch screws for the bottom screws.
10 Zone Terminal Installation Sheet
Mounting the ZT
UPM
Behind a Window
Enclosure in the
The Panel Unit in Poteau, Oklahoma has a bracket available for mounting
the ZT behind a window that allows control equipment to be mounted
behind the ZT, thereby maximizing the use of the UPM. Contact the
Panel Unit for more information.
Johnson Controls Panel Unit wires and configures units, complete with
accessories, to your specifications. The ZTU internal mounting bracket is
also available. Contact:
Panel Unit -- Poteau
3100 North Broadway
P.O. Box 1088
Poteau, OK 74953
(918) 647-2195
FAX: (918) 647-4895 (Customer Service)
Bottom View of UPM
ZT
UNT
ALA R M
ztin2
Figure 10: Bracket for Mounting the ZTU Internally in the UPM
Zone Terminal Installation Sheet 11
Removing a
Mounted ZT
Milwaukee, WI 53201Printed in U.S.A
Use a large flat-head screwdriver and insert it in the bottom where the ZT
and mounting base come together. Gently pry the ZT out of the mounting
base. As you push the screwdriver in, the ZT slides up and then out.
REMOVAL
Figure 11: Removing Mounted ZT
Controls Group
507 E. Michigan Street
P.O. Box 423Issue Date 0495
12 Zone Terminal Installation Sheet
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.