Johnson Controls Metasys MS-IOM4711 Series Installation Instructions Manual

IOM47 Input/Output Module Installation Instructions
Part No. 24-10144-92, Rev. LMS-IOM4711-x
Issued November 2017
Refer to the QuickLIT website for the most up-to-date version of this document.

Application

The IOM47 field controller is part of the Metasys®system
Field Equipment Controller family. Input/Output Module (IOM) controller expand the number of points connected to a Network Automation Engine (NAE), Network Control Engine (NCE), Field Equipment Controller (FEC), or Advanced Application Field Equipment Controller (FAC) to monitor and control a wide variety of HVAC equipment.
IOM controllers operate on an RS-485 BACnet®
Master-Slave/Token-Passing (MS/TP) Bus as BACnet Application Specific Controllers (B-ASCs) and integrate
into Johnson Controls®and third-party BACnet systems.
Note: At CCT Release 10.1 and later, a new capability
was introduced allowing VMAs, FECs, and FACs to communicate by using either the BACnet or the N2 field bus networking protocol. The I/O can be connected through the SA bus to a host controller that is using either the BACnet or the N2 protocol. Only the BACnet protocol is supported when the I/O is connected directly to the trunk using the FC bus.
Important: In Metasys system smoke control
applications, use only the MS-IOM4711-0U and MS-IOU4710-0U at Metasys Release
8.1 that are UL 864 UUKL/UUKLC 10th Edition Smoke Control Listed. For Metasys system smoke control applications, you must refer to the Metasys System UL 864
UUKL Tenth Edition Smoke Control System Technical Bulletin (LIT-12012487) for
detailed requirements and procedures for installing, commissioning, and operating UL 864 UUKL/UUKLC Listed Metasys system devices. The UL 864 UUKL/UUKLC listing for Smoke Control Equipment is voided if (1) you do not use the required software tools at the required versions; or (2) you do not meet the requirements or do not follow the procedures as documented in the
Metasys System UL 864 UUKL Tenth Edition Smoke Control System Technical Bulletin (LIT-12012487).

North American Emissions Compliance

Canada

This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations. Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.

United States

This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area may cause harmful interference, in which case the users will be required to correct the interference at their own expense.

Installation

Observe these guidelines when installing a controller:
Transport the controller in the original container to minimize vibration and shock damage.
Verify that all parts shipped with the controller.
Do not drop the controller or subject it to physical shock.

Parts Included

one controller with removable terminal blocks (Power and SA/FC bus are removable)
one installation instructions sheet
1IOM47 Input/Output Module Installation Instructions

Materials and Special Tools Needed

three fasteners appropriate for the mounting surface (M4 screws or #8 screws)
one 20 cm (8 in.) or longer piece of 35 mm DIN rail and appropriate hardware for DIN rail mount (only)
small straight-blade screwdriver for securing wires in the terminal blocks

Mounting

Observe these guidelines when mounting a controller:
Ensure the mounting surface can support the controller, DIN rail, and any user-supplied enclosure.
Mount the controller horizontally on 35 mm DIN rail whenever possible.
Mount the controller in the proper mounting position (Figure 1).
Mount the controller on a hard, even surface whenever possible in wall-mount applications.
Use shims or washers to mount the controller securely and evenly on the mounting surface.
Mount the controller in an area free of corrosive vapors and observe the Ambient Conditions requirements in Table 10.
Provide for sufficient space around the controller for cable and wire connections for easy cover removal and good ventilation through the controller (50 mm [2 in.] minimum on the top, bottom, and front of the controller).
Do not mount the controller on surfaces prone to vibration, such as duct work.
Do not mount the controller in areas where electromagnetic emissions from other devices or wiring can interfere with controller communication.
Figure 1: Controller Mounting Positions

DIN Rail Mount Applications

Mounting the controller horizontal on 35 mm DIN rail is the preferred mounting method.
To mount an IOM47 controller on 35 mm DIN rail:
1. Securely mount a 20 cm (8 in.) or longer section of 35 mm DIN rail horizontal and centered in the desired space so that the controller mounts in the horizontal position shown in Figure 1.
2. Pull the two bottom mounting clips outward from the controller to the extended position (Figure 2).
3. Hang the controller on the DIN rail by the hooks at the top of the (DIN rail) channel on the back of the controller (Figure 2), and position the controller snugly against the DIN rail.
4. Push the bottom mounting clips inward (up) to secure the controller on the DIN rail.
To remove the controller from the DIN rail, pull the bottom mounting clips out to the extended position and carefully lift the controller off the DIN rail.
Observe these additional guidelines when mounting an IOM47 controller in a panel or enclosure:
Mount the controller so that the enclosure walls do not obstruct cover removal or ventilation through the controller.
Mount the controller so that the power transformer and other devices do not radiate excessive heat to the controller.
Do not install the controller in an airtight enclosure.

Wall Mount Applications

To mount a controller directly on a wall or other flat vertical surface:
1. Pull the two bottom mounting clips outward and ensure they are locked in the extended position as shown in Figure 2.
2. Mark the mounting hole locations on the wall using the dimensions in Figure 2 and one of the mount positions shown in Figure 1. Or, hold the controller up to the wall or surface in a proper mount position and mark the hole locations through the mounting clips.
3. Drill holes in the wall or surface at the marked locations, and insert appropriate wall anchors in the holes (if necessary).
2IOM47 Input/Output Module Installation Instructions
4. Hold the controller in place, and insert the screws through the mounting clips and into the holes (or anchors). Carefully tighten all of the screws.
Important: Do not overtighten the mounting screws.
Overtightening the screws may damage the mounting clips.
Figure 3: IOM47 Physical Features
Figure 2: Back of Controller Showing Extended
Mounting Clips, DIN Rail Channel, and Mounting
Dimensions, mm (in.)
Table 1: IOM47 Physical Features Callouts and Descriptions
Physical Feature DescriptionCallout
1
2
4
Binary Output (BO) Source Power Selection Jumper Pin Blocks, 3 – BO Jumper Pin Blocks. (See Table 3.)
Device Address DIP Switch Block. (See Setting the Device Addresses.)
Mounting Clip (One of Three)3
Configurable Output (CO) Terminal Blocks, 4 – Configurable Outputs. (See Table 3.)
3IOM47 Input/Output Module Installation Instructions
Table 1: IOM47 Physical Features Callouts and Descriptions
Physical Feature DescriptionCallout
5
6
7
8
9
10
11
12
13
14
Analog Output (AO) Terminal Block, 2 – Analog Outputs. (See Table 3.)
24 VAC, Class 2 Supply Power Terminal Block. (See Table 5.)
Cover Lift Tab (One of Two). (See Removing the Controller Cover.)
Sensor/Actuator (SA) Bus or Field Controller (FC) Bus Terminal Block. (See Table 5.)
Binary Input (BI) Terminal Block, 2 – Binary Inputs. (See Table 3.)
Universal Input (UI) Terminal Blocks, 6 – Universal Inputs. (See Table 3.)
End-of-Line (EOL) Switch. (See Setting the End-of-Line (EOL) Switch)
Note: The EOL Switch is located under the controller cover. You must remove the cover to change the EOL switch position.
LED Status Indicators. (See Table 8.)
Sensor Actuator (SA) Bus / Field Controller (FC) Bus Port (RJ-12 6-pin Modular Jack). (See SA/FC Bus Port.)
BO Terminal Block, 3 – Binary Outputs. (See Table 3.)

Wiring

Observe the following guidelines when wiring a controller:
Risk of Electric Shock: Disconnect the power supply before making electrical connections to avoid electric shock.
Mise En Garde: Risque de décharge électrique:
Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de décharge électrique.
Risk of Property Damage: Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment.
Mise En Garde: Risque de dégâts matériels: Ne pas mettre le système sous tension avant d'avoir vérifié tous les raccords de câblage. Des fils formant un court-circuit ou connectés de façon incorrecte risquent d'endommager irrémédiablement l'équipement.
Important: Do not exceed the controller electrical
ratings. Exceeding controller electrical ratings can result in permanent damage to the controller and void any warranty.
Important: Use copper conductors only. Make all wiring
in accordance with local, national, and regional regulations.
Important: Electrostatic discharge can damage
controller components. Use proper electrostatic discharge precautions during installation, setup, and servicing to avoid damaging the controller.
For detailed information on configuring and wiring an MS/TP Bus, FC bus, and SA bus, refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034).

Terminal Blocks and Bus Ports

See Figure 3 for terminal block and bus port locations on the controller. Observe the following guidelines when wiring a controller.

Input and Output Terminal Blocks

All of the input terminal blocks are mounted on the bottom of the controller and the output terminal blocks are mounted on the top of the controller. See Table 3 for more information about I/O terminal functions, requirements, and ratings.

SA/FC Bus Terminal Block

An IOM can be connected to a Sensor/Actuator (SA) bus or a Field Controller (FC) bus, but not to both buses simultaneously. The SA/FC bus terminal block is a removable, 4-terminal plug that fits into a board-mounted jack.
When connecting the IOM to an FC bus, wire the bus terminal block plugs on the controller, and the other controllers in a daisy-chain configuration using 3-wire twisted, shielded cable as shown in Figure 4. See Table
5 for more information.
4IOM47 Input/Output Module Installation Instructions
Figure 4: FC Bus Terminal Block Wiring
When connecting the IOM to an SA bus, wire the bus terminal block plugs on the controller and other SA bus devices in a daisy-chain configuration using 4-wire twisted, shielded cable as shown in Figure 5. See Table
3 for more information.
Figure 5: SA Bus Terminal Block Wiring

SA/FC Bus Port

The SA/FC bus port on the front of the controller is an RJ-12, 6-position modular jack that provides a connection
for devices on the SA bus, a Bluetooth® Wireless
Commissioning Converter, or a ZFR/ZFR Pro Wireless Router (depending on which bus the IOM is operating on).
The SA/FC bus port is connected internally to the SA/FC bus terminal block. See Table 5 for more information. The SA/FC bus port pin assignment is shown in Figure
6.
Figure 6: Pin Number Assignments for Sensor, SA
Bus and FC Bus Ports on Controllers
Note: The SA PWR/SHLD terminal does not supply 15
VDC. The SA PWR/SHLD terminal is isolated and can be used to connect (daisy chain) the 15 VDC power leads on the SA bus (Figure 5) or the cable shields on the FC bus (Figure 4). The SA bus supervisor supplies 15 VDC to devices on the SA bus requiring power.

Supply Power Terminal Block

The 24 VAC supply power terminal block is a gray, removable, 3-terminal plug that fits into a board-mounted jack on the top right of the controller.
Wire the 24 VAC supply power wires from the transformer to the HOT and COM terminals on the terminal plug as shown in Figure 7. The middle terminal on the supply power terminal block is not used. See Table 5 for more information about the supply terminal block.
5IOM47 Input/Output Module Installation Instructions
Figure 7: 24 VAC Supply Power Terminal Block Wiring
Note: The supply power wire colors may be different on
transformers from other manufacturers. Refer to the transformer manufacturer’s instructions and the project installation drawings for wiring details.
Important: Connect 24 VAC supply power to the
controller and all other network devices so that transformer phasing is uniform across the network devices. Powering network devices with uniform 24 VAC supply power phasing reduces noise, interference, and ground loop problems. The controller does not require an earth ground connection.

Wireless Network Applications

The controller can also be installed in a wireless application using a ZFR/ZFR Pro Wireless Field Bus Router.
Important: Wireless operation is not approved for
smoke control applications. Refer to the
Metasys System UL 864 UUKL Tenth Edition Smoke Control System Technical Bulletin (LIT-12012487) for detailed
requirements and procedures for installing, commissioning, and operating UL 864 UUKL/UUKLC Listed Metasys system devices.
To configure a controller for use with the ZFR/ZFR Pro Series Wireless Field Bus system:
Note: IOMs can communicate wirelessly on the FC bus
only.
1. Connect the ZFR/ZFR Pro Wireless Field Bus Router to the FC bus port (RJ-12 modular jack) on the front of the controller.
2. Ensure that the controller's device address DIP switches are set to the correct device address. See
Setting the Device Addresses.
3. Set DIP switch 128 to ON, which enables wireless operation on the controller.
For more information on the ZFR Pro Wireless Field Bus system, refer to the WNC1800/ZFR182x Pro
Series Wireless Field Bus System Product Bulletin (LIT-12012320).
For more information on the ZFR 1800 Wireless Field Bus system, refer to the ZFR1800 Series Wireless Field Bus System Product Bulletin (LIT-12011336).
6IOM47 Input/Output Module Installation Instructions

Termination Details

A set of Johnson Controls® termination diagrams provides details for wiring inputs and outputs to the controllers.
See the figures in this section for the applicable termination diagrams.
Table 2: Termination Details
Type of Field Device
Input/Output
UITemperature Sensor
UIVoltage Input - External
Source
UIVoltage Input - Internal Source
Termination DiagramsType of
Source (Isolated)
(2-wire)
UIVoltage Input (Self-Powered)
UICurrent Input - External
UICurrent Input - Internal Source
7IOM47 Input/Output Module Installation Instructions
Table 2: Termination Details
Type of Field Device
(3 wire)
Source (in Loop)
Termination DiagramsType of
Input/Output
UICurrent Input - Internal Source
UICurrent Input - External
UIFeedback from EPP-1000
(External Source)
(Internal Source)
UI or BIDry Contact (Binary Input)
CO or AO0–10 VDC Output to Actuator
CO or AO0–10 VDC Output to Actuator
8IOM47 Input/Output Module Installation Instructions
Table 2: Termination Details
Type of Field Device
Termination DiagramsType of
Input/Output
CO or AO4–20 mA Output to Actuator
CO or AO4–20 mA Output to Actuator
AOVoltage (Analog Output)
Low, External Source)
Actuator (Switch Low, Externally Sourced)
High, Externally Sourced)
AOAnalog Output (Current)
CO or AO24 VAC Triac Output (Switch
CO or AOIncremental Control to
CO or AO24 VAC Triac Output (Switch
9IOM47 Input/Output Module Installation Instructions
Table 2: Termination Details
Type of Field Device
Actuator (Switch High, Externally Sourced)
Actuator (Switch Low, Externally Sourced)
Low, Externally Sourced)
Termination DiagramsType of
Input/Output
CO or AOIncremental Control to
BOIncremental Control to
BO24 VAC Binary Output (Switch
High, Externally Sourced)
Actuator (Switch High, Externally Sourced)
BO24 VAC Binary Output (Switch
BOIncremental Control to
10IOM47 Input/Output Module Installation Instructions
Table 2: Termination Details
Type of Field Device
(Fixed Address = 199)
Addressable
Termination DiagramsType of
Input/Output
SA BusNetwork Stat with Phone Jack
SA BusNetwork Stat with Terminals
SA BusNetwork Stat with Terminals
(Fixed Address = 199)

Terminal Wiring Guidelines, Functions, Ratings, and Requirements

Input and Output Wiring Guidelines

Table 3 provides information and guidelines about the
functions, ratings, and requirements for the controller input and output terminals; and references guidelines for determining proper wire sizes and cable lengths.
Note: Inputs/outputs with cables less than 30 m (100 ft)
typically do not require an offset in the software setup. Cable runs over 30 m (100 ft) may require an offset in the input/output software setup.
In addition to the wiring guidelines in Table 3, observe these guidelines when wiring controller inputs and outputs:
Run all low-voltage wiring and cables separate from high-voltage wiring.
All input and output cables, regardless of wire size or number of wires, should consist of stranded, insulated, and twisted copper wires.
Shielded cable is not required for input or output cables.
Shielded cable is recommended for input and output cables that are exposed to high electromagnetic or radio frequency noise.
11IOM47 Input/Output Module Installation Instructions
Table 3: IOM47 Terminal Blocks, Functions, Ratings, Requirements, and Cables
Terminal Block Label
(Inputs)
BINARY
(Inputs)
Label
+15 VUNIVERSAL
INn
ICOMn
INn
ICOMn
Function, Ratings, RequirementsTerminal
15 VDC Power Source for active (3-wire) input devices
connected to the Universal INn terminals.
Provides 100 mA total current
Analog Input - Voltage Mode (0–10 VDC)
10 VDC maximum input voltage
Internal 75k ohm Pull-down
Analog Input - Current Mode (4–20 mA)
Internal 100 ohm load impedance
Note: A current loop fail-safe jumper can be positioned to maintain a closed 4 to 20 mA current loop, even when the power to the controller is interrupted or off. See UI Current
Loop Jumpers.
Analog Input - Resistive Mode (0–600k ohm)
Internal 12 V. 15k ohm pull up
Qualified Sensors: 0-2k ohm potentiometer, RTD (1k Nickel
[Johnson Controls® sensor], 1k Platinum, and A99B Silicon
Temperature Sensor) Negative Temperature Coefficient (NTC) Sensor (10k Type L, 10k JCI Type II, 2.252k Type II)
Binary Input - Dry Contact Maintained Mode
1 second minimum pulse width
Internal 12 V. 15k ohm pull up
Universal Input Common for all Universal Input terminals
Note: All Universal ICOMn terminals share a common,
which is isolated from all other commons.
Binary Input - Dry Contact Maintained Mode
0.01 second minimum pulse width
Internal 18 V. 3k ohm pull up
Binary Input - Pulse Counter/Accumulator Mode
0.01 second minimum pulse width
(50 Hz at 50% duty cycle)
Internal 18 V. 3k ohm pull up
Binary Input Common for all Binary Input (IN) terminals
Note: All Binary ICOMn terminals share a common, which
is isolated from all other commons, except the Configurable Output (CO) common (OCOMn) when the CO is defined as an Analog Output.
Determine Wire Size and Maximum Cable Length
Same as (Universal) INn
Note: Use 3-wire cable for
devices that source power from the +15V terminal.
See Guideline A in Table 4.
See Guideline B in Table 4.
See Guideline A in Table 4.
See Guideline A in Table 4.
Same as (Universal) INn
See Guideline A in Table 4.
1
12IOM47 Input/Output Module Installation Instructions
Table 3: IOM47 Terminal Blocks, Functions, Ratings, Requirements, and Cables
Terminal Block Label
ANALOG
(Outputs)
BINARY
(Output)
Power Selection Jumper positioned to External (EXT) power.
BINARY
(Output)
Power Selection Jumper positioned to Internal (INT) power.
Label
OUTn
OCOMn
OUTn
OCOMn
OUTn
OCOMn
Function, Ratings, RequirementsTerminal
Analog Output - Voltage Mode (0–10 VDC)
10 VDC maximum output voltage
10 mA maximum output current
Required an external load of 1,000 ohm or more.
Note: The Analog Output (AO) operates in the Voltage Mode when connected to devices with impedances greater than 1,000 ohm. Devices that drop below 1,000 ohm may not operate as intended for Voltage Mode applications.
Analog Output - Current Mode (4–20 mA)
Requires and external load between 0 and 300 ohm.
Note: The Analog Output (AO) operates in the Current Mode when connected to devices with impedances less than 300 ohm. Devices that exceed below 300 ohm may not operate as intended for Current Mode applications.
Analog Output Signal Common for all Analog OUT terminals.
Note: All Analog Output Common terminals (OCOMn) share a common, which is isolated from all other commons.
Binary Output - 24 VAC Triac (External Power Source)
Connects OUTn to OCOMn when activated.
External Power Source Requirements:
30 VAC maximum output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
40 mA minimum load current
Binary Output Common (for OUTn terminal)
Note: Each Binary Output Common terminal (OCOMn) is
isolated from all other commons, including other Binary Output Common terminals.
Binary Output - 24 VAC Triac (Internal Power Source)
Sources internal 24 VAC power (24~ HOT).
Binary Output - 24 VAC Triac (Internal Power Source)
Connects OCOMn to 24~ when activated.
Internal Power Source:
30 VAC maximum output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
40 mA minimum load current
Determine Wire Size and Maximum Cable Length
See Guideline C in Table 4.
See Guideline C in Table 4.
See Guideline C in Table 4.
1
13IOM47 Input/Output Module Installation Instructions
Table 3: IOM47 Terminal Blocks, Functions, Ratings, Requirements, and Cables
Terminal Block Label
CONFIGURABLE
(Outputs)
Label
OUTn
OCOMn
Function, Ratings, RequirementsTerminal
Analog Output - Voltage Mode (0–10 VDC)
10 VDC maximum output voltage
10 mA maximum output current
Required an external load of 1,000 ohm or more.
Binary Output - 24 VAC Triac (External Power Source only)
Connects OUTn to OCOMn when activated.
External Power Source Requirements:
30 VAC maximum output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
40 mA minimum load current
Analog Output Signal Common All Configurable Outputs (COs) defined as Analog Outputs (AOs) share a common, which is isolated from all other commons except the Binary Input common.
Binary Output Signal Common All Configurable Outputs (COs) defined as Binary Outputs are isolated from all other commons, including other CO commons.
Determine Wire Size and Maximum Cable Length
See Guideline A in Table 4.
See Guideline C in Table 4.
Same as (Configurable) OUTn.
1
1
See Table 4 to determine wire size and cable lengths for cables.
14IOM47 Input/Output Module Installation Instructions

Cable and Wire Length Guidelines

Table 4 defines cable length guidelines for the various wire sizes that may be used for wiring low-voltage (<30 V)
input and outputs.
Table 4: Cable Length Guidelines for Recommended Wire Sizes for Low-Voltage (<30 V) Inputs and Outputs
Wire Size/Gauge and TypeGuideline
AssumptionsMaximum Cable
Length and Type
1.0 mm (18 AWG) stranded copperA
C
See Figure 8 to select wire size/gauge. Use stranded copper wire.
457 m (1,500 ft) twisted wire
297 m (975 ft) twisted wire0.8 mm (20 AWG) stranded copper
183 m (600 ft) twisted wire0.6 mm (22 AWG) stranded copper
107 m (350 ft) twisted wire0.5 mm (24 AWG) stranded copper
229 m (750 ft) twisted wire1.0 mm (18 AWG) stranded copperB
137 m (450 ft) twisted wire0.8 mm (20 AWG) stranded copper
91 m (300 ft) twisted wire0.6 mm (22 AWG) stranded copper
61 m (200 ft) twisted wire0.5 mm (24 AWG) stranded copper
See Figure 8 to determine cable length. Use twisted wire cable.
100 mV maximum voltage drop
Depending on cable and the connected input or output device, you may have to define an offset in the setup software for the input or output point.
100 mV maximum voltage drop
Depending on cable and the connected input or output device, you may have to define an offset in the setup software for the input or output point.
N/A

Maximum Cable Length versus Load Current

Use Figure 8 to estimate the maximum cable length relative to the wire size and the load current (in mA) when wiring inputs and outputs.
Note: Figure 8 applies to low-voltage (<30 V) inputs and outputs only.
Figure 8: Maximum Wire Length for Low-Voltage (<30V) Inputs and Outputs by Current and Wire Size
15IOM47 Input/Output Module Installation Instructions

SA/FC Bus and Supply Power Wiring Guidelines

Table 5 provides information about the functions, ratings,
and requirements for the communication bus and supply power terminals; and guidelines for wire sizes, cable types, and cable lengths when wiring the controller's communication buses and supply power.
In addition to the guidelines in Table 5, observe these guidelines when wiring an SA or FC bus and the 24 VAC supply power:
Run all low-voltage wiring and cables separate from high-voltage wiring.
All SA and FC bus cables, regardless of wire size, should be twisted, insulated, stranded copper wire.
Shielded cable is strongly recommended for all SA and FC bus cables.
Refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034) for detailed information regarding wire size and cable length requirements for the SA and FC buses.
Table 5: Communications Bus and Supply Power Terminal Blocks, Functions, Ratings, Requirements, and Cables
Terminal Block/Port Label
FC BUS
or
SA BUS
SA/FC BUS
(Port)
2
2
2
Labels
-
COM
SHLD
or
SAPWR
HOT24~
COM
Function, Electrical Ratings/RequirementsTerminal
FC or SA Bus Communications+
Signal Reference (Common) for FC or SA Bus communications
SHLD on FC Bus: Isolated terminal (optional shield drain connection
SAP WR on SA Bus: 15 VDC power lead connection
Note: The SA PWR terminal on an IOM controller does
not supply 15 VDC. The SA bus supervisor (FAC, FEC, or VMA) supplies 15 VDC to devices on the SA bus requiring power.
RJ-12 6-Position Modular Connector provides:
FC or SA Bus Communications
FC or SA Bus Signal Reference and 15 VDC Common
Commissioning Converter or ZFR/ZFR Pro Wireless Router
(Maximum total current draw for SA bus is 240 mA.)
24 VAC Power Supply - Hot
Supplies 20–30 VAC (Nominal 24 VAC)
24 VAC Power Supply - Common
(Isolated from all other Common terminals on controller.)
Recommended Cable Type
FC Bus: 0.6 mm (22 AWG) stranded, 3-wire twisted, shielded cable recommended.
SA Bus: 0.6 mm (22 AWG) stranded, 4-wire (2 twisted-pairs), shielded cable recommended.
Note: On the SA Bus, the + and - wire are one twisted pair, and the COM and SA PWR are the second twisted pair of wires.
Wireless Commissioning Converter retractable cable or 24 AWG 3-pair CAT 3 Cable <30.5 m (100 ft)
0.8 mm to 1.0 mm
(18 AWG) 2-wire
1
1
See Table 4 to determine wire size and cable lengths for cables.
2 The SA Bus and FC Bus wiring recommendations in this table are for MS/TP bus communications at 38,400 baud. For more
information, refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034).
16IOM47 Input/Output Module Installation Instructions

Setup and Adjustments

Setting the Device Addresses

Metasys field controllers are master devices on MS/TP (SA or FC) buses. Before operating controllers on a bus, you must set a valid and unique device address for each controller on the bus. You set a controller's device address by setting the positions of the switches on the DIP switch block at the top of the controller (Figure 3). Device addresses 4 through 127 are the valid addresses for these controllers.
The DIP switch block has eight switches numbered 128, 64, 32, 16, 8, 4, 2, and 1 (Figure 9). Switches 64 through 1 are device address switches. Switch 128 is a mode switch that enables a controller to operate on a ZFR/ZFR Pro Series Wireless Field Bus. Switch 128 must be set to off for all hard-wired SA and FC bus applications. Set switch 128 to ON for wireless FC bus applications only.
Figure 9: Device Address DIP Switch Block Set to
Address 21
Note: Controllers ship with switch 128 ON and the
remaining address switches off rendering the controllers wired slave devices, which do not operate on MS/TP buses, but will not interfere with bus operation. Set a valid and unique device address on the controller before applying power to the controller on the bus.
To set the device addresses on Metasys field controllers:
1. Set all of the switches on the address DIP switch block (128 through 1) to Off.
2. Set one or more of the seven address switches (64 though 1) to ON, so that the sum of the switch numbers set to ON equals the intended device address. See Table 6 for valid device addresses.
Set the highest number switch that is less than or equal to the intended device address to ON. Then continue setting lower numbered switches until the total equals the intended address. For example, if the intended device address is 21, set switch 16 to ON first, then set switch 4 ON, followed by switch 1 (16+4+1= 21). See Figure 9.
3. Set switch 128 to ON only for controllers on a ZFR/ZFR Pro Series Wireless Field Bus application. For all hard-wired SA and FC bus applications, ensure that switch 128 is set to Off.
Note: Do not connect a controller with switch 128
set to ON to an active (hard-wired) SA or FC bus. When a controller with switch 128 set to ON and a device address from 4 to 127 is connected to a wired field bus, the entire field bus is rendered inoperable until the controller is disconnected or switch 128 is set to Off.
Refer to the WNC1800/ZFR182x Pro Series Wireless
Field Bus System Technical Bulletin (LIT-12012356) or the ZFR1800 Series Wireless Field Bus System Technical Bulletin (LIT-12011295) for more
information on device addresses in wireless applications.
4. Set a unique and sequential device address for each of the controllers connected on the SA or FC bus starting with device address 4.
To ensure the best bus performance, set sequential device addresses with no gaps in the device address range (4, 5, 6, 7, 8, 9, and so on). The controllers do not need to be physically connected on the bus in their numerical device address order.
5. Write each controller's device address on the white label below the DIP switch block on the controller's cover.
Table 6 describes the FC bus and SA bus devices
addresses for Johnson Controls MS/TP communications bus applications.
Refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034) for more information on controller device addresses and how to set them on MS/TP buses.
Table 6: SA/FC Bus Device Address Descriptions
Use on DescriptionDevice
Address
0
(Switch 128 Off)
1 to 3
(Switch 128 Off)
4 to 127
(Switch 128 Off)
Reserved for FC Bus Supervisory Controller (not for use on controllers).
Reserved for peripheral devices (not for use on controllers).
Used for MS/TP master devices controllers) that are hardwired to an SA Bus or FC Bus.
17IOM47 Input/Output Module Installation Instructions
Table 6: SA/FC Bus Device Address Descriptions
Use on DescriptionDevice
Address
0 to 3
(Switch 128 ON)
4 to 127
(Switch 128 ON)
Reserved addresses for wired slave devices (not for use on controllers).
Note: Metasys field controllers ship with switch 128 ON and the remaining address switches off rendering the controllers wired slave devices, which do not operate on MS/TP buses.
Valid for MS/TP Master controllers on wireless
FC Buses only.
Note: Do not connect a controller with switch
128 ON to an active (hard-wired) SA or FC Bus. When a controller with switch 128 ON and a device address from 4 to 127 is connected to a wired field bus, the entire field bus is rendered inoperable until the controller is disconnected or switch 128 is set to Off.

Removing the Controller Cover

Important: Electrostatic discharge can damage
controller components. Use proper electrostatic discharge precautions during installation, setup, and servicing to avoid damaging the controller.
Figure 10: IOM47 with Cover Removed Showing EOL
Switch and Jumper Positions

Setting the End-of-Line (EOL) Switch

Each controller has an EOL switch, which, when set to ON, sets the controller as a terminating device on the bus. See Figure 10 for the EOL switch location. The default EOL switch position is Off.
Figure 11: End-of-Line Switch Positions
Important: Disconnect all power sources to the
controller before removing cover and changing the position of any jumper or the EOL switch on the controller. Failure to disconnect power before changing a jumper or EOL switch position can result in damage to the controller and void any warranties.
The controller cover is held in place by four plastic latches that extend from the base and snap into slots on the inside of the housing cover.
To remove the controller cover:
1. Place your fingernails under the two cover lift tabs (Figure 3) on the sides of the housing cover and gently pry the top of the cover away from the base to release the cover from the two upper latches.
2. Pivot the top of the cover further to release it from the lower two latches.
3. Replace the cover by placing it squarely over the base, and then gently and evenly push the cover on to the latches until they snap into the latched position.
To set the EOL switch on a controller:
1. Determine the physical location of the controller on the SA or FC bus.
2. Determine if the controller must be set as a terminating device on the bus.
Note: The EOL termination rules for SA buses and
FC buses are different. Refer to the MS/TP
Communications Bus Technical Bulletin (LIT-12011034) for detailed information
regarding EOL termination rules and EOL switch settings on SA and FC buses.
3. If the controller is a terminating device on the FC bus, set the EOL switch to ON. If the controller is not a terminating device on the bus, set the EOL switch to Off.
When a controller is connected to power with its EOL switch set to ON, the amber EOL LED on the controller cover is lit.
18IOM47 Input/Output Module Installation Instructions

Input/Output Jumper Settings

Binary Output (BO) Source Power Selection Jumpers

Risk of Electric Shock: Disconnect the supply power to the controller before attempting to adjust the Binary Output Source Power Selection Jumpers. Failure to disconnect the supply power may result in electric shock.
Mise En Garde: Risque de décharge électrique:
Débrancher l'alimentation de l'controller avant tout réglage du Binary Output Source Power Selection Jumpers. Le non-respect de cette précaution risque de provoquer une décharge électrique.
Important: Do not connect an external power source
to a binary output (BO) when the BO power source jumper is in the internal power (INT) position. Connecting external power to a BO that sources internal power can damage the controller and void any warranties.

UI Current Loop Jumpers

The current loop fail-safe jumpers are on the circuit board under the controller cover near the UI terminals (Figure
10). When a UI is defined (in the system software) as a
4-20 mA Analog Input and the UI’s current loop jumper is in the Disabled (default) position (Figure 13), the 4-20 mA current loop circuit opens whenever power to the controller is interrupted or off.
Figure 13: Current Loop Jumper Positions
Setting the current loop jumper to the Enabled position (Figure 13) connects an internal 100 ohm resistor across the UI terminals, which maintains the 4-20 mA current loop circuit even when power to the controller is interrupted or off.
The BO source power selection jumpers determine whether a BO provides internal power (sourced from the controller) to the output load (INT position) or requires an external power source (EXT position) for the output load. Figure 12 shows an example of a controller BOs and the associated power selection jumpers to the right of the BOs terminal block.
Figure 12: Example Binary Outputs and the
Associated Source Power Jumper Positions
Important: Current Loop jumpers must be in the
Disabled (default) position for all UIs that are not set up to operate as 4-20 mA analog inputs.
Table 7 identifies the current loop jumpers associated
with each UI on the IOM47 controller.
Table 7: IOM47 UI Inputs and Jumper Labels
Jumper Label on Circuit BoardUniversal Input
Label
J20IN1
J21IN2
J22IN3
J23IN4
J24IN5
J25IN6

Commissioning the Controllers

You commission controllers with the Controller Configuration Tool (CCT) software, either via a Bluetooth Wireless Commissioning Converter, a ZigBee wireless dongle, through MAP 4.2+/BACnet Router (Mobile Access Portal (MAP) Gateway at version 4.2 or above), or in
BACnet® router mode when connected to an NAE or
NCE. Refer to the Controller Tool Help (LIT-12011147) for detailed information on commissioning controllers.
19IOM47 Input/Output Module Installation Instructions

Troubleshooting the Controllers

Observe the Status LEDs on the front of the controller and see Table 8 to troubleshoot the controller.
Table 8: Status LEDs and Descriptions of LED States
LED ColorLED Label
State
On SteadyGreenPOWER
Off SteadyRedFAULT
Blink - 2 HzGreenSA/FC BUS
AmberEOL
Off (Except on terminating devices)
Description of LED StatesNormal LED
Off Steady = No Supply Power or the controller’s polyswitch/resettable fuse is open. Check Output wiring for short circuits and cycle power to controller.
On Steady = Power Connected
Off Steady = No Faults
On Steady = Device Fault; no application loaded; Main Code download required, if controller is in Boot mode, or a firmware mismatch exists between the controller and the ZFR1811 Wireless Field Bus Router.
Blink - 2 Hz = Download or Startup in progress, not ready for normal operation
Blink - 2 Hz = Data Transmission (normal communication)
Off Steady = No Data Transmission (N/A - auto baud not supported)
On Steady = Communication lost, waiting to join communication ring
On Steady = EOL switch in ON position
Off Steady = EOL switch in Off position

Repair Information

If a controller fails to operate within its specifications, replace the controller. For a replacement controller,
contact your Johnson Controls® representative.

Accessories

See Table 9 for controller accessories ordering information.
Table 9: Accessories Ordering Information
DescriptionProduct Code Number
Transformer, 120 VAC Primary to 24 VAC secondary, 20 VA, Wall PlugTP-2420
Y65T31-0
WNC1800/ZFR182x Pro Wireless field Bus System
ZFR1800 Series Wireless Field Bus System
Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, Foot Mount, 8 in. Primary Leads and Secondary Screw Terminals, Class 2
Note: Additional Y6x-x Series transformers are also available. Refer to the Series Y63, Y64, Y65, Y66, and Y69 Transformers Product Bulletin (LIT-125755) for more information.
Power transformer (Class 2, 24 VAC, 50 VA maximum output), no enclosureAS-XFR050-0
Replacement SA Bus Terminal Blocks, 4-Position, Brown, Bulk Pack of 10AP-TBK4SA-0
Replacement FC Bus Terminal Blocks, 4-Position, Blue, Bulk Pack of 10AP-TBK4FC-0
Replacement Power Terminal Blocks, 3-Position, Gray, Bulk Pack of 10AP-TBK3PW-0
This system is used for installations that support BACnet/IP but can also coexist with the ZFR1800 Series when installed under the same supervisor (i.e., network engine). Refer to the WNC1800/ZFR182x Pro Series Wireless Field Bus System Product Bulletin (LIT-12012320) for a list of available products.
This system is used for installations that only support BACnet MS/TP. Refer to the ZFR1800 Series Wireless Field Bus System Product Bulletin (LIT-12011336) for a list of available products.
For the MS-IOU4710-0U and MS-IOM4711-0U models that are UL 864 10th Edition UUKL/ORD-C100-13 UUKLC listed for smoke control, contact the Johnson Controls Repair Center in Louisville, Kentucky, at 1-502-671-7312.
20IOM47 Input/Output Module Installation Instructions
Table 9: Accessories Ordering Information
DescriptionProduct Code Number
NS Series Network Sensors
WRZ Series Wireless Room Sensors
Mobile Access Portal (MAP)Gateway
Refer to the NS Series Network Sensors Product Bulletin (LIT-12011574) for specific sensor model descriptions.
Refer to the WRZ Series Wireless Room Sensors Product Bulletin (LIT-12000653) for specific sensor model descriptions.
Refer to the Mobile Access Portal Gateway Catalog Page (LIT-1900869) to identify the appropriate product for your region.

Technical Specifications

Table 10: IOM4711-X Technical Specifications
Product Code Number
Supply Voltage
Power Consumption
Ambient Conditions
Addressing
Communications Bus
Input and Output Capabilities
Analog Input/Analog Output Resolution and Accuracy
Terminations
Mounting
MS-IOM4711-x Input/Output Module
MS-IOM4711-0U Input/Output Module
24 VAC (nominal, 20 VAC minimum/30 VAC maximum), 50/60 Hz, power supply Class 2 (North America), Safety Extra-Low Voltage (SELV) (Europe)
14 VA maximum for IOM4711 only
Note: VA rating does not include any power supplied to the peripheral devices connected to Binary Outputs (BOs) or Configurable Outputs (COs), which can consume up to 12 VA for each BO or CO; for a possible total consumption of an additional 84 VA (maximum).
Operating: 0° to 50°C (32° to 122°F); 10% to 90% RH noncondensing
Storage: -40° to 80°C (-40° to 176°F); 5% to 95% RH noncondensing
DIP switch set; valid controller device addresses 4–127 (Device addresses 0–3 and 128–255 are reserved and not valid addresses.)
BACnet® MS/TP, RS-485:
3-wire FC Bus between the supervisory controller and other controllers
4-wire SA bus between controller, network sensors and other sensor/actuator devices, includes a lead to source 15 VDC supply power (from controller) to bus devices.
H8SX/166xR Renesas® 32-bit microcontrollerProcessor
512 KB Flash Memory and 128 KB Random Access Memory (RAM)Memory
6 - Universal Inputs: Defined as 0–10 VDC, 4–20 mA, 0–600k ohm, or Binary Dry Contact
2 - Binary Inputs: Defined as Dry Contact Maintained or Pulse Counter/Accumulator Mode
3 - Binary Outputs: Defined as 24 VAC Triac (selectable internal or external source power)
4 - Configurable Outputs: Defined as 0–10 VDC or 24 VAC/DC Field-Effect Transistor (FET) BO
2 - Analog Outputs: Defined as 0–10 VDC or 4–20 mA
Input: 16-bit resolution
Output: 16-bit resolution, +/- 200 mV accuracy in 0-10 VDC applications
Input/Output: Fixed Screw Terminal Blocks
SA/FC Bus and Supply Power: 4-Wire and 3-Wire Pluggable Screw Terminal Blocks
SA/FC Bus Port: RJ-12 6-Pin Modular Jacks
Horizontal on single 35 mm DIN rail mount (preferred), or screw mount on flat surface with three integral mounting clips on controller
21IOM47 Input/Output Module Installation Instructions
Table 10: IOM4711-X Technical Specifications
Housing
Dimensions(Height x Width x Depth)
Compliance
Enclosure material: ABS and polycarbonate UL94 5VB; Self-extinguishing, Plenum Rated
Protection Class: IP20 (IEC 60529)
150 x 190 x 53 mm (5-7/8 x 7-1/2 x 2-1/8 in.) including terminals and mounting clips Note: Mounting space requires an additional 50 mm (2 in.) space on top, bottom and front face of controller for easy cover removal, ventilation and wire terminations.
0.5 kg (1.1 lb)Weight
United States: UL Listed, File E107041, CCN PAZX, UL 916, Energy Management Equipment; UL Listed, File S4977, UUKL 864 - 10th Edition, Smoke Control Equipment (MS-IOU4710-0U and MS-IOM4711-0U models only)
FCC Compliant to CFR47, Part 15, Subpart B, Class A
Canada: UL Listed, File E107041, CCN PAZX7 CAN/CSA C22.2 No.205, Signal Equipment
Industry Canada Compliant, ICES-003
Europe: Johnson Controls declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive.
Note: Conducted RF Immunity within EN 61000-6-2 meets performance criteria B.
Australia and New Zealand: RCM Mark, Australia/NZ Emissions Compliant
BACnet International: BACnet Testing Laboratories (BTL) Protocol Revision 4
Listed BACnet Application Specific Controller (B-ASC)
The performance specifications are nominal and conform to acceptable industry standard. For application at conditions
beyond these specifications, consult the local Johnson Controls® office. Johnson Controls shall not be liable for
damages resulting from misapplication or misuse of its products.
APAC Single Point of Contact:NA/SA Single Point of Contact:European Single Point of Contact:
JOHNSON CONTROLS
WESTENDHOF 3
45143 ESSEN
GERMANY
JOHNSON CONTROLS
507 E MICHIGAN ST
MILWAUKEE WI 53202
USA
JOHNSON CONTROLS
C/O CONTROLS PRODUCT MANAGEMENT
NO. 22 BLOCK D NEW DISTRICT
WUXI JIANGSU PROVINCE 214142
CHINA
507 E. Michigan Street, Milwaukee, WI 53202
Johnson Controls® is a registered trademark of Johnson Controls.
All other marks herein are the marks of their respective owners.© 2018 Johnson Controls
Building Technologies & Solutions
www.johnsoncontrols.comPublished in U.S.A.
22IOM47 Input/Output Module Installation Instructions
Loading...